5x16mm2 5 Cores Cable Copper Xlpe Insulated Armoured For Building MEP Works
Product Summary
Product Details
5x16mm2 5 Core Cable
,5 Core Cable flame retardant
,MEP Works xlpe insulated armoured cable
Product Description
5*16mm² Flame Retardant Power Cable ZR-YJV Copper Conductor for Building MEP Works
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Class C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
Polyvinyl chloride (PVC) sheath |
|
5×16 mm² |
Five equal cores of 16 mm² copper conductor |
Construction: Five 16 mm² copper conductors (3 phase + 1 neutral + 1 earth), XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).
Applicable Standards
- GB/T 12706.1-2020 / IEC 60502-1 — Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV) — Part 1: Cables for rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV)
- GB/T 19666-2019 — Flame retardant and fire resistant wires and cables
- GB/T 18380.12 / IEC 60332-1-2 — Flame propagation test for a single vertical insulated wire
- GB/T 3956-2008 / IEC 60228 — Conductors of insulated cables
- GB/T 2951-2008 / IEC 60811 — Common test methods for insulating and sheathing materials
ZC-YJV 5×16 mm² — LV Flame-Retardant Five-Core TN-S Small Feeder Cable — Specification
1. Overview & Ratings. ZC-YJV 5×16 is a five-core LV small feeder rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C PVC sheath: five equal 16 mm² compacted copper cores (L1/L2/L3 plus neutral N and separate protective PE), dry-cured XLPE, unarmored. OD ≈ 18 mm, ≈ 1100 kg/km (est.), ≈ 68 A per core free air at 30 °C (est.). Scope: TN-S socket groups, small motor/fan-pump feeders and lighting board out-feeds — not 950°C fire duty.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Phase cores L1/L2/L3 | 3×16 compacted Cu, Class 2, ≈7 strands | Phases; R ≤1.15 |
| Neutral N | 1×16 compacted Cu, equal | Separate return; distinct from PE |
| Protective PE | 1×16 compacted Cu, dedicated | TN-S safety earth |
| Strand compaction | Concentric layers rolled compact per core | Compact round bundle, clean lugs |
| XLPE insulation | Dry-cured PE, ≈1.2 mm on each core | Uniform 90°C dielectric |
| Five-core laying | Equal cores into round bundle | Compact round cable |
| PVC ZC sheath | Class C, ≈1.6 mm overall | Self-extinguishes, prints clear |
3. Electrical Characteristics. All five cores R ≤ 1.15 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 68 A per core (est., air 30 °C); short-circuit ≈ 2.3 kA / 1 s (est.); 50/60 Hz; unscreened; separate N and PE; low-loss XLPE; high stable insulation resistance.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 1.15 Ω/km per core |
GB/T 3956 Class 2 Cu max (16 mm²) |
|
AC resistance @90 °C (est.) |
≈ 1.47 Ω/km per core |
— |
|
Current rating in air (30 °C) |
3-phase: 75 A |
5×16, touching, in free air |
|
Current rating in tray (30 °C) |
3-phase: 84 A |
5×16, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
3-phase: 78 A |
direct buried |
|
Current rating in conduit (30 °C) |
3-phase: 67 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 1.76 kA (1,760 A) per core |
— |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.16 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.08 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 5×16 at 75 A three-phase, 400 V → max load ≈ 45 kW (cos φ = 0.8). Suitable for extra-light to light three-phase distribution with full neutral and earth (TN-S), control panels, and building final branch circuits.
4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; withstands feeder cycling; indoor preferred, UV jacket optional.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. Hydraulic crimp 16 mm² lugs on all five cores, glands to ≈18 mm OD, torque per table; bend ≥ 15×OD ≈ 270 mm; keep N and PE distinct; apply conduit fill derating; verify continuity of all cores, phase sequence, N/PE separation and insulation before energizing.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 263 mm at Ø17.5 mm |
five-core unarmoured |
|
Max. pulling tension |
240 N per core (16 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Cable tray, ladder, cleats |
— |
|
Conduit ID |
≥ 32 mm |
— |
|
Fixing |
cable ties, small cleats |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Typical Service Applications. TN-S socket groups, small motors and fan/pump feeders, lighting sub-board out-feeds, and small equipment requiring a dedicated protective earth.

7. Testing & QA Regime (16 items). Routine: DC resistance all cores, 3.5 kV withstand, insulation resistance, continuity, insulation thickness, sheath thickness, dimensional check, strand construction, core color coding, N/PE separation check, print legibility, mass, packing inspection. Type: ZC flame test, short-circuit rating, sheath mechanical.
Cable Parameters
| ZR-YJV 5×16 mm² — Flame-Retardant Five-Core Power Cable (0.6/1 kV) · Product Parameters | ||||
| CU / XLPE / PVC · 5 × 16 mm² · GB/T 12706.1, IEC 60502-1, GB/T 3956, GB/T 19666 · nominal values for reference | ||||
| Code | Parameter | Value | Unit | Remarks |
| 01 · Identification | ||||
| Std: GB/T 12706.1 / IEC 60502-1; fire GB/T 19666; Um = 1.2 kV; 50 Hz | ||||
| 1-A | Product name | Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable (five-core) | — | ZR-YJV; halogen-containing flame-retardant |
| 1-B | Model | ZR-YJV 5×16 | — | 5 cores × 16 mm²; CU / XLPE / PVC |
| 1-C | Design standards | GB/T 12706.1; IEC 60502-1 | — | Conductor GB/T 3956 |
| 1-D | Rated voltage U0/U | 0.6/1 | kV | Um = 1.2 kV; AC 50 Hz |
| 1-E | Core arrangement | 5 cores (L1/L2/L3/N/PE) | — | Three phases + neutral + earth |
| 1-F | Nominal cross-section | 16 | mm² | Per core, GB/T 3956 |
| 02 · Conductor | ||||
| Std: GB/T 3956 / IEC 60228 Class 2 — 16 mm² = 7 wires (round) | ||||
| 2-A | Material | Plain annealed copper | — | High conductivity |
| 2-B | Class | Class 2 (stranded) | — | GB/T 3956 / IEC 60228 |
| 2-C | Stranding (per core) | 7 × 1.70 mm (7/1.70) | — | 1+6 concentric rings |
| 2-D | Conductor diameter | ≈ 5.1 | mm | Per core (7 × 1.70) |
| 2-E | Max. DC resistance @ 20 °C | 1.15 | Ω/km | GB/T 3956 Class 2 Cu |
| 03 · Insulation | ||||
| Std: Mingda five-core unarmored table — 1.0 mm wall at 16 mm² (five-core step) | ||||
| 3-A | Material | Cross-linked polyethylene (XLPE) | — | Thermally cross-linked |
| 3-B | Nominal thickness | 1.0 | mm | Mingda five-core table |
| 3-C | Diameter over insulation | ≈ 7.1 | mm | Per core (calculated) |
| 04 · Assembly | ||||
| Std: pentagonal ring lay-up; filler takes the residual gap | ||||
| 4-A | Core lay-up | Five cores in a pentagonal ring + dry filler + binder tape | — | Round bundle |
| 4-B | Diameter over lay-up | ≈ 19.2 | mm | Calculated |
| 05 · Sheath | ||||
| Std: Mingda five-core unarmored table (Ø 22; 978.8 / 470.3 kg/km) | ||||
| 5-A | Material | Flame-retardant PVC, ST2 | — | Black (or as ordered) |
| 5-B | Nominal thickness | 1.8 | mm | Mingda five-core table |
| 5-C | Overall diameter | ≈ 22 | mm | Mingda five-core unarmored |
| 5-D | Approx. cable weight | ≈ 978.8 | kg/km | Mingda 978.8 (YJLV ≈ 470.3) |
| 06 · Electrical | ||||
| Std: Mingda five-core unarmored table (soil 105 / air 83 A Cu @ 25 °C) | ||||
| 6-A | DC conductor resistance | 1.15 | Ω/km | GB/T 3956 @ 20 °C, per core |
| 6-B | Routine voltage test | 3.5 kV / 5 min | — | No breakdown; 50 Hz AC |
| 6-C | Insulation resistance | ≥ 36.7 | MΩ·km | Finished cable @ 20 °C |
| 6-D | XLPE volume resistivity | ≥ 1 × 10¹² | Ω·cm | Material level |
| 6-E | Capacitance (approx.) | ≤ 0.45 | μF/km | Per core |
| 6-F | Ampacity — buried @ 25 °C (5 cores) | ≈ 105 | A | Mingda basis (Cu) |
| 6-G | Ampacity — air @ 25 °C (5 cores) | ≈ 83 | A | Mingda basis (Cu) |
| 07 · Thermal | ||||
| Std: XLPE class per GB/T 12706.1 / IEC 60502-1 | ||||
| 7-A | Continuous conductor temperature | 90 | °C | XLPE class |
| 7-B | Short-circuit temperature (≤ 5 s) | 250 | °C | GB/T 12706.1 / IEC 60502-1 |
| 7-C | Ambient service range | -20 to +45 | °C | Per datasheet family |
| 7-D | Min. laying temperature | 0 | °C | Pre-heat below 0 °C |
| 08 · Fire (ZR) | ||||
| Std: GB/T 19666; GB/T 18380.12; GB/T 18380.35 (20 min, ≥ 1.5 L/m) | ||||
| 8-A | Flame-retardant class | ZC by default ("ZR") | — | Halogen-containing PVC |
| 8-B | Single-cable flame test | Pass | — | GB/T 18380.12 |
| 8-C | Bunched flame test — class C | Char ≤ 2.5 m | — | GB/T 18380.35 |
| 8-D | Halogen content | Halogen-containing | — | LSZH needs WDZ-YJY |
| 09 · Installation | ||||
| Std: Q/GDW 13244.1-2018 for site test | ||||
| 9-A | Min. bending radius (multi-core) | ≥ 15 × OD | — | GB 50168 practice |
| 9-B | Laying methods | Conduit, tray, trench, duct, trunking | — | Mechanical protection where buried |
| 9-C | Site test after installation | DC 4U0 = 2.4 kV / 15 min | — | Q/GDW 13244.1-2018 |
| 10 · Packing | ||||
| Std: custom lengths available; GB/T 6995 / project spec | ||||
| 10-A | Standard delivery length | 100 m per coil/drum | — | Custom lengths available |
| 10-B | Marking | Model, voltage, maker, year, length marks | — | GB/T 6995 / project spec |
Cable Test Parameters
| ZR-YJV 5×16 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1) | ||||
| Stage | Test Item | Method / Standard | Acceptance Criterion | Notes |
| Routine | Conductor DC resistance | GB/T 3956 (IEC 60228) | ≤ 1.15 Ω/km @ 20 °C (per core) | Every production length |
| Routine | Power-frequency withstand voltage | GB/T 12706.1 / IEC 60502-1 | 3.5 kV AC / 5 min, no breakdown | Conductor-to-earth/water |
| Routine | Construction check | GB/T 2951 | Ins. ≥ 1.0 mm; sheath ≥ 1.8 mm; OD within tolerance | Thickness & diameter |
| Sample | Hot set test — XLPE | GB/T 12706.1 §16.3.13 / GB/T 2951.11 | 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % | Cross-linking degree |
| Sample | Conductor construction & diameter | GB/T 3956 | Class 2; 7 × 1.70 mm; Ø ≈ 5.1 mm | Per batch |
| Type | Single-cable flame test | GB/T 18380.12 | No flame spread to top reference | ZR property |
| Type | Bunched flame test — class C | GB/T 18380.35 | Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m | ZC class |
| Type | Bending test | GB/T 12706.1 | No damage on specified mandrel | Multi-core rule |
| Post-install | DC withstand test | Q/GDW 13244.1-2018 | 2.4 kV DC / 15 min, no breakdown | New installations |
| Optional | Insulation resistance @ 20 °C | Factory method | ≥ 36.7 MΩ·km | Not routine in GB/T 12706.1 |
| Optional | XLPE volume resistivity | Material test | ≥ 1 × 10¹² Ω·cm | Material reference |
Cable Cross Section Structure

| ZR-YJV 5×16 mm² — Cable Cross-Section Structure (Schematic) | |||||
| Five-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor (Cu) × 5 | Annealed copper, Class 2 stranded — 7 × 1.70 mm per core (7/1.70, 1+6), nominal 16 mm² per core | — | ≈ 5.1 (Ø per core) | Current-carrying element; max DC resistance ≤ 1.15 Ω/km @ 20 °C (per core) |
| 2 | Insulation (XLPE) × 5 | Cross-linked polyethylene | 1 | ≈ 7.1 (Ø per core, over insulation) | Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min |
| 3 | Core lay-up | Five insulated cores laid up in a pentagonal ring around dry filler; binder tape | — | ≈ 19.2 (Ø over lay-up, calc.) | Round assembly; the 5th core is the PE (earthing) core |
| 4 | Outer sheath (PVC) | Flame-retardant PVC, ST2 type, black | 1.8 | ≈ 22 (Ø overall, Mingda five-core) | Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666 |
| Key Dimensions & Properties | |||||
| Overall diameter | ≈ 22 | mm | Mingda five-core unarmored table | ||
| Approx. cable weight | ≈ 978.8 | kg/km | Mingda 978.8 (Al ≈ 470.3) | ||
| Rated voltage | 0.6/1 | kV | AC 50 Hz; max system voltage Um = 1.2 kV | ||
| Max conductor temperature | 90 / 250 | °C | Continuous / short-circuit (≤ 5 s) | ||
| Min. bending radius (multi-core) | ≥ 15 × OD | — | OD = actual cable diameter | ||
| Flame-retardant class | ZC (ZR) | — | GB/T 19666 | ||
| Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate. | |||||
Product Structure Introduction
| Product Structure Introduction — ZR-YJV 5×16 mm² | |||
| Five-core layered construction description, from conductor to outer sheath · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV | |||
| 1. Overview & Ratings | |||
| ZR-YJV 5×16 is the second size of the flame-retarding five-core family: five 16 mm² copper conductors, XLPE insulation and one ST2 PVC jacket, rated 0.6/1 kV. Production and testing follow GB/T 12706.1 / IEC 60502-1, stranding follows GB/T 3956, and the ZR (ZC) fire class of GB/T 19666 is standard. Finished diameter ≈ 22 mm (Mingda five-core row), weight ≈ 978.8 kg/km; 100 m coils or drums. | |||
| Five cores loaded, the cable is rated ≈ 83 A in air at 25 °C on the Mingda basis — sized for lighting, small power and control feeders where a separate PE core is required. | |||
| 2. Copper Stranded Conductor | |||
| Each 16 mm² core strands seven 1.70 mm annealed wires (7/1.70) in the 1+6 pack — the Class 2 pack for this section — to ≈ 5.1 mm Ø. DC resistance is capped at 1.15 Ω/km at 20 °C; the tight 1+6 arrangement yields a clean circular profile for the 1.0 mm insulation wall and compact terminations. | |||
| 3. XLPE Dielectric Layer | |||
| XLPE is extruded at 1.0 mm — the wall Mingda's five-core table assigns to 16 mm², thicker than the 0.7 mm of the three/four-core step — giving ≈ 7.1 mm per core over the insulation. The dielectric is rated 90 °C continuously and 250 °C for five seconds, holds volume resistivity ≥ 1×10¹² Ω·cm and passes the 3.5 kV AC five-minute routine proof. | |||
| 4. Cabling & PVC Sheath | |||
| Five insulated cores are cabled in a pentagonal ring with dry filler and binder tape into a ≈ 19.2 mm bundle, then sheathed in 1.8 mm of flame-retarded ST2 PVC to the published 22 mm finish. The jacket delivers ZC behaviour via GB/T 18380.12 and GB/T 18380.35; since PVC contains halogen, low-smoke orders move to WDZ-YJY. | |||
| 5. Field Handling & Usage | |||
| • Respect the 15 × OD bending floor. • Apply the DC 4U0 = 2.4 kV / 15 min site test before first energisation. • Service ambient −20 to +45 °C; warm drums below 0 °C before pulling. • Derate the 83 A (air) / 105 A (buried) reference for ambient, grouping and soil. • Use lugs and glands sized for the 5.1 mm core and 22 mm sheath. |
8. Factory Advantages.
- Dedicated TN-S safety — separate N and PE cores for compliant earthing.
- Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent.
- Dosed ZC compound — self-extinguishing jacket protects socket circuits and panel rooms.
- Length-on-demand — cut to exact feeder meter with sealed ends.
- Uniform resistance log — all five equal cores R recorded to lot.
- Continuous print line — type, size, ZC, voltage and length readable along runs.
- Color-coded cores — phase, neutral and PE distinguished at terminals.
- Lightweight compact drum — small section easy to pull and handle.
- Certified QA pack — routine + type test record shipped per batch.

9. Packaging, Storage & Logistics. Cut to measured feeder length on a compact wooden drum with sealed ends; continuous marking; store dry indoor on drum supports, shaded, avoid direct UV.

10. Procurement Specification. State "ZC-YJV 5×16", length, class C and the TN-S requirement; request resistance log and 16-item QA record. Est. values confirmed against the factory certificate.
11. Cable Industry FAQ.
- Q1: How does 5×16 differ from 4×70? A five-wire TN-S small feeder rather than a heavy four-core power cable: five 16 mm² equal cores vs four 70; R 1.15 vs 0.268 Ω/km, current ≈68 vs 175 A; aimed at socket groups and small motors with a dedicated PE rather than heavy power distribution.
- Q2: Why a separate PE core? TN-S keeps neutral and protective earth distinct; required where safety earth must remain separate from the neutral conductor.
- Q3: Is ZC fire-resistant? No. Class C self-extinguishes; it does not hold live at 950°C/180min.
- Q4: DC resistance? ≤1.15 Ω/km at 20°C on every 16 mm² core.
- Q5: Screen or armor? Unscreened standard; add braid near VFD EMI; armor for ground-crushing ducts.
- Q6: Current per core? ≈68 A (est.) free air 30°C; derate for conduit fill.
- Q7: Bending? ≈270 mm (15×OD); small section bends easily in conduit.
- Q8: Connectors? 16 mm² lugs on all five cores; gland to ≈18 mm OD.
- Q9: Indoor or outdoor? Indoor preferred; specify UV-stabilized jacket for exposed runs.
- Q10: Packing? Compact wooden drum with moisture-sealed ends.
- Q11: What proof ships? Resistance log + 16-test record; est. values confirmed against certificate.