ZR-YJV 2*25mm² Flame Retardant Copper Cable,0.6/1kV XLPE Insulation PVC Sheath for Power Distribution Code Mean:ZR-Flame Retardant,YJ-XLPE Insulation,V-PVC Outer Sheathed. ZR-YJV 2×25 mm² — Product Data Review 1. Product Summary. ZR-YJV 2×25 is a two-core flame-retardant power cable — twin 25 mm² ...

Product Details

Highlight:

Class 2 2 Core Cable

,

25mm 2 core cable Flame Retardant

,

Power Distribution pvc cable sheath

Conductor (×2):
Bare Annealed Copper, Class 2 Stranded, 7×∅2.14 Mm, Conductor Ø ≈ 6.4 Mm
Conductor nominal area:
25 Mm²
Number of cores:
2
Conductor construction:
Class 2, 7×∅2.14 Mm,min. 7 Wires
Conductor diameter (approx.):
6.4mm
Insulation (×2):
XLPE,
Insulation thickness:
0.9 Mm (25 Mm² Class)
Diameter over insulated core:
8.2 Mm (6.4 + 2×0.9)
Filler:
Flame-retardant PP/PE To Form Round Assembly
Binder:
Flame-retardant Tape Over Laid-up Cores
Outer sheath:
Flame-retardant PVC (ZR Grade)
Sheath thickness:
1.8 Mm (multi-core Rule, ≥1.8 Mm)
Overall cable diameter:
19.0 – 19.8 Mm Use 19.4 Mm For Design
Approx. weight:
480 – 540 Kg/km Use ≈ 510 Kg/km
Long-term service temp.:
90 °C
Short-circuit temp. (≤5 s):
250°C
Emergency overload:
105–130 °C
Routine test:
3.5 KV AC / 5 Min; Type Test 4.0 KV
Volume resistivity @90 °C:
≥ 10¹² Ω·cm

Product Description

ZR-YJV 2*25mm² Flame Retardant Copper Cable,0.6/1kV XLPE Insulation PVC Sheath for Power Distribution

 

Code Mean:ZR-Flame Retardant,YJ-XLPE Insulation,V-PVC Outer Sheathed.

 

ZR-YJV 2×25 mm² — Product Data Review

1. Product Summary. ZR-YJV 2×25 is a two-core flame-retardant power cable — twin 25 mm² copper conductors, XLPE insulation, PVC sheath, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz. It complies with GB/T 12706.1 / IEC 60502-1, GB/T 3956 / IEC 60228 (core) and GB/T 19666 / GB/T 18380 (fire, default ZC).

 

2. Construction Overview. Core-to-jacket stack:

Layer Build Wall Diameter
Conductor (×2) Annealed copper, Class 2, 7 × 2.14 mm (7/2.14) each, 25 mm² per core — ≈ 6.4 mm per core
Insulation (×2) Cross-linked polyethylene 0.9 mm ≈ 8.2 mm per core (over ins.)
Lay-up Two cores + non-hygroscopic filler, optional binder tape — ≈ 16.4 mm
Sheath Flame-retarded PVC, ST2, black 1.8 mm ≈ 20.0 mm overall

Weight ≈ 659 kg/km (Al version ≈ 329).

 

Class 2 25mm2 2 Cores Cable Flame Retardant Copper Cable Xlpe Insulation Pvc Sheath

 

3. Electrical Ratings. DC resistance ≤ 0.727 Ω/km per core @ 20 °C; routine 3.5 kV / 5 min; XLPE volume resistivity ≥ 1×10¹² Ω·cm; typical insulation resistance ≥ 36.7 MΩ·km; capacitance ≤ 0.45 μF/km per core. Reference ampacity (both cores loaded) ≈ 150 A in air (30 °C) and ≈ 191 A direct-buried (20 °C) per Chengtantai; Mingda's armored YJV22 table quotes 128 A @25 °C — derate per GB/T 16895 / IEC 60364.

 

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502

DC resistance @20 °C (Class 2 Cu, per core)

≤ 0.727 Ω/km

GB/T 3956 max

AC resistance @90 °C (est.)

≈ 0.945 Ω/km

per core

Current rating in air (30 °C, single circuit, 2-core)

≈ 90 – 100 A

design ≈ 95 A

Direct buried (20 °C, soil 1.0 K·m/W, 0.7 m)

≈ 115 – 125 A

design ≈ 120 A

Short-circuit current (1 s, Cu, 250 °C, per core)

≈ 2.50 kA

reference

Frequency

50/60 Hz AC (DC usable)

—

 

4. Thermal & Bending. Continuous 90 °C; short-circuit 250 °C (≤ 5 s); ambient −20 to +45 °C; laying ≥ 0 °C; minimum bend radius ≥ 15 × OD (multi-core).

 

ZR-YJV 2×25 mm² Flame-Retardant Copper-Conductor XLPE-Insulated PVC-Sheathed Power Cable — Product Parameters (0.6/1 kV, Two-Core)
Construction: CU / XLPE / PVC, 2 cores  •  Standards: GB/T 12706.1, IEC 60502-1 (cable), GB/T 3956 (conductor), GB/T 19666 & GB/T 18380 (flame retardance)  •  Nominal values for reference — confirm against factory test certificate
No. Category Parameter Value Unit Notes / Standard Reference
A. Product Identification
1 Identification Product name Flame-retardant copper-conductor XLPE-insulated PVC-sheathed power cable (two-core) — Designation ZR-YJV; "ZR" = flame-retardant (halogen-containing)
2 Identification Model designation ZR-YJV 2×25 — 2 cores × 25 mm²; Cu / XLPE / PVC
3 Identification Design standards GB/T 12706.1; IEC 60502-1 — Conductor: GB/T 3956 / IEC 60228; flame retardance: GB/T 19666, GB/T 18380; safety: CCC / production licence
4 Identification Rated voltage U0/U 0.6/1 kV Max system voltage Um = 1.2 kV
5 Identification Rated frequency 50 Hz AC power distribution
6 Identification Number of cores 2 — Two-core cable, both cores live (phase + neutral / L + N applications)
7 Identification Nominal cross-sectional area 25 mm² Per core; nominal cross-section per GB/T 3956
B. Cable Construction (from conductor to outer sheath)
8 Conductor Material Plain annealed copper (Cu) — High-conductivity electrolytic / oxygen-free copper
9 Conductor Conductor class Class 1 or Class 2 (typical: Class 2, stranded) — GB/T 3956 / IEC 60228
10 Conductor Typical stranding construction (per core) 7 wires × 2.14 mm (7/2.14) — Class 2 round stranded; nominal section 25 mm² per core
11 Conductor Conductor diameter (per core) ≈ 6.4 mm Ø of the 7/2.14 stranded core (6.0–6.4 mm across practice)
12 Conductor Max. DC resistance of conductor at 20 °C 0.727 Ω/km GB/T 3956, Class 2 copper; acceptance criterion for 25 mm²
13 Insulation Material Cross-linked polyethylene (XLPE) — Thermally cross-linked; natural/transparent colour
14 Insulation Nominal insulation thickness 0.9 mm GB/T 12706.1 / IEC 60502-1 (0.6/1 kV, 25 mm²)
15 Insulation Diameter over insulation (per core) ≈ 8.2 mm ≈ 6.4 + 2 × 0.9 (calculated)
16 Lay-up Core assembly Two insulated cores laid up with non-hygroscopic filler; optional binder tape — Round construction, right-hand lay
17 Sheath Material Flame-retardant polyvinyl chloride (PVC, ST2 type) — Colour: black (or as ordered)
18 Sheath Nominal sheath thickness 1.8 mm GB/T 12706.1 / IEC 60502-1 (ahtk & Mingda tables agree)
19 Dimensions Approx. overall diameter 20.0 mm ≈ 20.0 mm (ahtk 20.0; Chengtantai 19.8)
20 Dimensions Approx. cable weight ≈ 659 kg/km ahtk 659 (aluminium version ≈ 329 kg/km); armored YJV22 2×25 ≈ 863 kg/km
C. Electrical Performance
21 Electrical Max. DC conductor resistance at 20 °C 0.727 Ω/km GB/T 3956; routine measurement
22 Electrical Power-frequency withstand voltage (routine test) 3.5 kV / 5 min, no breakdown — AC 50 Hz; per GB/T 12706.1 / IEC 60502-1
23 Electrical Insulation resistance (finished cable, 20 °C) ≥ 36.7 MΩ·km Typical finished-cable reference for 0.6/1 kV XLPE cables; varies with geometry and manufacturer test method
24 Electrical XLPE volume resistivity at 20 °C ≥ 1 × 10¹² Ω·cm Material-level requirement (manufacturer reference)
25 Electrical Capacitance (approx., per core) ≤ 0.45 μF/km Manufacturer reference value
26 Electrical Reference ampacity — in air, 30 °C, both cores loaded ≈ 150 A Chengtantai two-core table (150 A Cu); applies to the cable as a whole; Mingda armored YJV22 quotes 128 A @25 °C — derate per GB/T 16895 / IEC 60364
27 Electrical Reference ampacity — direct burial, 20 °C ≈ 191 A Chengtantai two-core table (191 A Cu); depends on soil thermal resistivity and depth
D. Thermal Performance
28 Thermal Max. continuous conductor temperature 90 °C XLPE insulation temperature class
29 Thermal Max. conductor temperature under short-circuit (≤ 5 s) 250 °C Per GB/T 12706.1 / IEC 60502-1
30 Thermal Ambient service temperature range -20 to +45 °C Per Qifan datasheet family; check project specification
31 Thermal Min. installation (laying) temperature 0 °C Pre-heat the cable if ambient is below 0 °C
E. Flame Retardance (ZR)
32 Flame retardance Flame-retardant class ZC (class C) by default for "ZR" — GB/T 19666; ZA / ZB available on request; halogen-containing PVC (not LSZH)
33 Flame retardance Single-cable vertical flame-spread test Pass — GB/T 18380.12
34 Flame retardance Bunched flame-spread test (class C) Char extent ≤ 2.5 m above burner bottom edge — GB/T 18380.35: non-metallic volume ≥ 1.5 L/m; flame application 20 min
35 Flame retardance Halogen content Halogen-containing (PVC) — For low-smoke, zero-halogen requirement select WDZ-YJY (LSZH) type
F. Installation
36 Installation Min. bending radius — multi-core cable ≥ 15 × OD — GB 50168 practice for multi-core XLPE cables (Chengtantai lists 15 × OD = 297 mm); OD = actual cable diameter
37 Installation Laying methods Conduit, tray, cable trench, duct, building trunking, supported/suspended aerial — Also direct burial with mechanical protection where permitted
38 Installation Site withstand test after installation DC 4U0 = 2.4 kV, 15 min (recommended) — Per utility procurement standard Q/GDW 13244.1-2018; practice may vary by project
G. Packing & Delivery
39 Packing Standard delivery length 100 m per coil/drum (or as ordered) — Typical industry practice; custom lengths available
40 Packing Cable marking Model, rated voltage, manufacturer, year of manufacture, sequential length marks — Per GB/T 6995 / project specification
41 Packing Packing form Coil (carton drum) / wooden drum / export packing — As per customer requirement

 

5. Fire Behaviour. Passes GB/T 18380.12 single burn and class-C bunched burn GB/T 18380.35 (char ≤ 2.5 m) → ZC per GB/T 19666. PVC contains halogen — WDZ-YJY for LSZH duty.

 

Technical Datasheet - ZR-YJV 0.6/1 kV 2x25 mm² - Flame-Retardant (FR) Characteristics
Cable Designation: ZR (Flame Retardant, Class C) | YJ (XLPE Insulation) | V (PVC Sheath) | 2x25 mm² (2 cores x 25 mm² Cu)
 
1. Cable Identification
Code Meaning Standard / Reference Notes
ZR Legacy prefix for flame retardant (Class C) GB/T 19666-2019 Modern equivalent: ZC
YJ XLPE (cross-linked polyethylene) insulation GB/T 12706.1-2020 (IEC 60502-1) Long-term 90 °C
V PVC outer sheath (flame-retardant grade, contains halogen Cl) GB/T 19666-2019 Not low-smoke
0.6/1 kV Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV IEC 60502-1 —
2x25 mm² Two cores, nominal copper conductor area 25 mm² per core GB/T 3956 (IEC 60228) Class 2 stranded
 
2. Flame-Retardant (FR) & Fire Performance Characteristics
Property Value / Requirement Test Standard Class / Grade Remarks
Flame retardant class Class C (bundled combustion) GB/T 19666-2019 Class C Legacy ZR defaults to C
Bunched flame test Char length ≤ 2.5 m GB/T 18380.3 (IEC 60332-3) Class C Cable bundle test
Single flame test Self-extinguishing IEC 60332-1 Pass Flame spread limited
Halogen content Contains chlorine (Cl) - PVC sheath GB/T 17650 (IEC 60754) Halogenated Produces HCl gas
Smoke density Heavy dark smoke (not low-smoke) GB/T 17651 (IEC 61034) Not LS LSZH option: WDZ-YJY
Gas corrosivity Corrosive HCl gas released GB/T 17650 (IEC 60754) Corrosive pH / conductivity not certified
Acid gas emission High (HCl) IEC 60754-1 / -2 — Not for enclosed spaces
Oxygen index (LOI) ≥ 30 % (typical for FR-PVC) GB/T 2406 (IEC 4589) ≥ 30 % Reference value
Max. conductor temp. (normal) 90 °C IEC 60502-1 — XLPE insulation
Max. short-circuit temp. (≤5 s) 250 °C IEC 60502-1 — Cu conductor
Emergency overload temp. 105 - 130 °C IEC 60502-1 — Short duration
Min. installation temp. 0 °C (pre-heat below 0 °C) Manufacturer spec. — Ambient
 
3. Fire Test Summary (ZR = Class C)
Test Item Requirement Result (Typical) Verdict Alternative (if required)
Bunched flame propagation Char ≤ 2.5 m @ Class C Char ≈ 1.8 m Pass —
Single vertical flame No flame spread after removal Self-extinguishing Pass —
Smoke opacity (light transmittance) Not low-smoke (PVC) Heavy smoke N/A WDZ-YJY (LS)
Halogen / acid gas Cl present (PVC) HCl released N/A WDZ-YJY (HFFR)
Fire survival (circuit integrity) Not certified — Fail / N/A NH-ZR-YJV (NH = fire-resistant)
 
4. Key Electrical & Thermal Parameters (Reference)
Parameter Value Unit Standard Notes
Rated voltage U₀/U 0.6 / 1 kV IEC 60502-1 Uₘ = 1.2 kV
DC resistance @ 20 °C (per core) ≤ 0.727 Ω/km GB/T 3956 Class 2 Cu
AC resistance @ 90 °C (est.) ≈ 0.945 Ω/km — Per core
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1 Routine test
Type-test voltage 4.0 kV IEC 60502-1 Type test
Current rating - in air (30 °C) ≈ 95 A Design value Single circuit, 2-core
Current rating - buried (20 °C) ≈ 120 A Design value Soil 1.0 K·m/W, 0.7 m
 
5. Construction & Material (Impact on FR Performance)
Layer (inside -> outside) Description Material / Spec. Flame Retardant? Thickness
Conductor (x2) Bare annealed copper, Class 2 stranded 7xØ2.14 mm, IEC 60228 No —
Insulation (x2) XLPE, colours red/black/blue 90 °C, 0.9 mm nom. Yes (XLPE) 0.9 mm
Filler Flame-retardant filler to form round assembly FR PP / PE Yes —
Binder Flame-retardant tape over laid-up cores FR tape Yes —
Outer sheath Flame-retardant PVC (ZR grade), black FR-PVC, black Yes (FR-PVC, Class C) 1.8 mm
Armour / Screen None — — —
 
6. Selection Guide (When FR Requirement Matters)
Requirement Recommended Cable Why Smoke Halogen
Standard flame retardant (this cable) ZR-YJV 2x25 Class C FR-PVC Heavy Yes (Cl)
Low-smoke halogen-free WDZ-YJY 2x25 LSZH sheath, low smoke Low No
Fire survival (circuit integrity) NH-ZR-YJV 2x25 Mica tape for fire resistance Heavy Yes (Cl)
Heavy mechanical load / burial ZR-YJV22 2x25 Steel tape armour Heavy Yes (Cl)
Notes: (1) ZR is a legacy designation; under GB/T 19666-2019 it defaults to Flame Retardant Class C (modern equivalent ZC). (2) PVC-sheathed (V) cables contain halogen (Cl) and produce corrosive HCl gas with heavy smoke when burned - not suitable for enclosed or populated areas; use WDZ-YJY for LSZH. (3) Values are typical/reference; confirm with manufacturer's test reports before specification. (4) HS Code (China): 8544.4921.

 

6. Verification. Routine: resistance, 3.5 kV/5 min, dimension audit (ins. ≥ 0.9 mm, sheath ≥ 1.8 mm). Sample: XLPE hot-set (200 ± 3 °C / 15 min / 0.2 MPa). Type: flame + bending. Site: DC 4U0 = 2.4 kV / 15 min (Q/GDW 13244.1-2018).

 

ZR-YJV 2×25 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Test Stage Test Item Method / Standard Requirement / Acceptance Criterion Notes
Routine test Conductor DC resistance measurement GB/T 3956 (IEC 60228) ≤ 0.727 Ω/km at 20 °C (per core) Measured on every production length
Routine test Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC, 5 min, no breakdown Applied between each conductor and earth/water; 50 Hz
Routine test Construction check — insulation & sheath thickness, outer diameter GB/T 2951 Within GB/T 12706.1 tolerances Insulation ≥ 0.9 mm nominal; sheath ≥ 1.8 mm nominal
Sample test Hot set (thermal elongation) test — XLPE insulation GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, stress 0.2 MPa: elongation under load ≤ 175 %; permanent elongation after cooling ≤ 15 % Verifies degree of cross-linking
Sample test Conductor construction & diameter check GB/T 3956 Class 2; 7 × 2.14 mm; Ø ≈ 6.4 mm Sampled per batch
Type test Single-cable vertical flame-spread test (flame retardance) GB/T 18380.12 No flame spread; charring does not reach top reference point ZR / ZC flame-retardant property
Type test Bunched flame-spread test, class C GB/T 18380.35 Char extent ≤ 2.5 m above burner bottom edge; flame application 20 min; non-metallic volume ≥ 1.5 L/m Class ZC per GB/T 19666
Type test Bending test (mechanical) GB/T 12706.1 Bend around specified mandrel without insulation/sheath damage Mandrel diameter related to cable OD (multi-core)
Post-installation DC withstand test after installation Q/GDW 13244.1-2018 (recommended practice) 4U0 = 2.4 kV DC, 15 min, no breakdown For new installations; verify project specification
Optional Insulation resistance measurement at 20 °C Manufacturer test method ≥ 36.7 MΩ·km (typical finished-cable value) Not a routine item in GB/T 12706.1; confirm with factory
Optional XLPE volume resistivity at 20 °C Manufacturer / material test ≥ 1 × 10¹² Ω·cm Material-level reference

 

7. Usage Cautions. Bend ≥ 15 × OD; avoid kinks and drag over sharp edges; shield from UV; run the DC site test before energising; load both cores symmetrically; choose lugs sized for the ≈ 6.4 mm core.

 

Class 2 25mm2 2 Cores Cable Flame Retardant Copper Cable Xlpe Insulation Pvc Sheath

 

8.Cross Section Structure

 

Class 2 25mm2 2 Cores Cable Flame Retardant Copper Cable Xlpe Insulation Pvc Sheath

 

ZR-YJV 2×25 mm² — Cable Cross-Section Structure (Schematic)
Two-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
           
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 2 Annealed copper, Class 2 stranded — 7 × 2.14 mm per core (7/2.14), nominal 25 mm² per core — ≈ 6.4 (Ø per core) Current-carrying element; max DC resistance ≤ 0.727 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 2 Cross-linked polyethylene 0.9 ≈ 8.2 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Two insulated cores laid up with non-hygroscopic filler; optional binder tape — ≈ 16.4 (Ø over lay-up) Forms a round assembly for sheathing
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 1.8 ≈ 20.0 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
Key Dimensions & Properties
Overall diameter 20.0 mm ahtk 20.0; Chengtantai 19.8  
Approx. cable weight ≈ 659 kg/km ahtk 659 (Al 329); armored YJV22 2×25 ≈ 863 kg/km
Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV
Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)
Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter
Flame-retardant class ZC (ZR) — GB/T 19666

 

Product Structure Introduction — ZR-YJV 2×25 mm² (English)
Two-core layered construction description, from conductor to outer sheath · per GB/T 12706.1 & IEC 60502-1 · CU / XLPE / PVC · 0.6/1 kV
 
1. Document Introduction
This document introduces ZR-YJV 2×25, a flame-retardant two-core low-voltage power cable rated 0.6/1 kV AC and built on the CU / XLPE / PVC formula. The product follows GB/T 12706.1 / IEC 60502-1, GB/T 3956 / IEC 60228 for conductors and GB/T 19666 (default ZC) for flame retardance. Outer diameter about 20.0 mm, mass ≈ 659 kg/km, delivered in 100 m coils or on drums.
Both cores are identical and live; the cable is designed for fixed wiring and should not be handled as a flexible lead.
 
2. Conductor Construction
Each core is formed by stranding seven annealed copper wires of 2.14 mm (7/2.14) to Class 2, giving 25 mm² per core at a diameter of ≈ 6.4 mm. The per-core DC resistance is limited to 0.727 Ω/km at 20 °C. This size balances capacity and bendability, making the bundle straightforward to pull into conduits and trunking.
 
3. Insulation Construction
Every core is covered by a 0.9 mm XLPE layer, bringing the diameter over insulation to ≈ 8.2 mm. The cross-linked dielectric is rated for 90 °C continuous operation and 250 °C for five seconds under short-circuit, with volume resistivity ≥ 1×10¹² Ω·cm and a production routine of 3.5 kV AC for five minutes.
 
4. Assembly & Sheathing
The two insulated cores are twisted together with non-hygroscopic filler (optionally held by binder tape) into a round bundle of ≈ 16.4 mm. A 1.8 mm flame-retardant PVC (ST2) sheath over the bundle completes the cable at ≈ 20.0 mm. The ZC rating is proven by GB/T 18380.12 (single burn) and GB/T 18380.35 (class C, char ≤ 2.5 m); PVC carries halogen, so WDZ-YJY is the zero-halogen alternative.
 
5. Field Handling Notes
• Keep bends at or above 15 × OD for multi-core routes.  • After installation run the DC 4U0 = 2.4 kV / 15 min site test.  • Ambient −20 to +45 °C; warm the coil below 0 °C.  • Ampacity is quoted per cable — apply grouping and burial derating.  • Confirm the actual core Ø (≈ 6.4 mm) before selecting lugs and glands.

 

9. Application Range. Single-phase feeders, L+N distribution, small sub-boards, pump and HVAC circuits, control supplies at 0.6/1 kV — conduits, trays, trunking, trenches; indoor or sheltered outdoor.

 

Class 2 25mm2 2 Cores Cable Flame Retardant Copper Cable Xlpe Insulation Pvc Sheath

 

10. Ordering Information. ZR-YJV 0.6/1 kV 2×25, length, coil/drum type, marking. Standard 100 m; confirm all figures against the factory certificate.

 