Low Voltage 2 Cores Cable 2 X 10mm2 Stranded Copper Fire Resistant PVC Insulated Sheathed

Low Voltage 2 Cores Cable 2 X 10mm2 Stranded Copper Fire Resistant PVC Insulated Sheathed

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
ZC-YJV 2*10mm²

Trading Properties

moq
100 meters
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

Low Voltage Power Cable 0.6/1kv YJV-2*10mm² Stranded Copper XLPE Insulation Fire-Resistant PVC Outer Sheath Technical Datasheet — ZC-YJV 0.6/1 kV 2×10 mm² 1. Cable Designation & Meaning Code Meaning ZC​ Flame retardant, Class C​ (bundled combustion test per GB/T 18380.3 / GB/T 19666) YJ​ XLPE (cross...

Product Details

Highlight:

Low Voltage 2 Core Cable

,

2 Core Cable 2 x 10mm2

,

Fire Resistant pvc insulated sheathed cable

Conductor nominal area:
10 Mm²
Number of cores:
2
Conductor construction:
Class 2, 7×∅1.35 Mm
Conductor diameter (approx.):
4.0 Mm
Insulation nominal thickness:
0.7 Mm
Diameter over insulation:
5.4 Mm
Sheath nominal thickness:
1.8mm
Overall cable diameter:
15.2 – 15.3 Mm
Approx. weight:
324 – 348 Kg/km
Long-term service temperature:
90 °C
Short-circuit temperature (≤5 s):
250 °C
Routine test:
3.5 KV AC / 5 Min; Type Test 4.0 KV
Volume resistivity @90 °C:
≥ 10¹² Ω·cm
Insulation resistance constant:
≈ 3.67 MΩ·km @90 °C

Product Description

Low Voltage Power Cable 0.6/1kv YJV-2*10mm² Stranded Copper XLPE Insulation Fire-Resistant PVC Outer Sheath

 

Technical Datasheet — ZC-YJV 0.6/1 kV 2×10 mm²

Low Voltage 2 Cores Cable 2 X 10mm2 Stranded Copper Fire Resistant PVC Insulated Sheathed

1. Cable Designation & Meaning

 

Code

Meaning

ZC​

Flame retardant, Class C​ (bundled combustion test per GB/T 18380.3 / GB/T 19666)

YJ​

XLPE (cross-linked polyethylene) insulation

V​

PVC (polyvinyl chloride) outer sheath (flame-retardant ZC grade)

0.6/1 kV​

Rated voltage U₀/U = 600/1000 V; max. system voltage Uₘ = 1.2 kV

2×10 mm²​

Two cores, nominal copper conductor area 10 mm² per core

Construction​

Unarmoured, non-screened, round multi-core

Compared with plain YJV 2×10, the only difference is the ZC prefix: flame-retardant PVC sheath + flame-retardant filler/binder, passing Class C bunched flame test. Dimensions, conductor, insulation thickness and electrical values are identical.

2. Applicable Standards

  • GB/T 12706.1-2020​ (equiv. IEC 60502-1) — Extruded insulation power cables ≤ 1 kV
  • GB/T 3956 / IEC 60228​ — Conductors (Class 2)
  • GB/T 19666-2019​ — Flame retardant & fire resistant cables (ZC = Class C)
  • GB/T 18380.3​ — Bunched flame propagation test, Class C (sample non-metal volume 1.5 L/m, flame 20 min, char ≤ 2.5 m above burner)

Low Voltage 2 Cores Cable 2 X 10mm2 Stranded Copper Fire Resistant PVC Insulated Sheathed

3. Product Components / Construction (inside → outside)

  1. Conductor (×2)​ — Bare annealed copper, Class 2 stranded circular, 7×∅1.35 mm​ (typical); Class 1 solid permitted for 10 mm²
  2. Conductor screen​ — Not required for 0.6/1 kV; omitted
  3. Insulation (×2)​ — XLPE compound, extruded (red/black/blue/brown etc.)
  4. Insulation thickness (nominal)​ — 0.7 mm​ (GB/T 12706.1, 10/16 mm² class)
  5. Filler​ — Flame-retardant non-hygroscopic PP/PE filler​ (ZC grade, replaces plain filler)
  6. Binder​ — Flame-retardant glass-fibre tape / halogen-free flame-retardant tape​ (ZC grade)
  7. Outer sheath​ — Flame-retardant PVC​ compound (ZC grade)
  8. Sheath thickness (nominal)​ — 1.8 mm​ (multi-core rule)
  9. Sheath colour​ — Black (standard); other colours available
  10. Armour​ — None
  11. Metallic screen​ — None

4. Dimensional Data

 

Item

Typical value

Remarks

Conductor nominal area (per core)

10 mm²

—

Number of cores

2

—

Conductor construction

Class 2, 7×∅1.35 mm​

min. 7 wires

Conductor diameter (approx.)

4.0 mm​

—

Insulation nominal thickness

0.7 mm​

—

Diameter over insulation (approx.)

5.4 mm

4.0 + 2×0.7

Sheath nominal thickness

1.8 mm​

—

Overall cable diameter

15.2 – 15.3 mm​

15.2 (structure table), 15.3 (JCCC)

Approx. weight

324 – 348 kg/km​

328 (Langfang), 331 (structure table), 348 (ZC-YJV structure sheet)

Cable shape

Round

—

 

Low Voltage 2 Cores Cable 2 X 10mm2 Stranded Copper Fire Resistant PVC Insulated Sheathed

5. Insulation Data

  • Material:​ XLPE (cross-linked polyethylene)
  • Nominal thickness:​ 0.7 mm
  • Long-term service temperature:​ 90 °C
  • Short-circuit temperature (≤5 s):​ 250 °C
  • Emergency overload:​ 105 °C (limited duration)
  • Routine test:​ 3.5 kV AC / 5 min; type test 4.0 kV
  • Volume resistivity @90 °C:​ ≥ 10¹² Ω·cm
  • Insulation resistance constant:​ ≈ 3.67 MΩ·km @90 °C

6. Electrical Parameters

 

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV​

 

DC resistance @20 °C (Class 2 Cu, per core)​

≤ 1.83 Ω/km​

GB/T 3956 max

AC resistance @90 °C (est.)

≈ 2.38 Ω/km

—

Current rating in air (25–30 °C, single circuit, 2-core)

≈ 65–86 A​

65 (Langfang 25℃), 70 (JCCC air), 86 (Joca air)

Current rating direct buried (20 °C, soil 1.0 K·m/W, 0.7 m)

≈ 80–100 A​

80 (Langfang), 90 (JCCC), 100 (Joca)

Short-circuit current (1 s adiabatic, Cu, 250 °C, per core)

≈ 1.00 kA

reference

Frequency

50/60 Hz AC (DC usable)

—

 

7. Temperature Characteristics

  • Max. conductor operating temp. (continuous):​ 90 °C
  • Max. short-circuit temp. (≤5 s):​ 250 °C
  • Min. installation ambient temp.:​ 0 °C​ (pre-heat below 0 °C)
  • Service ambient range:​ −20 °C to +90 °C (sheath)
  • Flame retardant class:​ Class C​ per GB/T 19666 (bundled, self-extinguishing, char ≤ 2.5 m)

8. Mechanical & Installation Parameters

  • Min. bending radius (unarmoured multi-core):​ ≥ 15 × OD​ → ≈ 228 mm at Ø15.2 mm
  • Max. pulling tension (Cu only):​ 50 N/mm² × 10 mm² × 2 = 1000 N total
  • Sheath grip:​ avoid; use conductor sock
  • Direct burial:​ allowed in non-aggressive soil, sand bed + warning tape, ≥ 0.7 m depth, conduit under roads
  • Conduit ID:​ ≥ 1.5 × OD → ≥ 23 mm (use 25 mm conduit)
  • Elevation:​ no limit for XLPE

9. Material Specification Summary

  • Conductor:​ Cu annealed, Class 2, 7×1.35 mm, IEC 60228
  • Insulation:​ XLPE 0.7 mm, 90 °C
  • Filler:​ Flame-retardant PP/PE
  • Binder:​ Flame-retardant glass fibre tape
  • Sheath:​ Flame-retardant PVC (ZC), 1.8 mm nom.
  • No armour, no screen

 

Low Voltage 2 Cores Cable 2 X 10mm2 Stranded Copper Fire Resistant PVC Insulated Sheathed

10. Scope of Application / Usage Range

ZC-YJV 0.6/1 kV 2×10 mm²​ is for fixed installation​ in LV distribution up to 1.2 kV where flame-retardant Class C​ is required (plain YJV is not sufficient).

Typical use:

  • Single-phase AC circuits (L+N)​ or DC pairs (+,−)​ in buildings with fire-code requirement for ZC
  • Indoor distribution boards, residential/commercial final circuits, lighting & small equipment feeders
  • Cable trays, ducts, trenches, shafts in high-rise buildings, hotels, stations, metros, hospitals, data centres​ (where ZC or better is specified)
  • Industrial plants, warehouses, PV/battery/charger branch circuits (DC polarity check needed)
  • Direct buried in non-aggressive soil, low mechanical risk

 

Low Voltage 2 Cores Cable 2 X 10mm2 Stranded Copper Fire Resistant PVC Insulated Sheathed

 

Not suitable for:

  • Fire-survival circuits → use NH-ZC-YJV 2×10
  • Heavy mechanical load → use ZC-YJV22 2×10
  • Three-phase → use 3-core / 4-core
  • Magnetic conduit AC run (eddy risk, though less critical at 10 mm²)
  • Corrosive/oily environment without extra barrier

11. Packing

  • Drum / coil:​ Steel-wooden drum or coil, 100–500 m typical.