Low Voltage 2 Cores Cable 2 X 10mm2 Stranded Copper Fire Resistant PVC Insulated Sheathed
Basic Properties
Trading Properties
Product Summary
Product Details
Low Voltage 2 Core Cable
,2 Core Cable 2 x 10mm2
,Fire Resistant pvc insulated sheathed cable
Product Description
Low Voltage Power Cable 0.6/1kv YJV-2*10mm² Stranded Copper XLPE Insulation Fire-Resistant PVC Outer Sheath
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant C — IEC 60332-3-24, Category C |
|
YJ |
Cross-linked polyethylene (XLPE) insulation |
|
V |
PVC sheath |
|
2×10 mm² |
Two cores, 10 mm² copper conductor each |
Construction: Two Class 2 stranded copper conductors, XLPE insulation, PVC outer sheath (no armour, no shield, circular or flat formation).

Applicable Standards
- GB/T 12706.1-2020 (equiv. IEC 60502-1) — Extruded insulation power cables ≤ 1 kV
- GB/T 3956 / IEC 60228 — Conductors (Class 2)
- GB/T 19666-2019 — Flame retardant & fire resistant cables (ZC = Class C)
- GB/T 18380.3 — Bunched flame propagation test, Class C (sample non-metal volume 1.5 L/m, flame 20 min, char ≤ 2.5 m above burner)

ZC-YJV 2×10 mm² — LV Flame-Retardant Twin-Core Power Cable — Specification
1. Overview & Ratings. ZC-YJV 2×10 is a twin-core (L + N) LV power cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C flame-retardant PVC sheath. Two matched compacted 10 mm² copper cores, dry-cured XLPE, unarmored. OD ≈ 10.0 mm, ≈ 320 kg/km (est.), ≈ 55 A per core free air at 30 °C (est.). Scope: 230 V lighting branches, luminaire feeds, socket drops — not 950°C fire duty.
2. Construction Stack (Inner → Outer, expanded).
| Layer / Feature | Build | Function |
|---|---|---|
| Conductor L | 1×10 compacted Cu, Class 2, ≈7 strands | Phase, R ≤1.91 Ω/km |
| Conductor N | 1×10 compacted Cu, Class 2, ≈7 strands | Matched neutral |
| Strand compaction | Concentric layers rolled compact | Round bundle, clean lug entry |
| XLPE insulation (L/N) | Dry-cured PE, ≈1.0 mm per core | 90°C dielectric |
| Core identification | Color band / printed L/N | Prevents crossed wiring |
| Twin-core laying | Two cores twisted compact | Stable ≈8.8 mm sub-bundle |
| PVC ZC sheath | Class C, ≈1.1 mm overall | Binds pair, self-extinguishes |
| Jacket print | Continuous type/size/voltage/length | On-site readable spec |
3. Electrical Characteristics. Per-core R ≤ 1.91 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 55 A per core (est., air 30 °C); short-circuit ≈ 1.4 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
XLPE (cross-linked polyethylene) |
|
Outer sheath material |
PVC (ST₂) |
|
Long-term service temp. |
90 °C (continuous) |
|
Max. conductor temp. (normal) |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Test voltage AC (5 min) |
3.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹⁴ Ω·cm |
|
Shield |
None as standard (can be added) |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage |
1.2 kV AC |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 1.83 Ω/km per core |
GB/T 3956 Class 2 Cu max |
|
AC resistance @90 °C (est.) |
≈ 2.35 Ω/km per core |
— |
|
Current rating in air (30 °C) |
Phase: 75 A |
two-core, touching, in free air |
|
Current rating in tray (30 °C) |
Phase: 85 A |
two-core, spaced 2×OD |
|
Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W) |
Phase: 80 A |
direct buried |
|
Current rating in conduit (30 °C) |
Phase: 65 A |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 1.1 kA (1,100 A) per core |
— |
|
Capacitance (core-to-core, approx.) |
≈ 0.12 µF/km |
XLPE |
|
Capacitance (core-to-sheath, approx.) |
≈ 0.13 µF/km |
XLPE |
|
Inductive reactance (approx.) |
≈ 0.07 Ω/km |
at 50 Hz |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 2×10 at 75 A single-phase, 230 V → max load ≈ 17 kW (cos φ = 0.8). Suitable for control circuits, signal wiring, and light single-phase distribution.
4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; withstands repeated 0~90°C cycles; indoor; UV-grade jacket optional.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C (≤1 h) |
|
Min. installation ambient temp. |
0 °C (below 0 °C requires preheating) |
|
Service ambient range |
−20 °C to +90 °C |
|
Flexing temp. range |
0 °C to +90 °C |
Fire Performance (ZC-YJV — Flame Retardant C)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.12 / IEC 60332-1-2 (single cable, self-extinguishing) |
|
Flame retardant class |
Class C (ZC) per GB/T 19666 |
|
Halogen content |
Contains halogen (PVC sheath) |
|
Smoke density |
Not low-smoke (PVC) |
|
Corrosivity |
Corrosive (PVC) |
|
Toxicity |
Toxic fumes when burned (PVC) |
|
EMI shielding |
None (no metallic screen/armour) |
5. Installation Practice & Handling. 10 mm² Cu lugs, miniature glands, crimp/torque per table; bend ≥ 15×OD ≈ 150 mm; derate bundled/conduit runs; avoid pinching the slim twin bundle; continuity + insulation per core after pulling.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 165 mm at Ø11.0 mm |
two-core unarmoured |
|
Max. pulling tension |
150 N per core (10 mm² × 15 N/mm²) |
Cu conductor limit |
|
Direct burial |
Suitable (with sand bedding) |
— |
|
Surface mounting |
Excellent (cable tray, ladder, cleats) |
— |
|
Conduit ID |
≥ 16 mm |
— |
|
Fixing |
cable ties, cleats |
— |
|
Impact resistance |
Moderate |
— |
|
Water resistance |
Good (PVC sheath) |
— |
|
UV resistance |
Fair (PVC degrades outdoors, use UV-resistant PVC or conduit) |
— |
|
Flex life |
Good (Class 2 stranded) |
fixed installation |
|
Termination note |
Standard compression lugs or mechanical connectors |
— |
6. Typical Service Applications. 230 V lighting sub-branches and luminaire circuits, switch tails, short socket drops, small auxiliary and signal power leads in light commercial and residential branch wiring.

7. Testing & QA Regime (16 items). Routine: DC resistance L/N, 3.5 kV withstand, insulation resistance, continuity, sheath/insulation thickness, dimensional check, strand construction, eccentricity, appearance, print legibility, mass. Type: ZC flame test, short-circuit rating, sheath mechanical, 0~90°C cycle.
Cable Parameters
| ZC-YJV 2×10 mm² — LV Flame-Retardant Twin-Core Power Cable — Full Parameter Sheet | |||
| 2×Cu / XLPE / PVC · ZC class C · 0.6/1 kV · ≈10.0 mm · phase + neutral twin-core for 230V lighting branch circuits, luminaire feeds and socket drops | |||
| Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | |||
| Cable type | ZC-YJV — Cu/XLPE/PVC, flame-retardant class C | — | ZC-YJV denotes a copper-conductor cable with cross-linked polyethylene insulation and a PVC outer sheath; the leading ZC marks a Chinese flame-retardant class C compound that self-extinguishes after the ignition source is removed. |
| Rated voltage (U0/U) | 0.6/1 | kV | 0.6 kV phase-to-earth (U0) and 1 kV phase-to-phase (U) rating defines this as a general low-voltage power cable suited to 230/400 V building distribution. |
| Maximum operating voltage (Um) | 1.2 | kV | The 1.2 kV maximum system voltage is the continuous upper phase-to-earth limit the XLPE insulation may withstand in normal service. |
| Core configuration | 2×10 (L + N) | — | Two equal 10 mm² compacted copper cores twisted together — one phase (L) and one neutral (N) — for single-phase 230 V lighting branches, luminaire and socket drop circuits. |
| Conductor material | Compacted stranded annealed copper | — | Soft annealed copper strands are layer-compacted into a round bundle to lower skin effect, reduce diameter and give a clean entry into a 10 mm² lug. |
| Insulation | XLPE cross-linked polyethylene | — | Chemically cross-linked polyethylene bonds into a heat-resistant dielectric that keeps its properties at the 90 °C operating temperature. |
| Sheath | PVC, flame-retardant class C (ZC) | — | An overall PVC jacket protects the twisted cores from abrasion and dust and carries the class C flame-retardant formulation; warm clay-brown finish. |
| Flame retardancy | ZC class C (self-extinguishing, not fire-rated) | — | On removal of a flame the cable stops propagating fire; this is flame-retardancy, not 950 °C/180 min circuit-integrity fire resistance. |
| Suitable for | Fixed indoor tray, conduit, trunking, branch | — | Designed for fixed light single-phase wiring: lighting sub-branches, luminaire tails and socket drops. |
| Application | 230V lighting branch, luminaire feed | — | Typically runs a phase-and-neutral feed from a lighting board to luminaires, switches or socket drops. |
| Application note | Not for 950°C circuit-integrity fire duty | — | Do not substitute this ZC cable for a mineral-insulated or fire-resistant circuit; it cannot maintain live integrity under sustained fire. |
| 02 · Conductors | |||
| Power core count / area | 2 × 10 | mm² | Two identical 10 mm² conductors provide balanced phase and neutral paths for single-phase lighting and socket-drop power. |
| Conductor type | Compacted stranded Cu, Class 2 | — | Class 2 stranded compacted construction gives a fixed-wiring conductor that rounds into a stable bundle for clean lug termination. |
| DC resistance (10) @ 20°C | ≤ 1.91 | Ω/km | Maximum permitted DC resistance of a 10 mm² copper conductor at 20 °C; keep branch runs short as resistance limits voltage drop. |
| Stranding | Layer-compacted concentric bundle | — | Concentric layers of strands are compacted radially to reduce gaps, tighten the bundle and present a clean round entry into the lug. |
| Strands (nom., est.) | ≈ 7 compacted | — | Approximate number of compacted strands in a 10 mm² Class 2 bundle; exact count follows the conductor standard and factory drawing. |
| Surface | Bare copper; tinned optional | — | Bare copper suits most indoor use; optional tinned plating improves corrosion resistance in damp sites. |
| Core identification | L phase / N neutral by color or marking | — | Cores are distinguished by insulation color or printed marking so phase and neutral are wired consistently at both ends. |
| Nominal area tolerance | Within conductor class 2 band | — | Actual cross-sectional area and strand geometry stay inside the class 2 tolerance band rather than a solid bare count. |
| 03 · Insulation | |||
| Insulation material | XLPE (cross-linked polyethylene) | — | Cross-linked PE delivers a higher continuous temperature rating and lower dielectric loss than ordinary PVC insulation for the same size. |
| Insulation thickness (nom.) | ≈ 1.0 | mm | Nominal radial insulation wall on each core; gauged to withstand the 3.5 kV routine test and the 90 °C heat load. |
| Working conductor temp. | 90 | °C | Maximum continuous conductor temperature under rated current without shortening insulation life. |
| Short-circuit temp. | 250 | °C | Peak conductor temperature the insulation may survive for a short fault duration (seconds) before damage occurs. |
| Insulation resistance | High and stable | MΩ·km | XLPE keeps a high, stable insulation resistance over life, supporting reliable earth-fault detection on branch circuits. |
| Color | Phase / neutral color on request | — | Insulation colors are matched to local wiring convention (e.g. brown/blue) or supplied natural with printed marking. |
| Cure type | Chemical / dry-cured XLPE | — | A controlled cross-linking cure locks the polymer network so the insulation stays elastic rather than melting under heat. |
| 04 · Sheath & Flame Retardancy | |||
| Sheath material | PVC, flame-retardant ZC | — | The class C PVC outer jacket blends a flame-suppressing formulation while keeping a smooth, printable surface. |
| Sheath thickness (nom.) | ≈ 1.1 | mm | Nominal overall jacket wall sized to shield the two twisted cores from abrasion, dust and occasional moisture. |
| Finished outer diameter | ≈ 10.0 | mm | Overall twin-core finished diameter used to size small conduit fill, trunking and gland entry. |
| Flame behavior | Self-extinguishing, class C | — | After the test flame is removed the sample extinguishes without propagating along the cable; it is not 950°C fire-rated. |
| Sheath color | Warm clay brown (black/gray on request) | — | Standard warm clay brown; black or dark gray jackets are supplied for industrial aesthetics on request. |
| Surface finish | Smooth, continuous print | — | A smooth jacket carries a continuous printed line of type, size, voltage, ZC class and meter length along its length. |
| 05 · Electrical | |||
| Rated voltage (U0/U) | 0.6/1 | kV | Low-voltage rating matching 230/400 V distribution systems. |
| Max voltage (Um) | 1.2 | kV | Continuous upper system voltage for phase-to-earth insulation stress. |
| Nominal current (per 10 core, est.) | ≈ 55 | A | Approximate ampacity of a single 10 mm² core in free air at 30 °C; reduce for bundling, duct fill and high ambient. |
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine dielectric withstand applied between conductor and sheath for five minutes without breakdown. |
| Insulation resistance | High, XLPE | MΩ·km | Measured after conditioning; confirms no void, crack or contamination in the cured insulation. |
| Short-circuit current (10, 1s, est.) | ≈ 1.4 | kA | Approximate 1-second copper short-time withstand; the branch core trips under a light fault. |
| Frequency | 50 / 60 | Hz | Compatible with both 50 Hz and 60 Hz low-voltage power systems. |
| Dielectric | XLPE, low loss | — | Low dielectric loss keeps heating down under continuous lighting load. |
| 06 · Thermal & Environment | |||
| Normal conductor temp. | 90 | °C | Sustained operating temperature the XLPE insulation is rated for under full load. |
| Installed ambient | 0 ~ +40 | °C | Recommended continuous ambient around the cable; higher rooms require ampacity derating. |
| Min install temp. | 0 | °C | Avoid cold bending below 0 °C where the PVC jacket and insulation may stiffen and crack. |
| Burning | Self-extinguishing, ZC class C | — | Class C vertical flame test behavior: flame stops once the external burner is removed. |
| Outdoor / UV | Indoor preferred; UV-grade jacket optional | — | Standard PVC degrades under prolonged direct sun; specify UV-stabilized jacket for exposed outdoor runs. |
| Oil / chemicals | Resistant to common oils; check aggressive media | — | Withstands typical machine oils; verify against specific solvents or acid fumes before use. |
| Temperature cycle | Withstands repeated 0~90°C duty | — | The insulation and jacket survive repeated heating/cooling cycles without cracking or delamination. |
| 07 · Mechanical & Construction | |||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 150 | mm | Fixed-installation minimum bend radius for the twin-core cable; tighter bends strain insulation and jacket. |
| Flexibility | Stranded, easy to pull on site | — | Compacted strands keep the small cable flexible enough to route through tight conduit and trunking. |
| Shielding / Armor | None / unarmored | — | No copper braid screen and no armor; add screening or armor where EMI or mechanical protection is required. |
| Cable weight per km (est.) | ≈ 320 | kg/km | Approximate mass per kilometer used for tray loading and coil sizing. |
| Circularity | Compacted twin bundle, stable OD | — | The two cores lay into a compact bundle so the finished OD stays consistent along the length. |
| Tensile / elongation | Jacket meets PVC grade | — | Sheath tensile strength and elongation satisfy the PVC compound grade for durable handling. |
| 08 · Factory Advantages | |||
| Matched twin cores | L and N built to the same 10 mm² spec for balanced branches | — | Both cores match in size and resistance so phase and neutral drop equally along a lighting run. |
| Stable XLPE cure | Even cross-linking keeps the 90°C dielectric consistent lot to lot | — | Controlled cure removes soft spots in insulation that would age faster under continuous lighting load. |
| Dosed ZC compound | Flame-retardant PVC self-extinguishes to class C | — | Dosed flame inhibitors give a safety margin against incidental ignition in ceiling and wall voids. |
| Length-on-demand | Cut to exact meter, sealed ends, minimal offcut | — | Custom cut lengths match the measured luminaire run and reduce waste. |
| Batch resistance log | Per-core DC R recorded against the lot number | — | Each core's resistance is logged against batch ID for procurement traceability. |
| Continuous print line | Type, size, ZC, voltage and meter length along jacket | — | Clear continuous marking lets installers read the spec without a certificate on site. |
| Phase-color option | L/N insulation colors matched to local convention | — | Pre-colored phase and neutral remove guesswork at termination and inspection. |
| Drum or coil pack | Supplied on drum or small coil to match the branch | — | Choose a small coil for short runs or a drum for longer lighting circuits. |
| Certified QA pack | Routine + type test record shipped per batch | — | A complete QA packet supports buyer audit and commissioning sign-off. |
| 09 · Installation | |||
| Laying | Tray, conduit, trunking, branch | — | Route in fixed supports; avoid pinching the slim twin bundle and keep bending above 15×OD. |
| Connectors | 10 mm² Cu lugs, miniature glands | — | Crimp matched 10 mm² copper lugs on each core; select a miniature gland sized to the 10.0 mm OD. |
| Bend radius | ≥ 15×OD ≈ 150 mm | — | Maintain the minimum radius around corners to prevent insulation cold-working. |
| Parallel runs | Derate when bundled in conduit/tray | — | Adjacent heating cores share heat; apply bundle derating before sizing the branch breaker. |
| Site test | Continuity + insulation post-laying | — | After pulling, verify L and N continuity and insulation resistance before energizing luminaires. |
| Termination | Strip, crimp lug, torque per table | — | Strip insulation without nicking strands, crimp the lug fully, and torque per the lug table. |
| 10 · Packing & Applications | |||
| Supply length | Custom / drum or coil | m | Cut to the measured branch length; drum or small-coil packing. |
| Length tolerance | Per trade standard for cut lengths | — | Cut-length tolerance follows the applicable trade standard rather than a fixed meter promise. |
| Reel type | Wooden drum / small coil | — | Drum for long pulls; coil for short luminaire tails. |
| Surface marking | ZC-YJV, 2×10, 0.6/1kV, ZC, length | — | Jacket prints type, two-core size, voltage, flame class and cumulative meter length. |
| Typical use | Lighting branch, luminaire feed, socket drop | — | Runs phase+neutral to luminaires, switches and short socket drops. |
| Storage | Dry indoor, avoid direct UV | — | Store on a pallet, dry and shaded, to keep the slim jacket intact. |
Cable Test Parameters
| Test Parameters — ZC-YJV 2×10 LV Flame-Retardant Twin-Core Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | 20 °C, each core L and N | 10 ≤1.91 Ω/km | Routine |
| 2 | Voltage test (AC) | 3.5 kV AC, 5 min, core-to-sheath | No breakdown | Routine |
| 3 | Insulation resistance | XLPE, 20°C, per core | High & stable | Routine |
| 4 | Continuity | Each core L and N | Continuous | Routine |
| 5 | Flame retardancy | Class C vertical test | Self-extinguish | Type |
| 6 | Sheath thickness | Micrometer, cross-section | Nominal ≥1.1 mm | Routine |
| 7 | Insulation thickness | Micrometer, per core | Nominal ≥1.0 mm | Routine |
| 8 | Dimensional check | Caliper, overall OD | OD ≈ 10.0 mm | Routine |
| 9 | Conductor construction | Visual / strand count | Class 2 compacted | Routine |
| 10 | Short-circuit rating | Calculated / type | 1.4 kA / 1 s | Type |
| 11 | Insulation eccentric test | Cross-section measure per core | Within tolerance | Routine |
| 12 | Sheath appearance | Visual along length | Smooth, no flaw | Routine |
| 13 | Printing legibility | Visual | Marking readable | Routine |
| 14 | Mass per unit length | Weigh / calculate | ≈ 320 kg/km | Routine |
| 15 | Sheath mechanical | Tensile / elongation check | Meets PVC grade | Type |
| 16 | Temperature cycle | Repeated 0~90°C duty | No cracking | Type |
Cable Cross Section

| ZC-YJV 2×10 — Twin-Core Cross-Section Construction Diagram | |||||
| 2×Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · ≈10.0 mm · L+N lighting branches, luminaire feeds & socket drops | |||||
| No. | Layer / Feature | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Detailed Function / Remarks |
| 1 | Conductor (L) — phase | 1×10 compacted Cu, Class 2, ≈7 strands | — | ≈ 3.6 | Phase core, DC R ≤1.91 Ω/km @20°C; keep lighting runs short to limit drop. |
| 2 | Conductor (N) — neutral | 1×10 compacted Cu, Class 2, ≈7 strands | — | ≈ 3.6 | Matched neutral core, same size/resistance to balance single-phase drop. |
| 3 | Strand compaction | Concentric layers rolled compact | — | — | Radial compaction closes strand gaps for a round bundle and clean lug entry. |
| 4 | XLPE insulation (L) | Dry-cured cross-linked PE | ≈ 1.0 | ≈ 5.6 | 90°C dielectric on the phase core, low loss, high stable insulation resistance. |
| 5 | XLPE insulation (N) | Dry-cured cross-linked PE | ≈ 1.0 | ≈ 5.6 | Matching neutral insulation; L/N distinguished by color or print. |
| 6 | Core identification | Color band or printed L/N marking | — | — | Phase and neutral readable at both ends to prevent crossed wiring. |
| 7 | Twin-core laying | Two cores twisted into a compact bundle | — | ≈ 8.8 | Controlled lay keeps the pair stable and reduces OD for small conduit fill. |
| 8 | PVC ZC sheath | Flame-retardant class C, smooth, overall | ≈ 1.1 | ≈ 10.0 | Binds the pair, shields from abrasion/dust, self-extinguishes to class C. |
| 9 | Jacket print | Continuous type/size/voltage/length line | — | — | Marking along the jacket: ZC-YJV, 2×10, 0.6/1kV, ZC, cumulative length. |
| Key Dimensions, Electrical & Mechanical Properties (expanded) | |||||
| Finished cable diameter | ≈ 10.0 | mm | Slim twin-core OD for small conduit and miniature gland sizing. | ||
| Approx. cable mass (est.) | ≈ 320 | kg/km | Very light, easy to pull and coil on site. | ||
| Nominal voltage rating | 0.6/1 | kV | Matches 230/400 V distribution systems. | ||
| Max voltage (Um) | 1.2 | kV | Phase-to-earth continuous upper limit. | ||
| Normal conductor temp. | 90 | °C | Continuous load temperature of XLPE. | ||
| Short-circuit temp. | 250 | °C | Short-time fault peak before insulation damage. | ||
| DC resistance (10) | ≤ 1.91 | Ω/km | Per core @20°C; short runs to limit drop. | ||
| Nominal current (est.) | ≈ 55 | A | Per core, free air 30°C; derate bundled. | ||
| Short-circuit rating (1s, est.) | ≈ 1.4 | kA | 10 Cu, light branch fault duty. | ||
| Flame retardancy | ZC class C, self-extinguishing | — | Not 950°C fire-rated. | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 150 | mm | Fixed twin-core install corner radius. | ||
| Frequency | 50 / 60 | Hz | Compatible with both power systems. | ||
| Insulation resistance | High & stable | MΩ·km | XLPE; supports earth-fault detection. | ||
| Dielectric loss | Low | — | XLPE keeps heating down on lighting load. | ||
| Temperature cycle | 0~90°C repeated | — | Survives heating/cooling without cracking. | ||
| Sheath mechanical | Meets PVC grade | — | Tensile/elongation checked at type test. | ||
| Pack choice | Drum or small coil | — | Small coil for luminaire tails. | ||
| Core configuration | 2×10 (L+N) | — | Balanced twin single-phase. | ||
| Application | Lighting branch, luminaire feed, socket drop | — | 230 V light branch power. | ||
| Schematic — not to exact scale. OD ≈10.0 mm, weight ≈320 kg/km, ≈55 A per core free air at 30°C and ≈1.4 kA/1s are (est.) from cross-referenced industry samples. ZC-YJV 2×10 serves 230 V lighting branches, luminaire feeds and socket drops; ZC class C self-extinguishes but is not 950°C fire-rated. Estimated values require confirmation against the factory test certificate for the specific batch. | |||||
Cable Construction Description
| Construction Description — ZC-YJV 2×10 LV flame-retardant twin-core cable | |||
| 2×Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈10.0 mm · L+N lighting branches, luminaire feeds & socket drops | |||
| 1. Product Identity & Ratings | |||
| ZC-YJV 2×10 rated 0.6/1 kV (Um 1.2), 90°C working, ZC class C; twin L+N cores. OD ≈10.0 mm, ≈320 kg/km (est.), ≈55 A per core free air at 30°C (est.), drum or small coil. It is a fixed lighting-branch / luminaire cable, not a flexible cord and not a 950°C fire-rated circuit. | |||
| 2. Copper Conductors (2×10) | |||
| Two matched 10 mm² compacted Class 2 Cu cores (L + N), ≈7 strands each; DC R ≤1.91 Ω/km @20°C; keep runs short to limit voltage drop; tinned plating optional for damp sites; phase-color insulation supplied on request. | |||
| 3. Strand Compaction & Bundle | |||
| Concentric strands are rolled compact to close gaps, round the bundle and give a clean entry into a 10 mm² lug; the two cores are twisted at a controlled lay to hold a stable ≈8.8 mm sub-bundle before sheathing. | |||
| 4. XLPE Insulation | |||
| Dry-cured cross-linked PE ≈1.0 mm on each core, stable 90°C dielectric, low dielectric loss, high and stable insulation resistance; short-circuit peak 250°C; L/N distinguished by color or printed marking. | |||
| 5. Core Identification | |||
| Phase (L) and neutral (N) are identified by insulation color band or printed marking so wiring matches at both ends; brown/blue colors can be supplied to local convention instead of natural insulation. | |||
| 6. PVC ZC Sheath | |||
| Flame-retardant PVC ≈1.1 mm overall, self-extinguishing class C; warm clay-brown standard (black/gray on request); smooth printable surface; binds the slim pair and shields from abrasion, dust and occasional moisture. | |||
| 7. Electrical Characteristics | |||
| 0.6/1 kV, Um 1.2; per-core R ≤1.91 Ω/km; routine 3.5 kV AC/5 min; ≈55 A per core (est., air 30°C); short-circuit ≈1.4 kA/1s (est.); 50/60 Hz; unscreened; low-loss XLPE. | |||
| 8. Factory Advantages | |||
| • Matched twin cores for balanced lighting branches. • Stable XLPE cure lot to lot. • Dosed ZC self-extinguish. • Length-on-demand. • Per-batch resistance log. • Continuous clear print. • Phase-color option. • Drum or small coil pack. • Certified QA pack. | |||
| 9. Site Handling & Installation | |||
| • Bend 15×OD (≈150 mm). • 10 Cu lugs, miniature glands, torque per table. • Derate bundled/conduit runs. • Avoid pinching the slim twin bundle. • Continuity + insulation per core after pulling. • Indoor; UV grade if exposed. | |||
| 10. Typical Service Applications | |||
| 230 V lighting sub-branches and luminaire circuits, switch tails, short socket drops, small auxiliary and signal power leads in light commercial and residential branch wiring. | |||
| 11. Testing & QA | |||
| 16-item regime: routine DC resistance L/N, 3.5 kV withstand, insulation resistance, continuity, sheath/insulation thickness, dimensional check, strand construction, eccentricity, appearance, print legibility, mass; type ZC flame, short-circuit, sheath mechanical, 0~90°C cycle. | |||
| 12. Packaging, Storage & Notes | |||
| Cut to measured length on drum or small coil; continuous marking; store dry indoor on a pallet, shaded, avoid direct UV. Est. OD/weight/ampacity/short-circuit confirmed against the factory certificate; ZC is flame retardant, not 950°C fire-rated. |
8. Factory Advantages.
- Matched twin cores — L and N built to the same 10 mm² spec for balanced branches.
- Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent.
- Dosed ZC compound — self-extinguishes to class C.
- Length-on-demand — exact meter, sealed ends, minimal offcut.
- Batch resistance log — per-core DC R recorded against lot number.
- Continuous print line — type, size, ZC, voltage and length along jacket.
- Phase-color option — L/N colors matched to local convention.
- Drum or small coil pack — small coil for luminaire tails.
- Certified QA pack — routine + type test record per batch.

9. Packaging, Storage & Logistics. Cut to measured length on drum or small coil; continuous marking; store dry indoor on a pallet, shaded, avoid direct UV.

10. Procurement Specification. State "ZC-YJV 2×10", length, class C, L/N color, pack; note flame retardant not fire-rated; request per-batch resistance log and 16-item QA record. Est. values confirmed against the factory certificate.