Low Voltage 2 Cores Cable 2 X 10mm2 Stranded Copper Fire Resistant PVC Insulated Sheathed
Basic Properties
Trading Properties
Product Summary
Product Details
Low Voltage 2 Core Cable
,2 Core Cable 2 x 10mm2
,Fire Resistant pvc insulated sheathed cable
Product Description
Low Voltage Power Cable 0.6/1kv YJV-2*10mm² Stranded Copper XLPE Insulation Fire-Resistant PVC Outer Sheath
Technical Datasheet — ZC-YJV 0.6/1 kV 2×10 mm²

1. Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant, Class C (bundled combustion test per GB/T 18380.3 / GB/T 19666) |
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
V |
PVC (polyvinyl chloride) outer sheath (flame-retardant ZC grade) |
|
0.6/1 kV |
Rated voltage U₀/U = 600/1000 V; max. system voltage Uₘ = 1.2 kV |
|
2×10 mm² |
Two cores, nominal copper conductor area 10 mm² per core |
|
Construction |
Unarmoured, non-screened, round multi-core |
Compared with plain YJV 2×10, the only difference is the ZC prefix: flame-retardant PVC sheath + flame-retardant filler/binder, passing Class C bunched flame test. Dimensions, conductor, insulation thickness and electrical values are identical.
2. Applicable Standards
- GB/T 12706.1-2020 (equiv. IEC 60502-1) — Extruded insulation power cables ≤ 1 kV
- GB/T 3956 / IEC 60228 — Conductors (Class 2)
- GB/T 19666-2019 — Flame retardant & fire resistant cables (ZC = Class C)
- GB/T 18380.3 — Bunched flame propagation test, Class C (sample non-metal volume 1.5 L/m, flame 20 min, char ≤ 2.5 m above burner)

3. Product Components / Construction (inside → outside)
- Conductor (×2) — Bare annealed copper, Class 2 stranded circular, 7×∅1.35 mm (typical); Class 1 solid permitted for 10 mm²
- Conductor screen — Not required for 0.6/1 kV; omitted
- Insulation (×2) — XLPE compound, extruded (red/black/blue/brown etc.)
- Insulation thickness (nominal) — 0.7 mm (GB/T 12706.1, 10/16 mm² class)
- Filler — Flame-retardant non-hygroscopic PP/PE filler (ZC grade, replaces plain filler)
- Binder — Flame-retardant glass-fibre tape / halogen-free flame-retardant tape (ZC grade)
- Outer sheath — Flame-retardant PVC compound (ZC grade)
- Sheath thickness (nominal) — 1.8 mm (multi-core rule)
- Sheath colour — Black (standard); other colours available
- Armour — None
- Metallic screen — None
4. Dimensional Data
|
Item |
Typical value |
Remarks |
|---|---|---|
|
Conductor nominal area (per core) |
10 mm² |
— |
|
Number of cores |
2 |
— |
|
Conductor construction |
Class 2, 7×∅1.35 mm |
min. 7 wires |
|
Conductor diameter (approx.) |
4.0 mm |
— |
|
Insulation nominal thickness |
0.7 mm |
— |
|
Diameter over insulation (approx.) |
5.4 mm |
4.0 + 2×0.7 |
|
Sheath nominal thickness |
1.8 mm |
— |
|
Overall cable diameter |
15.2 – 15.3 mm |
15.2 (structure table), 15.3 (JCCC) |
|
Approx. weight |
324 – 348 kg/km |
328 (Langfang), 331 (structure table), 348 (ZC-YJV structure sheet) |
|
Cable shape |
Round |
— |
5. Insulation Data
- Material: XLPE (cross-linked polyethylene)
- Nominal thickness: 0.7 mm
- Long-term service temperature: 90 °C
- Short-circuit temperature (≤5 s): 250 °C
- Emergency overload: 105 °C (limited duration)
- Routine test: 3.5 kV AC / 5 min; type test 4.0 kV
- Volume resistivity @90 °C: ≥ 10¹² Ω·cm
- Insulation resistance constant: ≈ 3.67 MΩ·km @90 °C
6. Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
Uₘ = 1.2 kV |
|
Test voltage AC (5 min) |
3.5 kV |
|
|
DC resistance @20 °C (Class 2 Cu, per core) |
≤ 1.83 Ω/km |
GB/T 3956 max |
|
AC resistance @90 °C (est.) |
≈ 2.38 Ω/km |
— |
|
Current rating in air (25–30 °C, single circuit, 2-core) |
≈ 65–86 A |
65 (Langfang 25℃), 70 (JCCC air), 86 (Joca air) |
|
Current rating direct buried (20 °C, soil 1.0 K·m/W, 0.7 m) |
≈ 80–100 A |
80 (Langfang), 90 (JCCC), 100 (Joca) |
|
Short-circuit current (1 s adiabatic, Cu, 250 °C, per core) |
≈ 1.00 kA |
reference |
|
Frequency |
50/60 Hz AC (DC usable) |
— |
7. Temperature Characteristics
- Max. conductor operating temp. (continuous): 90 °C
- Max. short-circuit temp. (≤5 s): 250 °C
- Min. installation ambient temp.: 0 °C (pre-heat below 0 °C)
- Service ambient range: −20 °C to +90 °C (sheath)
- Flame retardant class: Class C per GB/T 19666 (bundled, self-extinguishing, char ≤ 2.5 m)
8. Mechanical & Installation Parameters
- Min. bending radius (unarmoured multi-core): ≥ 15 × OD → ≈ 228 mm at Ø15.2 mm
- Max. pulling tension (Cu only): 50 N/mm² × 10 mm² × 2 = 1000 N total
- Sheath grip: avoid; use conductor sock
- Direct burial: allowed in non-aggressive soil, sand bed + warning tape, ≥ 0.7 m depth, conduit under roads
- Conduit ID: ≥ 1.5 × OD → ≥ 23 mm (use 25 mm conduit)
- Elevation: no limit for XLPE
9. Material Specification Summary
- Conductor: Cu annealed, Class 2, 7×1.35 mm, IEC 60228
- Insulation: XLPE 0.7 mm, 90 °C
- Filler: Flame-retardant PP/PE
- Binder: Flame-retardant glass fibre tape
- Sheath: Flame-retardant PVC (ZC), 1.8 mm nom.
- No armour, no screen

10. Scope of Application / Usage Range
ZC-YJV 0.6/1 kV 2×10 mm² is for fixed installation in LV distribution up to 1.2 kV where flame-retardant Class C is required (plain YJV is not sufficient).
Typical use:
- Single-phase AC circuits (L+N) or DC pairs (+,−) in buildings with fire-code requirement for ZC
- Indoor distribution boards, residential/commercial final circuits, lighting & small equipment feeders
- Cable trays, ducts, trenches, shafts in high-rise buildings, hotels, stations, metros, hospitals, data centres (where ZC or better is specified)
- Industrial plants, warehouses, PV/battery/charger branch circuits (DC polarity check needed)
- Direct buried in non-aggressive soil, low mechanical risk

Not suitable for:
- Fire-survival circuits → use NH-ZC-YJV 2×10
- Heavy mechanical load → use ZC-YJV22 2×10
- Three-phase → use 3-core / 4-core
- Magnetic conduit AC run (eddy risk, though less critical at 10 mm²)
- Corrosive/oily environment without extra barrier
11. Packing
- Drum / coil: Steel-wooden drum or coil, 100–500 m typical.