BV 2.5mm² Green-Yellow Building Wire Solid Copper Single Core PVC Insulated Protective Earth Cable

BV 2.5mm² Green-Yellow Building Wire Solid Copper Single Core PVC Insulated Protective Earth Cable

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
BV-2.5mm²

Trading Properties

moq
100 meters
unit price
USD 0.13-0.16/Meter
payment method
L/C,T/T
supply capacity
100000 rolls per month

Product Summary

BV 2.5mm² Green-Yellow Building Wire Solid Copper Single Core PVC Insulated Protective Earth Cable Cable Designation & Meaning Code Meaning B Building Wire V PVC insulation 1×2.5 mm² Single core of 2.5 mm² copper conductor Green-Yellow White PVC insulation (for civil indoor visible wiring) ...

Product Details

Highlight:

2.5mm² green-yellow earth cable

,

solid copper single core PVC wire

,

PVC insulated protective earth cable

Conductor nominal area:
2.5 Mm² (Cu) × 1
Number of cores:
1 (single-core)
Conductor material:
Copper (Cu)
Conductor class:
Class 1 Solid
Conductor construction:
1×∅1.78 Mm
Conductor diameter:
≈ 1.78 Mm
Insulation thickness (nom.):
0.8 Mm
Insulation thickness (min.):
0.62 Mm
Overall cable diameter:
3.2 – 4.2 Mm
Design outer diameter:
≈ 3.7 Mm
Approx. weight:
30 – 42 Kg/km
Design weight:
≈ 36 Kg/km
Cable shape:
Round

Product Description

BV 2.5mm² Green-Yellow Building Wire Solid Copper Single Core PVC Insulated Protective Earth Cable

Cable Designation & Meaning

Code

Meaning

B

Building Wire

V

PVC insulation 

1×2.5 mm²

Single core of 2.5 mm² copper conductor

Green-Yellow

White PVC insulation (for civil indoor visible wiring)


Construction: One 2.5 mm² solid copper conductor, white PVC insulation applied directly over the conductor.


BV 2.5mm² Green-Yellow Building Wire Solid Copper Single Core PVC Insulated Protective Earth Cable

BV 1×2.5 mm² (Green-Yellow PE) — Single-Core PVC Insulated Copper Protective Earth Wire — Specification 

1. Overview & Ratings

BV 1×2.5 (Green-Yellow) is a 450/750 V single-core PVC insulated wire designated for protective earth (PE) duty. Its pure annealed bare copper conductor (not tinned) provides a low-resistance bonding path that carries fault current to the earthing system whenever an insulation failure occurs. One 2.5 mm² solid copper core is covered by a green-yellow striped PVC jacket; there is no braid, no inner sheath and no outer jacket. Finished OD ≈ 3.4 mm, ≈ 29 kg/km (est.). Service range -15 to +70 °C. The striped finish is the internationally reserved identification for earthing conductors and must never be used as a phase, neutral or control wire. Fixed indoor installation only.

2. Construction Stack (Inner → Outer, expanded)

Layer / Feature Build Function
Conductor Pure annealed Cu, solid Class 1, Ø 1.78 mm PE fault-current path; R ≤ 7.41 Ω/km
Insulation Green-yellow striped PVC ≈ 0.8 mm wall 450/750 V dielectric; PE identification
Shield None Single-core unshielded wire
Outer jacket None Insulation forms the outer layer

3. Electrical Characteristics

DC resistance ≤ 7.41 Ω/km at 20 °C per GB/T 3956 Class 1 pure copper. Rated 450/750 V. Unlike phase conductors, the PE wire carries no normal load current; its electrical role is to keep the protective bonding loop resistance as low as possible so the overcurrent device trips quickly during a fault. Insulation resistance ≥ 20 MΩ·km. Every routine coil passes a 2000 V AC withstand test held 5 minutes, and PE continuity is checked end to end. Typical capacitance ≈ 150 pF/m at 1 kHz. Cross-section should be verified against PE sizing rules tied to the phase conductor and upstream protective device.

Insulation & Sheath Data

Property

Value

Insulation material

White PVC (Type TI1 or TI2)

Outer sheath material

None​ (non-sheathed)

Shield material

None​

Long-term service temp.

70 °C (continuous, TI1/TI2)

Max. conductor temp. (normal)

70 °C

Short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Test voltage AC (5 min)

2.5 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹² Ω·cm

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

450 / 750 V

GB/T 5023.3 (fixed wiring)

Max. system voltage

500 V AC / 750 V DC

—

Test voltage AC (5 min)

2.5 kV

Routine test

DC resistance @20 °C

≤ 7.41 Ω/km

GB/T 3956 Class 1 Cu max (2.5 mm²)

AC resistance @70 °C (est.)

≈ 9.28 Ω/km

—

Current rating in air (30 °C)

24 A​ (reference, single-core open)

typical residential

Current rating in conduit (30 °C)

20 A​ (reference, 2-core conduit)

typical installation

DC current capacity

24 A​

—

Short-circuit current (1 s, Cu, 160 °C)

≈ 275 A

—

Capacitance (core-to-ambient, approx.)

≈ 0.10 µF/km

PVC

Inductive reactance (approx.)

≈ 0.10 Ω/km

at 50 Hz (single-core)

Frequency

50/60 Hz AC, DC

—


Reference values: BV 2.5 (white) at 24 A, 230 V AC → max load ≈ 5,520 VA​ (typical lighting/socket circuit). At 24 V DC → max load ≈ 576 W.

4. Thermal & Flame Behaviour

Normal continuous operation -15 to +70 °C; under a short-circuit fault the conductor withstands up to 160 °C for up to 5 seconds until protection operates. The striped PVC compound meets IEC 60332-1 flame retardancy and self-extinguishes once the ignition source is removed. It is halogen-containing PVC, so in a fire it releases HCl gas; avoid it in public, high-density or escape-route wiring where LSZH insulation is mandated. The PE run should stay inside conduit, trunking or a closed tray to preserve the jacket and stripes from abrasion and sunlight. Bare copper terminals belong in dry, enclosed locations only.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

70 °C (continuous)

Max. short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Min. installation ambient temp.

−15 °C

Service ambient range

−15 °C to +70 °C

Flexing temp. range

Not recommended for flexing


Fire Performance (BV — PVC, Non-Low-Smoke)

Property

Value / Requirement

Flame retardant

GB/T 18380.3 / IEC 60332-3​ (Category A/B/C as specified)

Halogen content

Contains halogen​ (PVC)

Smoke density

Not low-smoke​ (IEC 61034-2 not applicable)

Corrosivity

Corrosive​ (HCl emission from PVC)

Toxicity

Toxic fumes​ when burned (CO, HCl)

EMI shielding

None​

UV resistance

Poor​ (PVC degrades outdoors, use conduit)

Water resistance

Limited​ (PVC insulation only)

5. Installation Practice & Handling

Minimum bend radius ≥ 4×OD ≈ 14 mm. The solid Class 1 core is stiff and dimensionally stable; lay out straight runs with generous corner radii and avoid repeated back-and-forth bending. Strip the jacket cleanly, seat the solid wire fully into an earthing terminal or PE lug, and tighten to the rated torque; use a crimp or bolted bond rated for the fault-current level. Connect one end to the equipment chassis or socket earth contact and the other to the PE bar or earth terminal. Never splice the PE run inside a concealed box without a accessible, approved joint. After termination, verify continuity from each end and record the loop resistance before energizing.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 4 × OD → ≈ 15 mm at Ø3.7 mm

solid conductor

Max. pulling tension

150 N (2.5 mm² × 60 N/mm²)

Cu conductor limit

Direct burial

Not recommended​ (PVC, no sheath, water ingress)

—

Surface mounting

Conduit, trunking, surface-mounted wiring channel, DIN rail

—

Conduit ID

≥ 16 mm (single), ≥ 20 mm (multiple)

—

Fixing

cable clips, staples, trunking clips

—

Impact resistance

Low (PVC)

—

Water resistance

Limited​ (no sheath)

—

UV resistance

Poor​ (indoor/conduit only)

—

Flex life

Poor​ (Class 1 solid, NOT for flexing)

—

Termination note

Screw terminals, compression lugs (2.5 mm²)

—


6. Typical Service Applications

Protective earthing in residential, commercial and light industrial fixed wiring: earth contacts on socket outlets, equipment bonding inside distribution boards, PE bars in switchboards, metal enclosure and conduit bonding, and frame earthing for fixed electrical equipment. The striped jacket identifies the safety conductor at every terminal and along the run, reducing the risk of an open or wrongly connected earth. Accepted installation methods include conduit, trunking, cable tray and embedded wall wiring. It is unsuitable for: moving or trailing machine leads, shielded instrumentation signals, outdoor UV-exposed runs, submersible or buried circuits, and high-temperature heating elements.


BV 2.5mm² Green-Yellow Building Wire Solid Copper Single Core PVC Insulated Protective Earth Cable

7. Testing & Quality Assurance Regime

Routine tests on 100% of production: DC resistance and PE continuity, 2000 V/5 min AC withstand, insulation resistance, conductor construction, insulation thickness, dimensional inspection, stripe colour and proportion against the standard reference, mass per unit length, appearance and jacket integrity, and packing. Type tests per material batch or design change: heat aging at 100 °C for 7 days, cold bend at -15 °C, insulation tensile strength and elongation, flame retardancy, insulation flexibility, and wall thickness uniformity. Every coil ships with a mill test certificate plus ROHS and REACH declarations. Stripes are checked to remain continuous and undamaged along the full length.


The Wire Parameters


BV 1×2.5 mm² (Green-Yellow PE) — Full Parameter Sheet
Single-core green-yellow striped PVC insulated protective earth wire · 450/750 V · pure annealed Cu solid Class 1 · no shield, no outer jacket · GB/T 5023 / IEC 60227
Section Parameter Value Unit Remarks / Standard
01 · Identification

Cable type BV (Green-Yellow, PE) — Single-core, striped PVC insulated, pure Cu PE conductor

Rated voltage (U0/U) 450/750 V Fixed indoor wiring

Number of cores 1 — Single core, solid

Nominal cross-section 2.5 mm² Per core, Class 1 solid

Conductor material Pure annealed copper (bare) — Class 1 per GB/T 3956, not tinned

Insulation material PVC (green-yellow striped) — 70 °C rated, 0.8 mm wall

Shield None — No braid / foil on single-core wire

Outer jacket None — Insulation forms the outer layer

Standard reference GB/T 5023 / IEC 60227 / JB/T 8734 — PVC insulated fixed wiring wire
02 · Conductor

Conductor form Solid (single wire) — Class 1

Conductor diameter 1.78 mm Solid wire

DC resistance @ 20 °C ≤ 7.41 Ω/km Maximum per GB/T 3956 (pure Cu)

Conductor surface Bare pure copper — Not tinned; fixed indoor PE use
03 · Insulation

Insulation type PVC (green-yellow striped) — Soft PVC, 70 °C

Insulation thickness ≈ 0.8 mm Nominal

Finished diameter ≈ 3.4 mm Insulation outer Ø

Insulation resistance ≥ 20 MΩ·km At 20 °C
04 · Lay-Up & Shield

Core lay-up Not applicable — Single-core wire

Filler / bedding None — No inner sheath on BV

Shield type None — Unshielded building wire

Shield coverage — — Not applicable
05 · Insulation Finish

Outer surface Smooth striped PVC extrusion — Longitudinal green + yellow stripes

Printing Designation / size / voltage / PE mark / metre — Print at regular intervals

Insulation colour Green-yellow striped — Protective earth only; never phase / neutral
06 · Electrical

Rated voltage 450/750 V Fixed wiring

Test voltage (AC) 2000 V AC 5 min routine

DC resistance @ 20 °C ≤ 7.41 Ω/km Per GB/T 3956 (pure Cu)

PE duty Fault-current bonding — No normal load current; carries fault current only

Conductor cross-section check Per PE sizing rules — Match to phase conductor / protective device

Capacitance ≈ 150 pF/m At 1 kHz
07 · Thermal & Mechanical

Max continuous conductor temp. 70 °C Normal service

Short-circuit / fault temp. (≤5 s) 160 °C Copper limit during fault

Min. ambient temp. -15 °C Fixed installation

Min. bending radius ≥ 4 × OD ≈ 14 mm Fixed wiring, solid core

Halogen content Halogen-containing — PVC compound
08 · Flame & Environment

Flame retardancy IEC 60332-1 — Single vertical flame

Oil resistance Limited — PVC insulation

UV resistance Limited — Indoor / conduit use

Corrosion resistance Limited (bare Cu) — Dry indoor only; use tinned variant for damp/outdoor

ROHS / REACH Compliant — EU 2011/65/EU


The Wire Test Parameters


Test Parameters — BV 1×2.5 mm² (Green-Yellow PE)
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance / continuity GB/T 3956, 20 °C; PE continuity check ≤ 7.41 Ω/km; continuous path Routine
2 AC voltage withstand 2000 V AC, 5 min No breakdown Routine
3 Insulation resistance 500 V megohmmeter ≥ 20 MΩ·km Routine
4 Conductor construction Visual + micrometer Solid Ø 1.78 mm pure Cu Routine
5 Insulation thickness Micrometer cross-section ≈ 0.8 mm Routine
6 Dimensional check Caliper OD ≈ 3.4 mm Routine
7 Stripe colour / ratio inspection Visual, standard reference Green-yellow stripes correct & continuous Routine
8 Mass per unit length Weighing ≈ 29 kg/km Routine
9 Appearance / colour Visual Smooth jacket, stripes intact, no patches Routine
10 Packing Visual Coil, sealed ends, PE-labelled Routine
11 Heat aging test 7 days at 100 °C Retention ≥ 70% Type
12 Cold bend test -15 °C, 4 h mandrel No cracking Type
13 Insulation tensile & elongation Universal tester Meets GB/T 5023 min. Type
14 Flame retardancy IEC 60332-1 Self-extinguish Type
15 Insulation flexibility Mandrel bend at ambient No cracking, no peeling Type
16 Wall thickness uniformity Micrometer at 4 points Min. wall ≥ nominal − tolerance Type


Cross Section Structure


BV 2.5mm² Green-Yellow Building Wire Solid Copper Single Core PVC Insulated Protective Earth Cable

BV 1×2.5 mm² (Green-Yellow PE) — Cross-Section Construction Diagram (Schematic)
Layered build-up: pure copper solid conductor (single core) → green-yellow striped PVC insulation · 450/750 V protective earth (PE) building wire · reserved exclusively for earthing and bonding · no shield, no outer jacket · -15~+70 °C
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor Pure annealed copper, solid Class 1 — single wire Ø 1.78 mm — 1.78 PE fault-current path; R ≤ 7.41 Ω/km; bare pure copper for low-resistance bonding
2 Insulation Green-yellow striped PVC compound, extruded over the solid conductor ≈ 0.8 ≈ 3.4 (finished) Primary insulation; 450/750 V rated; striped identification reserved for protective earthing only






Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 3.4 mm Single-core PVC PE wire (est.)
Approximate cable mass ≈ 29 kg/km Pure Cu + striped PVC insulation
Nominal voltage rating 450/750 V Fixed indoor wiring
Max continuous conductor temp. 70 °C Normal service
Min. ambient / installation temp. -15 °C Fixed installation
DC resistance @ 20 °C ≤ 7.41 Ω/km Class 1 pure copper, GB/T 3956
Core count × cross-section 1 × 2.5 mm² Single core, solid
Shielding None — Single-core wire, no braid / foil
Insulation resistance ≥ 20 MΩ·km PVC at 20 °C
Test voltage (AC) 2000 V AC / 5 min — Routine withstand test
Flame retardancy IEC 60332-1 — Single vertical flame
Insulation colour Green-yellow striped (PE) — Protective earth / bonding only; never phase or neutral
Jacket colour — — BV has no outer jacket; insulation is the outer layer
Mass per 100 m ≈ 2.9 kg/100 m For coil loading
Reference standard GB/T 5023 / IEC 60227 / JB/T 8734 — PVC insulated fixed wiring wire
Schematic — not to exact scale. Finished Ø ≈ 3.4 mm and weight ≈ 29 kg/km from cross-referenced industry samples; solid pure copper conductor Ø 1.78 mm, 0.8 mm green-yellow striped PVC insulation. Pure copper (not tinned). Est. values confirmed against factory type certificate.


Construction Description


Construction Description — BV 1×2.5 mm² (Green-Yellow PE)
Layer-by-layer build-up narrative · 450/750 V green-yellow striped protective earth building wire · GB/T 5023 / IEC 60227 · pure annealed copper solid conductor / striped PVC insulation
1. Product Identity & Ratings
BV 1×2.5 (Green-Yellow) is a 450/750 V single-core PVC insulated building wire intended as a protective earth (PE) conductor. The conductor is pure annealed bare copper (not tinned), selected for a low-resistance, reliable fault-current bonding path. One 2.5 mm² solid copper core is covered by a green-yellow striped PVC extrusion. There is no braid shield, no inner sheath and no outer jacket. OD ≈ 3.4 mm, ≈ 29 kg/km. Max 70 °C, -15 to +70 °C. The striped jacket is the internationally recognised PE identification and must be used for earthing only.
2. Pure Copper Conductor
The 2.5 mm² conductor is a single solid annealed copper wire, Class 1, diameter 1.78 mm. Solid construction keeps the wire dimensionally stable and easy to seat in earthing terminals and lugs. DC resistance ≤ 7.41 Ω/km at 20 °C per GB/T 3956; low loop resistance matters because the PE conductor must carry fault current to the protective device quickly. Pure bare copper is used in dry, enclosed locations; for damp or outdoor sites a tinned variant should be considered.
3. Green-Yellow Striped PVC Insulation
A 0.8 mm PVC compound extruded over the solid copper core carries longitudinal green and yellow stripes, forming the only insulating and outer layer. The insulation provides the primary electrical barrier for 450/750 V circuits, with insulation resistance ≥ 20 MΩ·km at 20 °C. The two-colour stripe scheme makes the earth wire unmistakable at every terminal and along the run; stripe colours and proportions follow the applicable wiring standard.
4. Lay-Up & PE Colour Coding
As a single-core wire there is no stranding of multiple cores, fillers or bedding. The green-yellow combination is reserved exclusively for protective earthing and equipotential bonding. It must never be repurposed as a phase, neutral or control conductor, and its stripes must not be overprinted, painted over or stripped away at terminations where identification is needed.
5. Surface Marking & Application Range
The striped jacket is printed at regular intervals with the designation BV, cross-section, voltage rating, manufacturer, metre mark and a PE identification note; the print remains legible against both colours. The wire is designed for fixed indoor earthing inside conduits, trunking and panel enclosures: socket outlet earth contacts, distribution board PE bars, equipment bonding and panel earthing. It is not a flexible appliance cable, not a shielded signal cable and not a submersible or direct-burial wire.

8. Factory Advantages

Pure annealed solid copper gives stable, low-resistance bonding that helps the protective device clear fault current quickly. Continuous striped PVC extrusion produces a smooth, consistent wall with an even two-colour pattern and predictable diameter, without blisters or pinholes. The dedicated PE colour scheme keeps earth lots separate from phase and neutral stock, reducing mix-ups at the site. The jacket takes a legible print that stays readable after installation. The solid core seats squarely in PE lugs and terminals, lowering loose-connection risk. Every coil undergoes 100% routine electrical QA and continuity check. Cut-to-length coils with sealed ends cut site waste. At ≈ 29 kg/km the wire stays light to pull through conduit.


BV 2.5mm² Green-Yellow Building Wire Solid Copper Single Core PVC Insulated Protective Earth Cable

9. Packaging, Storage & Logistics

Cut to requested length on export-grade coils; both ends sealed against moisture. Coils are wrapped in waterproof film and cardboard, clearly labelled BV, PE designation, cross-section, green-yellow colour, length, weight, production date and reel number. Common lengths 100/200/500/1000 m; custom cuts available. Store indoors at -10 to +40 °C, below 75% RH, away from sunlight, solvents and chemical vapours. Keep the film on until installation to preserve jacket surface and stripe clarity; prolonged sun exposure can dull both colours. PE lots are packed separately from coloured phase wire to prevent mis-dispatch. Shipping terms FOB Shanghai/Nanjing/Qingdao; CIF and DAP on request. Sample lead 5–7 days, bulk 15–25 days.


BV 2.5mm² Green-Yellow Building Wire Solid Copper Single Core PVC Insulated Protective Earth Cable

10. Procurement Specification

Order wording: "BV 1×2.5 pure copper, green-yellow striped protective earth (PE) wire". Ask for the routine 2000 V AC withstand record, DC resistance certificate and continuity check for the specific lot. Confirm the 2.5 mm² cross-section satisfies PE sizing rules for the associated phase conductor and protective device in the target installation. Note this is a bare pure copper fixed-wiring variant for dry indoor use; for damp or outdoor service, select a tinned or appropriate insulated variant instead. Never order this striped wire for phase or neutral duty. State any regional certification requirements (CE, etc.) at order time. Terms: 30% T/T deposit, balance against B/L copy. Documents: MTC, ROHS/REACH, COO, commercial invoice, packing list.

11. Cable Industry FAQ

Q1: What does "BV" designate? B denotes copper conductor, V denotes PVC insulation; BV is the standard Chinese code for a single-core PVC insulated fixed-wiring wire, corresponding to plain building wire under IEC 60227 practice.

Q2: What does green-yellow striping mean? The two-colour scheme is reserved exclusively for protective earthing and equipotential bonding; it identifies the safety conductor at a glance anywhere along the circuit.

Q3: Can this wire be used as a phase or neutral? No. Green-yellow PE wire must only carry fault current in the earthing path; using it for live or neutral duty violates wiring safety rules and creates a serious shock hazard.

Q4: Solid or stranded conductor? Solid Class 1 pure annealed copper wire, Ø 1.78 mm; DC resistance ≤ 7.41 Ω/km at 20 °C.

Q5: What is the rated voltage? 450/750 V, intended for low-voltage fixed indoor earthing and bonding circuits.

Q6: Does the PE wire carry load current? No normal load current; it carries fault current only when an insulation failure occurs, and its low loop resistance helps the protective device trip quickly.

Q7: Why pure copper rather than tinned? Bare pure copper offers the highest conductivity for dry indoor bonding contacts; tinned copper is normally reserved for damp or exposed locations where corrosion could attack bare copper.

Q8: How is PE sizing checked? Cross-section is matched to the phase conductor and upstream protective device according to local wiring rules; confirm the 2.5 mm² rating against those rules before ordering.

Q9: Is there any shielding on BV? None — BV is an unshielded single-core building wire. EMI-sensitive signal circuits call for a shielded RVVP multiconductor cable instead.

Q10: What certification ships with the coil? Routine 2000 V AC test record, DC resistance certificate, continuity check and MTC, with stripe integrity noted on the appearance inspection.

Q11: When should BVR be chosen over BV? For frequent flexing, vibrating equipment connections or tight panel gaps, choose the stranded BVR variant; BV solid is best suited to straight, stationary fixed earthing runs.