BV 2.5mm² Green Building Wire Solid Copper Single Core PVC Insulated 450/750V Earth Wiring

BV 2.5mm² Green Building Wire Solid Copper Single Core PVC Insulated 450/750V Earth Wiring

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
BV-2.5mm²

Trading Properties

moq
100 meters
unit price
USD 0.13-0.16/Meter
payment method
L/C,T/T
supply capacity
100000 rolls per month

Product Summary

BV 2.5mm² Green Building Wire Solid Copper Single Core PVC Insulated 450/750V Earth Wiring Cable Designation & Meaning Code Meaning B Building Wire V PVC insulation 1×2.5 mm² Single core of 2.5 mm² copper conductor Green White PVC insulation (for civil indoor visible wiring) Construction: One 2.5 mm...

Product Details

Highlight:

2.5mm² green building wire

,

solid copper single core wire

,

PVC insulated earth wiring

Conductor nominal area:
2.5 Mm² (Cu) × 1
Number of cores:
1 (single-core)
Conductor material:
Copper (Cu)
Conductor class:
Class 1 Solid
Conductor construction:
1×∅1.78 Mm
Conductor diameter:
≈ 1.78 Mm
Insulation thickness (nom.):
0.8 Mm
Insulation thickness (min.):
0.62 Mm
Overall cable diameter:
3.2 – 4.2 Mm
Design outer diameter:
≈ 3.7 Mm
Approx. weight:
30 – 42 Kg/km
Design weight:
≈ 36 Kg/km
Cable shape:
Round

Product Description

BV 2.5mm² Green Building Wire Solid Copper Single Core PVC Insulated 450/750V Earth Wiring

Cable Designation & Meaning

Code

Meaning

B

Building Wire

V

PVC insulation 

1×2.5 mm²

Single core of 2.5 mm² copper conductor

Green

White PVC insulation (for civil indoor visible wiring)


Construction: One 2.5 mm² solid copper conductor, white PVC insulation applied directly over the conductor.


BV 2.5mm² Green Building Wire Solid Copper Single Core PVC Insulated 450/750V Earth Wiring

BV 1×2.5 mm² (Green) — Single-Core PVC Insulated Copper Building Wire — Specification

1. Overview & Ratings

BV 1×2.5 (Green) is a 450/750 V single-core PVC insulated building wire built around one solid pure annealed copper conductor (bare, not tinned). The plain green jacket is allocated to a dedicated auxiliary or phase conductor under the project colour schedule, providing a stable, easily recognised circuit identity inside panels and raceways. A single 2.5 mm² copper wire carries each run; there is no braid, no inner sheath and no outer jacket. Finished OD ≈ 3.4 mm, ≈ 29 kg/km (est.), rated ampacity ≈ 20–25 A in conduit. Service range -15 to +70 °C. Plain green must not be confused with protective earthing, which always uses green-yellow striped insulation. Fixed indoor wiring only.

2. Construction Stack (Inner → Outer, expanded)

Layer / Feature Build Function
Conductor Pure annealed Cu, solid Class 1, Ø 1.78 mm R ≤ 7.41 Ω/km, fixed wiring
Insulation Green PVC ≈ 0.8 mm wall 450/750 V dielectric, auxiliary/phase ID
Shield None Single-core unshielded wire
Outer jacket None Insulation forms the outer layer

3. Electrical Characteristics

DC resistance ≤ 7.41 Ω/km at 20 °C per GB/T 3956 Class 1 pure copper. Rated 450/750 V. Estimated load capacity ≈ 20–25 A in conduit at 30 °C, up to ≈ 32 A in free air, reduced when bundled in enclosures. Insulation resistance ≥ 20 MΩ·km. Every routine coil passes a 2000 V AC withstand test held 5 minutes. Typical capacitance ≈ 150 pF/m at 1 kHz. Since each wire runs one conductor, its circuit role is established by matching the green jacket and printed marking to the one-line diagram; colour alone should never be treated as proof of phase, neutral or earth without cross-checking the schedule.

Insulation & Sheath Data

Property

Value

Insulation material

White PVC (Type TI1 or TI2)

Outer sheath material

None​ (non-sheathed)

Shield material

None​

Long-term service temp.

70 °C (continuous, TI1/TI2)

Max. conductor temp. (normal)

70 °C

Short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Test voltage AC (5 min)

2.5 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹² Ω·cm

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

450 / 750 V

GB/T 5023.3 (fixed wiring)

Max. system voltage

500 V AC / 750 V DC

—

Test voltage AC (5 min)

2.5 kV

Routine test

DC resistance @20 °C

≤ 7.41 Ω/km

GB/T 3956 Class 1 Cu max (2.5 mm²)

AC resistance @70 °C (est.)

≈ 9.28 Ω/km

—

Current rating in air (30 °C)

24 A​ (reference, single-core open)

typical residential

Current rating in conduit (30 °C)

20 A​ (reference, 2-core conduit)

typical installation

DC current capacity

24 A​

—

Short-circuit current (1 s, Cu, 160 °C)

≈ 275 A

—

Capacitance (core-to-ambient, approx.)

≈ 0.10 µF/km

PVC

Inductive reactance (approx.)

≈ 0.10 Ω/km

at 50 Hz (single-core)

Frequency

50/60 Hz AC, DC

—


Reference values: BV 2.5 (white) at 24 A, 230 V AC → max load ≈ 5,520 VA​ (typical lighting/socket circuit). At 24 V DC → max load ≈ 576 W.

4. Thermal & Flame Behaviour

Normal continuous operation -15 to +70 °C; short-circuit withstand up to 160 °C for up to 5 seconds. The green PVC compound meets IEC 60332-1 flame retardancy and self-extinguishes once the ignition source is removed. It is halogen-containing PVC, so in a fire it releases HCl gas; avoid it in public, high-density or escape-route wiring where LSZH insulation is mandated. The medium green surface keeps a tidy appearance and masks light dust and minor marks better than pale jackets, but it should still stay inside conduit, trunking or a closed tray to avoid long-term sunlight and abrasion. Bare copper contacts belong in dry, enclosed locations only.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

70 °C (continuous)

Max. short-circuit temp. (≤5 s)

160 °C

Emergency overload temp.

100 °C (≤1 h)

Min. installation ambient temp.

−15 °C

Service ambient range

−15 °C to +70 °C

Flexing temp. range

Not recommended for flexing


Fire Performance (BV — PVC, Non-Low-Smoke)

Property

Value / Requirement

Flame retardant

GB/T 18380.3 / IEC 60332-3​ (Category A/B/C as specified)

Halogen content

Contains halogen​ (PVC)

Smoke density

Not low-smoke​ (IEC 61034-2 not applicable)

Corrosivity

Corrosive​ (HCl emission from PVC)

Toxicity

Toxic fumes​ when burned (CO, HCl)

EMI shielding

None​

UV resistance

Poor​ (PVC degrades outdoors, use conduit)

Water resistance

Limited​ (PVC insulation only)

5. Installation Practice & Handling

Minimum bend radius ≥ 4×OD ≈ 14 mm. The solid Class 1 core is stiff and dimensionally stable; lay out straight runs with generous corner radii and avoid repeated back-and-forth bending. Strip the green jacket cleanly, seat the solid wire fully into the terminal block or lug, and tighten to the rated torque. Before connecting, confirm on the one-line diagram whether this green conductor acts as the designated auxiliary or phase in that circuit. Route live, neutral and earth together in the same conduit; keep plain green physically separate from any green-yellow striped PE wire to prevent misidentification during later maintenance. Record insulation resistance and continuity before energizing.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 4 × OD → ≈ 15 mm at Ø3.7 mm

solid conductor

Max. pulling tension

150 N (2.5 mm² × 60 N/mm²)

Cu conductor limit

Direct burial

Not recommended​ (PVC, no sheath, water ingress)

—

Surface mounting

Conduit, trunking, surface-mounted wiring channel, DIN rail

—

Conduit ID

≥ 16 mm (single), ≥ 20 mm (multiple)

—

Fixing

cable clips, staples, trunking clips

—

Impact resistance

Low (PVC)

—

Water resistance

Limited​ (no sheath)

—

UV resistance

Poor​ (indoor/conduit only)

—

Flex life

Poor​ (Class 1 solid, NOT for flexing)

—

Termination note

Screw terminals, compression lugs (2.5 mm²)

—


6. Typical Service Applications

Fixed indoor wiring across residential, commercial and light industrial installations: auxiliary conductors in distribution boards, internal panel wiring, designated phase or control runs in lighting and socket circuits, and branch feeders where the contractor's colour schedule reserves plain green for a specific circuit function. The medium-tone jacket keeps installed wiring looking clean in service. Accepted installation methods include conduit, trunking, cable tray and embedded wall wiring. It is unsuitable for: moving or trailing machine leads, shielded instrumentation signals, outdoor UV-exposed runs, submersible or buried circuits, and high-temperature heating elements.


BV 2.5mm² Green Building Wire Solid Copper Single Core PVC Insulated 450/750V Earth Wiring

7. Testing & Quality Assurance Regime

Routine tests on 100% of production: DC resistance, 2000 V/5 min AC withstand, insulation resistance, conductor construction, insulation thickness, dimensional inspection, dark-print legibility against the green jacket, mass per unit length, appearance and shade uniformity, and packing. Type tests per material batch or design change: heat aging at 100 °C for 7 days, cold bend at -15 °C, insulation tensile strength and elongation, flame retardancy, insulation flexibility, and wall thickness uniformity. Every coil ships with a mill test certificate plus ROHS and REACH declarations. Green lots are visually checked for even pigment dispersion, free from pale patches or darker streaks.


The Wire Parameters


BV 1×2.5 mm² (Green) — Full Parameter Sheet
Single-core green PVC insulated building wire · 450/750 V · pure annealed Cu solid Class 1 · green PVC insulation · no shield, no outer jacket · GB/T 5023 / IEC 60227
Section Parameter Value Unit Remarks / Standard
01 · Identification

Cable type BV (Green) — Single-core, green PVC insulated, pure Cu conductor

Rated voltage (U0/U) 450/750 V Fixed indoor wiring

Number of cores 1 — Single core, solid

Nominal cross-section 2.5 mm² Per core, Class 1 solid

Conductor material Pure annealed copper (bare) — Class 1 per GB/T 3956, not tinned

Insulation material PVC (green) — 70 °C rated, 0.8 mm wall

Shield None — No braid / foil on single-core wire

Outer jacket None — Insulation forms the outer layer

Standard reference GB/T 5023 / IEC 60227 / JB/T 8734 — PVC insulated fixed wiring wire
02 · Conductor

Conductor form Solid (single wire) — Class 1

Conductor diameter 1.78 mm Solid wire

DC resistance @ 20 °C ≤ 7.41 Ω/km Maximum per GB/T 3956 (pure Cu)

Conductor surface Bare pure copper — Not tinned; fixed indoor use
03 · Insulation

Insulation type PVC (green) — Soft PVC, 70 °C

Insulation thickness ≈ 0.8 mm Nominal

Finished diameter ≈ 3.4 mm Insulation outer Ø

Insulation resistance ≥ 20 MΩ·km At 20 °C
04 · Lay-Up & Shield

Core lay-up Not applicable — Single-core wire

Filler / bedding None — No inner sheath on BV

Shield type None — Unshielded building wire

Shield coverage — — Not applicable
05 · Insulation Finish

Outer surface Smooth green PVC extrusion — Uniform medium-tone colour

Printing Designation / size / voltage / metre mark — Dark print at regular intervals

Insulation colour Green (plain) — Auxiliary/phase; PE = green-yellow striped only
06 · Electrical

Rated voltage 450/750 V Fixed wiring

Test voltage (AC) 2000 V AC 5 min routine

DC resistance @ 20 °C ≤ 7.41 Ω/km Per GB/T 3956 (pure Cu)

Ampacity (conduit, est.) ≈ 20–25 A 2.5 mm², 70 °C

Ampacity (free air, est.) Up to ≈ 32 A Derate for grouping / enclosure

Capacitance ≈ 150 pF/m At 1 kHz
07 · Thermal & Mechanical

Max continuous conductor temp. 70 °C Normal service

Short-circuit temp. (≤5 s) 160 °C Copper limit

Min. ambient temp. -15 °C Fixed installation

Min. bending radius ≥ 4 × OD ≈ 14 mm Fixed wiring, solid core

Halogen content Halogen-containing — PVC compound
08 · Flame & Environment

Flame retardancy IEC 60332-1 — Single vertical flame

Oil resistance Limited — PVC insulation

UV resistance Limited — Indoor / conduit use; keep out of long sunlight

Corrosion resistance Limited (bare Cu) — Dry indoor only; use tinned variant for damp/outdoor

ROHS / REACH Compliant — EU 2011/65/EU


The Wire Test Parameters


Test Parameters — BV 1×2.5 mm² (Green)
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3956, 20 °C ≤ 7.41 Ω/km Routine
2 AC voltage withstand 2000 V AC, 5 min No breakdown Routine
3 Insulation resistance 500 V megohmmeter ≥ 20 MΩ·km Routine
4 Conductor construction Visual + micrometer Solid Ø 1.78 mm pure Cu Routine
5 Insulation thickness Micrometer cross-section ≈ 0.8 mm Routine
6 Dimensional check Caliper OD ≈ 3.4 mm Routine
7 Print legibility Visual + rubbing Dark print legible on green Routine
8 Mass per unit length Weighing ≈ 29 kg/km Routine
9 Appearance / colour Visual Smooth, uniform green, no patches Routine
10 Packing Visual Coil, sealed ends, labelled Routine
11 Heat aging test 7 days at 100 °C Retention ≥ 70% Type
12 Cold bend test -15 °C, 4 h mandrel No cracking Type
13 Insulation tensile & elongation Universal tester Meets GB/T 5023 min. Type
14 Flame retardancy IEC 60332-1 Self-extinguish Type
15 Insulation flexibility Mandrel bend at ambient No cracking, no peeling Type
16 Wall thickness uniformity Micrometer at 4 points Min. wall ≥ nominal − tolerance Type


Cross Section Structure


BV 2.5mm² Green Building Wire Solid Copper Single Core PVC Insulated 450/750V Earth Wiring

BV 1×2.5 mm² (Green) — Cross-Section Construction Diagram (Schematic)
Layered build-up: pure copper solid conductor (single core) → green PVC insulation · 450/750 V single-core PVC insulated building wire · auxiliary / phase identification per local schedule · no shield, no outer jacket · -15~+70 °C
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor Pure annealed copper, solid Class 1 — single wire Ø 1.78 mm — 1.78 Fixed wiring; R ≤ 7.41 Ω/km; bare pure copper for high conductivity
2 Insulation Green PVC compound, extruded over the solid conductor ≈ 0.8 ≈ 3.4 (finished) Primary electrical insulation; 450/750 V rated; plain green auxiliary/phase ID — not green-yellow PE






Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 3.4 mm Single-core PVC building wire (est.)
Approximate cable mass ≈ 29 kg/km Pure Cu + PVC insulation
Nominal voltage rating 450/750 V Fixed indoor wiring
Max continuous conductor temp. 70 °C Normal service
Min. ambient / installation temp. -15 °C Fixed installation
DC resistance @ 20 °C ≤ 7.41 Ω/km Class 1 pure copper, GB/T 3956
Core count × cross-section 1 × 2.5 mm² Single core, solid
Shielding None — Single-core wire, no braid / foil
Insulation resistance ≥ 20 MΩ·km PVC at 20 °C
Test voltage (AC) 2000 V AC / 5 min — Routine withstand test
Flame retardancy IEC 60332-1 — Single vertical flame
Insulation colour Green (plain, designated) — Auxiliary/phase; PE must be green-yellow striped
Jacket colour — — BV has no outer jacket; insulation is the outer layer
Mass per 100 m ≈ 2.9 kg/100 m For coil loading
Reference standard GB/T 5023 / IEC 60227 / JB/T 8734 — PVC insulated fixed wiring wire
Schematic — not to exact scale. Finished Ø ≈ 3.4 mm and weight ≈ 29 kg/km from cross-referenced industry samples; solid pure copper conductor Ø 1.78 mm, 0.8 mm green PVC insulation. Pure copper (not tinned). Est. values confirmed against factory type certificate.


Construction Description


Construction Description — BV 1×2.5 mm² (Green)
Layer-by-layer build-up narrative · 450/750 V single-core green PVC insulated building wire · GB/T 5023 / IEC 60227 · pure annealed copper solid conductor / green PVC insulation
1. Product Identity & Ratings
BV 1×2.5 (Green) is a single-core PVC insulated building wire rated 450/750 V. The conductor is pure annealed bare copper (not tinned), selected for dependable conductivity and long-term contact in stationary wiring. One 2.5 mm² solid copper core is covered by a continuous green PVC extrusion. There is no braid shield, no inner sheath and no outer jacket. OD ≈ 3.4 mm, ≈ 29 kg/km. Max 70 °C, -15 to +70 °C. The plain green jacket marks a dedicated auxiliary or phase conductor under the project colour schedule.
2. Pure Copper Conductor
The 2.5 mm² conductor is a single solid annealed copper wire, Class 1, diameter 1.78 mm. Solid construction keeps the wire dimensionally stable and easy to seat in terminals and connectors. DC resistance ≤ 7.41 Ω/km at 20 °C per GB/T 3956. Pure bare copper provides the highest conductivity available for fixed installation; for damp or outdoor locations a tinned or insulated variant should be considered separately.
3. Green PVC Insulation
A 0.8 mm green PVC compound is extruded continuously over the solid copper core, forming the only insulating and outer layer. The insulation provides the primary electrical barrier for 450/750 V circuits, with insulation resistance ≥ 20 MΩ·km at 20 °C. The medium green surface retains a tidy look in service and masks light dust and minor marks; dark lettering is printed on the jacket for legibility.
4. Lay-Up & Colour Coding
As a single-core wire there is no stranding of multiple cores, fillers or bedding. Colour allocation varies by national practice; plain green typically serves as an auxiliary or phase conductor in panel wiring. Crucially, plain green is never a protective earth conductor: PE wiring must use green-yellow striped insulation, reserved exclusively for earthing.
5. Surface Marking & Application Range
The green insulation surface is printed at regular intervals with the designation BV, cross-section, voltage rating, manufacturer and metre mark; dark print remains legible against the jacket. The wire is designed for fixed installation inside conduits, trunking and panel enclosures: lighting circuits, socket outlets, panel internal wiring and branch circuits. It is not a flexible appliance cable, not a shielded signal cable and not a submersible or direct-burial wire.

8. Factory Advantages

Pure annealed solid copper gives stable conductivity and low resistance over long fixed runs. Continuous green PVC extrusion produces a smooth, consistent wall with a uniform medium shade and predictable diameter, without blisters or pinholes. Green is a standard stocked colour, which shortens lead times on general wiring orders. The jacket takes a dark, legible print that stays readable after installation. The solid core seats squarely in terminals, lowering the risk of loose joints. Every coil undergoes 100% routine electrical QA. Cut-to-length coils with sealed ends cut site waste. At ≈ 29 kg/km the wire stays light to pull through conduit. Full traceability is supported by MTC and certification packages for building-wiring tenders.


BV 2.5mm² Green Building Wire Solid Copper Single Core PVC Insulated 450/750V Earth Wiring

9. Packaging, Storage & Logistics

Cut to requested length on export-grade coils; both ends sealed against moisture. Coils are wrapped in waterproof film and cardboard, labelled with BV designation, cross-section, green colour, length, weight, production date and reel number. Common lengths 100/200/500/1000 m; custom cuts available. Store indoors at -10 to +40 °C, below 75% RH, away from sunlight, solvents and chemical vapours. Keep the film on until installation to preserve the jacket surface; green pigment is reasonably stable indoors, but prolonged sun exposure and solvent contact can still dull or stain it. Shipping terms FOB Shanghai/Nanjing/Qingdao; CIF and DAP on request. Sample lead 5–7 days, bulk 15–25 days. Different colours are packed and labelled in separate lots.


BV 2.5mm² Green Building Wire Solid Copper Single Core PVC Insulated 450/750V Earth Wiring

10. Procurement Specification

Order wording: "BV 1×2.5 pure copper, plain green insulation". Ask for the routine 2000 V AC withstand record and the DC resistance certificate for the specific green lot. Note this is a bare pure copper fixed-wiring variant for dry indoor use; for damp or outdoor service, select a tinned or appropriate insulated variant instead. Before ordering, confirm with the project colour schedule whether plain green is the assigned auxiliary or phase in that region — and never substitute it for the green-yellow striped protective earth conductor. State any regional certification requirements (CE, etc.) at order time. Terms: 30% T/T deposit, balance against B/L copy. Documents: MTC, ROHS/REACH, COO, commercial invoice, packing list.

11. Cable Industry FAQ

Q1: What does "BV" designate? B denotes copper conductor, V denotes PVC insulation; BV is the standard Chinese code for a single-core PVC insulated fixed-wiring wire, corresponding to plain building wire under IEC 60227 practice.

Q2: Is plain green the protective earth wire? No. Protective earthing uses green-yellow striped insulation only. Plain green is an auxiliary or phase conductor; using it as PE violates wiring safety rules.

Q3: Why specify a green jacket? Green provides a dedicated, stable circuit identity in panel and raceway wiring, matching the contractor's colour schedule; its medium tone also keeps the installed run looking tidy.

Q4: Solid or stranded conductor? Solid Class 1 pure annealed copper wire, Ø 1.78 mm; DC resistance ≤ 7.41 Ω/km at 20 °C.

Q5: What is the rated voltage? 450/750 V, intended for low-voltage fixed indoor lighting, socket and panel circuits.

Q6: How much current does 2.5 mm² carry? ≈ 20–25 A in conduit, up to ≈ 32 A in free air, derated for grouping and enclosure; match against local wiring rules and the upstream protective device.

Q7: Why pure copper rather than tinned? Bare pure copper offers the highest conductivity for dry indoor fixed contacts; tinned copper is normally reserved for damp or exposed locations where corrosion could attack bare copper.

Q8: Does green discolour in storage? Green pigment is reasonably stable indoors, but keep coils wrapped and away from direct sun and solvents; prolonged exposure can dull the shade or leave stains.

Q9: Is there any shielding on BV? None — BV is an unshielded single-core building wire. EMI-sensitive signal circuits call for a shielded RVVP multiconductor cable instead.

Q10: What certification ships with the coil? Routine 2000 V AC test record, DC resistance certificate and MTC, with shade uniformity noted on the appearance inspection.

Q11: When should BVR be chosen over BV? For frequent flexing, vibrating equipment connections or tight panel gaps, choose the stranded BVR variant; BV solid is best suited to straight, stationary fixed runs.