BV 2.5mm² White Building Wire Solid Copper Single Core PVC Insulated 450/750V for Fixed Domestic Power Wiring
Product Summary
Product Details
2.5mm² solid copper building wire
,PVC insulated single core wire
,450/750V fixed domestic power wiring
Product Description
BV 2.5mm² White Building Wire Solid Copper Single Core PVC Insulated 450/750V for Fixed Domestic Power Wiring
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
B |
Building Wire |
|
V |
PVC insulation |
|
1×2.5 mm² |
Single core of 2.5 mm² copper conductor |
|
White |
White PVC insulation (for civil indoor visible wiring) |
Construction: One 2.5 mm² solid copper conductor, white PVC insulation applied directly over the conductor.

BV 1×2.5 mm² (White) — Single-Core PVC Insulated Copper Building Wire — Specification
1. Overview & Ratings
BV 1×2.5 (White) is a single-core PVC insulated building wire rated 450/750 V. It uses pure annealed bare copper (not tinned) as a solid Class 1 conductor, chosen for high conductivity and stable long-term contact in fixed installation. One 2.5 mm² copper wire is covered by a continuous white PVC insulation; there is no braid shield, no inner sheath and no outer jacket. Finished OD ≈ 3.4 mm, ≈ 29 kg/km (est.), ≈ 20–25 A in conduit. Max conductor temperature 70 °C, -15 to +70 °C. The white finish serves as a supplementary phase, neutral or common-return conductor under the project wiring schedule. Intended for fixed indoor wiring; not for trailing drag chains, outdoor UV exposure or direct burial.
2. Construction Stack (Inner → Outer, expanded)
| Layer / Feature | Build | Function |
|---|---|---|
| Conductor | Pure annealed Cu, solid Class 1, Ø 1.78 mm | R ≤ 7.41 Ω/km, fixed wiring |
| Insulation | White PVC ≈ 0.8 mm wall | 450/750 V dielectric, circuit identification |
| Shield | None | Single-core unshielded wire |
| Outer jacket | None | Insulation forms the outer layer |
3. Electrical Characteristics
DC resistance ≤ 7.41 Ω/km at 20 °C per GB/T 3956 Class 1 pure copper. Rated voltage 450/750 V. Estimated ampacity ≈ 20–25 A in conduit at 30 °C, up to ≈ 32 A in free air, with derating for grouping and enclosure. Insulation resistance ≥ 20 MΩ·km. Routine AC withstand test at 2000 V for 5 minutes. Typical capacitance ≈ 150 pF/m at 1 kHz. As a single-core wire it carries one phase, neutral or earth conductor per run; circuit identification is handled by the white insulation colour rather than internal pairing.
Insulation & Sheath Data
|
Property |
Value |
|---|---|
|
Insulation material |
White PVC (Type TI1 or TI2) |
|
Outer sheath material |
None (non-sheathed) |
|
Shield material |
None |
|
Long-term service temp. |
70 °C (continuous, TI1/TI2) |
|
Max. conductor temp. (normal) |
70 °C |
|
Short-circuit temp. (≤5 s) |
160 °C |
|
Emergency overload temp. |
100 °C (≤1 h) |
|
Test voltage AC (5 min) |
2.5 kV |
|
Dielectric strength |
≥ 20 kV/mm |
|
Volume resistivity @20 °C |
≥ 1×10¹² Ω·cm |
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
450 / 750 V |
GB/T 5023.3 (fixed wiring) |
|
Max. system voltage |
500 V AC / 750 V DC |
— |
|
Test voltage AC (5 min) |
2.5 kV |
Routine test |
|
DC resistance @20 °C |
≤ 7.41 Ω/km |
GB/T 3956 Class 1 Cu max (2.5 mm²) |
|
AC resistance @70 °C (est.) |
≈ 9.28 Ω/km |
— |
|
Current rating in air (30 °C) |
24 A (reference, single-core open) |
typical residential |
|
Current rating in conduit (30 °C) |
20 A (reference, 2-core conduit) |
typical installation |
|
DC current capacity |
24 A |
— |
|
Short-circuit current (1 s, Cu, 160 °C) |
≈ 275 A |
— |
|
Capacitance (core-to-ambient, approx.) |
≈ 0.10 µF/km |
PVC |
|
Inductive reactance (approx.) |
≈ 0.10 Ω/km |
at 50 Hz (single-core) |
|
Frequency |
50/60 Hz AC, DC |
— |
Reference values: BV 2.5 (white) at 24 A, 230 V AC → max load ≈ 5,520 VA (typical lighting/socket circuit). At 24 V DC → max load ≈ 576 W.
4. Thermal & Flame Behaviour
Operating range -15 to +70 °C continuous. Short-circuit withstand up to 160 °C for ≤ 5 seconds. The white PVC insulation is flame-retardant per IEC 60332-1 and self-extinguishing after the ignition source is removed. The cable is halogen-containing (PVC), emitting HCl gas on burning — avoid in enclosed public or high-density spaces where LSZH wiring is required. The white surface shows dirt and abrasion more readily than dark colours, so protect it from direct sunlight, solvents and prolonged moisture. Bare copper should be terminated in dry, enclosed locations.
Temperature Characteristics
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
70 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
160 °C |
|
Emergency overload temp. |
100 °C (≤1 h) |
|
Min. installation ambient temp. |
−15 °C |
|
Service ambient range |
−15 °C to +70 °C |
|
Flexing temp. range |
Not recommended for flexing |
Fire Performance (BV — PVC, Non-Low-Smoke)
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.3 / IEC 60332-3 (Category A/B/C as specified) |
|
Halogen content |
Contains halogen (PVC) |
|
Smoke density |
Not low-smoke (IEC 61034-2 not applicable) |
|
Corrosivity |
Corrosive (HCl emission from PVC) |
|
Toxicity |
Toxic fumes when burned (CO, HCl) |
|
EMI shielding |
None |
|
UV resistance |
Poor (PVC degrades outdoors, use conduit) |
|
Water resistance |
Limited (PVC insulation only) |
5. Installation Practice & Handling
Minimum bending radius ≥ 4×OD ≈ 14 mm for fixed installation. The solid core is dimensionally stable but less flexible than stranded wire, so route straight runs with gentle bends and avoid repeated flexing. Terminate by stripping the insulation, inserting the solid wire into a terminal block, lug or connector, and tightening to the rated torque. Group live, neutral and earth conductors in the same conduit; keep white conductors identified per the project colour schedule. After installation, verify insulation resistance and continuity before energizing. Do not use this wire as a flexible appliance cord or drag-chain cable.
Mechanical & Installation Parameters
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 4 × OD → ≈ 15 mm at Ø3.7 mm |
solid conductor |
|
Max. pulling tension |
150 N (2.5 mm² × 60 N/mm²) |
Cu conductor limit |
|
Direct burial |
Not recommended (PVC, no sheath, water ingress) |
— |
|
Surface mounting |
Conduit, trunking, surface-mounted wiring channel, DIN rail |
— |
|
Conduit ID |
≥ 16 mm (single), ≥ 20 mm (multiple) |
— |
|
Fixing |
cable clips, staples, trunking clips |
— |
|
Impact resistance |
Low (PVC) |
— |
|
Water resistance |
Limited (no sheath) |
— |
|
UV resistance |
Poor (indoor/conduit only) |
— |
|
Flex life |
Poor (Class 1 solid, NOT for flexing) |
— |
|
Termination note |
Screw terminals, compression lugs (2.5 mm²) |
— |
6. Typical Service Applications
Fixed indoor wiring in residential, commercial and light industrial buildings: lighting circuits, socket outlet branch circuits, panel internal wiring, switchboard and distribution board connections, and control-panel internal conductor runs. The white insulation is commonly selected for supplementary phase, neutral or common-return conductors where a clearly distinguishable auxiliary wire is required inside cabinets and trunking. Typical installation methods: conduit, trunking, cable tray and embedded wall wiring. It is not designed for: shielded signal transmission, moving or trailing equipment, outdoor UV-exposed runs, submersible or buried circuits, or high-temperature heater wiring.

7. Testing & Quality Assurance Regime
Routine tests (100% production): DC resistance, AC voltage withstand (2000 V/5 min), insulation resistance, conductor construction, insulation thickness, dimensional check, print legibility, mass per length, appearance and colour uniformity, and packing. Type tests (per batch / material change): heat aging (100 °C/7 days), cold bend (-15 °C), insulation tensile and elongation, flame retardancy, insulation flexibility, and wall thickness uniformity. Every coil ships with mill test certificate, ROHS and REACH declarations. The 450/750 V rating uses a 2000 V withstand test; white lots are visually checked for consistent shade and freedom from streaks.
The Wire Parameters
| BV 1×2.5 mm² (White) — Full Parameter Sheet | ||||
| Single-core white PVC insulated building wire · 450/750 V · pure annealed Cu solid Class 1 · white PVC insulation · no shield, no outer jacket · GB/T 5023 / IEC 60227 | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | BV (White) | — | Single-core, white PVC insulated, pure Cu conductor | |
| Rated voltage (U0/U) | 450/750 | V | Fixed indoor wiring | |
| Number of cores | 1 | — | Single core, solid | |
| Nominal cross-section | 2.5 | mm² | Per core, Class 1 solid | |
| Conductor material | Pure annealed copper (bare) | — | Class 1 per GB/T 3956, not tinned | |
| Insulation material | PVC (white) | — | 70 °C rated, 0.8 mm wall | |
| Shield | None | — | No braid / foil on single-core wire | |
| Outer jacket | None | — | Insulation forms the outer layer | |
| Standard reference | GB/T 5023 / IEC 60227 / JB/T 8734 | — | PVC insulated fixed wiring wire | |
| 02 · Conductor | ||||
| Conductor form | Solid (single wire) | — | Class 1 | |
| Conductor diameter | 1.78 | mm | Solid wire | |
| DC resistance @ 20 °C | ≤ 7.41 | Ω/km | Maximum per GB/T 3956 (pure Cu) | |
| Conductor surface | Bare pure copper | — | Not tinned; fixed indoor use | |
| 03 · Insulation | ||||
| Insulation type | PVC (white) | — | Soft PVC, 70 °C | |
| Insulation thickness | ≈ 0.8 | mm | Nominal | |
| Finished diameter | ≈ 3.4 | mm | Insulation outer Ø | |
| Insulation resistance | ≥ 20 | MΩ·km | At 20 °C | |
| 04 · Lay-Up & Shield | ||||
| Core lay-up | Not applicable | — | Single-core wire | |
| Filler / bedding | None | — | No inner sheath on BV | |
| Shield type | None | — | Unshielded building wire | |
| Shield coverage | — | — | Not applicable | |
| 05 · Insulation Finish | ||||
| Outer surface | Smooth white PVC extrusion | — | Uniform white colour | |
| Printing | Designation / size / voltage / metre mark | — | At regular intervals | |
| Insulation colour | White | — | Supplementary phase / neutral / common conductor | |
| 06 · Electrical | ||||
| Rated voltage | 450/750 | V | Fixed wiring | |
| Test voltage (AC) | 2000 | V AC | 5 min routine | |
| DC resistance @ 20 °C | ≤ 7.41 | Ω/km | Per GB/T 3956 (pure Cu) | |
| Ampacity (conduit, est.) | ≈ 20–25 | A | 2.5 mm², 70 °C | |
| Ampacity (free air, est.) | Up to ≈ 32 | A | Derate for grouping / enclosure | |
| Capacitance | ≈ 150 | pF/m | At 1 kHz | |
| 07 · Thermal & Mechanical | ||||
| Max continuous conductor temp. | 70 | °C | Normal service | |
| Short-circuit temp. (≤5 s) | 160 | °C | Copper limit | |
| Min. ambient temp. | -15 | °C | Fixed installation | |
| Min. bending radius | ≥ 4 × OD ≈ 14 | mm | Fixed wiring, solid core | |
| Halogen content | Halogen-containing | — | PVC compound | |
| 08 · Flame & Environment | ||||
| Flame retardancy | IEC 60332-1 | — | Single vertical flame | |
| Oil resistance | Limited | — | PVC insulation | |
| UV resistance | Limited | — | Indoor / conduit use | |
| Corrosion resistance | Limited (bare Cu) | — | Dry indoor only; use tinned variant for damp/outdoor | |
| ROHS / REACH | Compliant | — | EU 2011/65/EU | |
The Wire Test Parameters
| Test Parameters — BV 1×2.5 mm² (White) | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3956, 20 °C | ≤ 7.41 Ω/km | Routine |
| 2 | AC voltage withstand | 2000 V AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | 500 V megohmmeter | ≥ 20 MΩ·km | Routine |
| 4 | Conductor construction | Visual + micrometer | Solid Ø 1.78 mm pure Cu | Routine |
| 5 | Insulation thickness | Micrometer cross-section | ≈ 0.8 mm | Routine |
| 6 | Dimensional check | Caliper | OD ≈ 3.4 mm | Routine |
| 7 | Print legibility | Visual + rubbing | Marks legible | Routine |
| 8 | Mass per unit length | Weighing | ≈ 29 kg/km | Routine |
| 9 | Appearance / colour | Visual | Smooth, uniform white, no blisters | Routine |
| 10 | Packing | Visual | Coil, sealed ends, labelled | Routine |
| 11 | Heat aging test | 7 days at 100 °C | Retention ≥ 70% | Type |
| 12 | Cold bend test | -15 °C, 4 h mandrel | No cracking | Type |
| 13 | Insulation tensile & elongation | Universal tester | Meets GB/T 5023 min. | Type |
| 14 | Flame retardancy | IEC 60332-1 | Self-extinguish | Type |
| 15 | Insulation flexibility | Mandrel bend at ambient | No cracking, no peeling | Type |
| 16 | Wall thickness uniformity | Micrometer at 4 points | Min. wall ≥ nominal − tolerance | Type |
Cross Section Structure

| BV 1×2.5 mm² (White) — Cross-Section Construction Diagram (Schematic) | |||||
| Layered build-up: pure copper solid conductor (single core) → black PVC insulation · 450/750 V single-core PVC insulated building wire · fixed indoor lighting / socket / panel wiring · no shield, no outer jacket · -15~+70 °C | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Conductor | Pure annealed copper, solid Class 1 — single wire Ø 1.78 mm | — | 1.78 | Fixed wiring; R ≤ 7.41 Ω/km; bare pure copper for high conductivity |
| 2 | Insulation | Black PVC compound, extruded over the solid conductor | ≈ 0.8 | ≈ 3.4 (finished) | Primary electrical insulation; 450/750 V rated; black phase / general-purpose conductor identification |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 3.4 | mm | Single-core PVC building wire (est.) | ||
| Approximate cable mass | ≈ 29 | kg/km | Pure Cu + PVC insulation | ||
| Nominal voltage rating | 450/750 | V | Fixed indoor wiring | ||
| Max continuous conductor temp. | 70 | °C | Normal service | ||
| Min. ambient / installation temp. | -15 | °C | Fixed installation | ||
| DC resistance @ 20 °C | ≤ 7.41 | Ω/km | Class 1 pure copper, GB/T 3956 | ||
| Core count × cross-section | 1 × 2.5 | mm² | Single core, solid | ||
| Shielding | None | — | Single-core wire, no braid / foil | ||
| Insulation resistance | ≥ 20 | MΩ·km | PVC at 20 °C | ||
| Test voltage (AC) | 2000 V AC / 5 min | — | Routine withstand test | ||
| Flame retardancy | IEC 60332-1 | — | Single vertical flame | ||
| Insulation colour | Black (designated) | — | Phase / general-purpose auxiliary conductor | ||
| Jacket colour | — | — | BV has no outer jacket; insulation is the outer layer | ||
| Mass per 100 m | ≈ 2.9 | kg/100 m | For coil loading | ||
| Reference standard | GB/T 5023 / IEC 60227 / JB/T 8734 | — | PVC insulated fixed wiring wire | ||
| Schematic — not to exact scale. Finished Ø ≈ 3.4 mm and weight ≈ 29 kg/km from cross-referenced industry samples; solid pure copper conductor Ø 1.78 mm, 0.8 mm black PVC insulation. Pure copper (not tinned). Est. values confirmed against factory type certificate. | |||||
Construction Description
| Construction Description — BV 1×2.5 mm² (White) | |||
| Layer-by-layer build-up narrative · 450/750 V single-core white PVC insulated building wire · GB/T 5023 / IEC 60227 · pure annealed copper solid conductor / white PVC insulation | |||
| 1. Product Identity & Ratings | |||
| BV 1×2.5 (White) is a single-core PVC insulated building wire rated 450/750 V. The conductor is pure annealed bare copper (not tinned), chosen for high conductivity and stable long-term contact in fixed wiring. One 2.5 mm² solid copper core is covered by a continuous white PVC extrusion. There is no braid shield, no inner sheath and no outer jacket. OD ≈ 3.4 mm, ≈ 29 kg/km. Max 70 °C, -15 to +70 °C. Intended for fixed indoor wiring; not for moving drag chains or outdoor UV exposure. | |||
| 2. Pure Copper Conductor | |||
| The 2.5 mm² conductor is a single solid annealed copper wire, Class 1, diameter 1.78 mm. Solid construction keeps the wire dimensionally stable and easy to terminate in terminals and connectors. DC resistance ≤ 7.41 Ω/km at 20 °C per GB/T 3956. Pure bare copper provides the highest conductivity available for fixed installation; for damp or outdoor locations a tinned or insulated variant should be considered separately. | |||
| 3. White PVC Insulation | |||
| A 0.8 mm white PVC compound is extruded continuously over the solid copper core, forming the only insulating and outer layer. The insulation provides the primary electrical barrier for 450/750 V circuits, with insulation resistance ≥ 20 MΩ·km at 20 °C. The white surface is smooth, uniform in wall thickness, and makes the conductor easy to identify inside panels, conduits and trunking. | |||
| 4. Lay-Up & Colour Coding | |||
| As a single-core wire there is no stranding of multiple cores, fillers or bedding. In standard coding red denotes live/phase, blue neutral, green-yellow protective earth; white serves as a supplementary phase, neutral or common-return conductor as defined by the project wiring schedule. White wires are often used where a clearly distinguishable auxiliary or common conductor is required in panel work. | |||
| 5. Surface Marking & Application Range | |||
| The white insulation surface is printed at regular intervals with the designation BV, cross-section, voltage rating, manufacturer and metre mark. The wire is designed for fixed installation inside conduits, trunking and panel enclosures: lighting circuits, socket outlets, panel internal wiring and branch circuits. It is not a flexible appliance cable, not a shielded signal cable and not a submersible or direct-burial wire. |
8. Factory Advantages
Pure annealed solid copper delivers stable conductivity and low resistance across long fixed runs. Continuous white PVC extrusion gives a smooth, uniform wall with a consistent shade and diameter, free from blisters or streaks. White insulation makes the conductor easy to identify inside panels and conduits, reducing wiring errors at site. The solid core seats cleanly in terminal blocks and lugs, reducing loose-connection risk. 100% routine electrical QA on every coil. Cut-to-length packaging with sealed ends reduces waste. Lightweight ≈ 29 kg/km for easy coil handling. Full traceability with MTC and certification support for building-wiring tenders and project procurement.

9. Packaging, Storage & Logistics
Cut to customer-specified length on export-grade coils, with both ends sealed to prevent moisture ingress. Coils wrapped in waterproof film and cardboard, labelled with designation BV, cross-section, white colour, length, weight, production date and reel number. Standard lengths 100/200/500/1000 m; custom lengths available. Store dry indoor, -10 to +40 °C, below 75% RH, away from direct sunlight, solvents and chemical fumes; keep white coils shaded to prevent yellowing. FOB Shanghai/Nanjing/Qingdao; CIF and DAP available. Sample lead time 5–7 days; bulk production 15–25 days. Mixed-colour lots are packed and labelled separately.

10. Procurement Specification
State wire designation "BV 1×2.5 pure copper, white insulation", and length per coil. Request the routine AC withstand test record (2000 V) and DC resistance certificate for the specific white batch. Note this is a pure copper (bare) fixed-wiring variant for dry indoor use — for damp or outdoor locations, specify a tinned or appropriate insulated variant. Confirm the white conductor's circuit role against the project colour schedule before ordering. Specify any regional certification requirements (CE, etc.) at order time. Payment: 30% T/T deposit, balance against B/L copy. Documents: MTC, ROHS/REACH, COO, commercial invoice, packing list.
11. Cable Industry FAQ
Q1: What does "BV" mean? B denotes a copper conductor, V denotes PVC insulation; BV is the standard Chinese designation for a single-core PVC insulated fixed-wiring wire, equivalent to the plain building wire in IEC 60227 practice.
Q2: Why choose a white wire? White is a supplementary colour used for a designated phase, neutral or common-return conductor; its light shade stands out inside panels and conduits, making the auxiliary circuit easy to trace and verify.
Q3: Is the conductor solid or stranded? Solid Class 1 pure annealed copper wire, Ø 1.78 mm; DC resistance ≤ 7.41 Ω/km at 20 °C.
Q4: What is the voltage rating? 450/750 V, suitable for low-voltage fixed indoor lighting, socket and panel wiring.
Q5: What current can 2.5 mm² carry? ≈ 20–25 A in conduit, up to ≈ 32 A in free air, derated for grouping and enclosure; confirm against local wiring rules and circuit protection.
Q6: Why pure copper instead of tinned? Bare pure copper gives the highest conductivity for fixed indoor contacts; tinned copper is normally chosen where moisture or outdoor corrosion is a concern.
Q7: Will the white insulation turn yellow? Stable indoor PVC resists aging, but prolonged direct sunlight and heat can discolour it; store shaded and install inside conduit or protected raceway.
Q8: Does BV have a shield? No — BV is an unshielded single-core building wire. For EMI-sensitive signal circuits, use a shielded RVVP-type multiconductor cable.
Q9: What is the temperature range? -15 to +70 °C continuous.
Q10: What proof ships? Routine AC test record (2000 V) + DC resistance certificate + MTC, with white shade uniformity noted on the appearance check.
Q11: When should I choose BVR instead? Where the wire must bend frequently, connect to vibrating equipment, or fit tight panel gaps, choose the stranded BVR variant; BV solid is best for straight fixed runs.