WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE Cable 0.6/1kV

WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE Cable 0.6/1kV

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
WDZBN-YJY-3x50mm²+2x25mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
100000 meters per month

Product Summary

WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE Cable 0.6/1kV Cable Designation & Meaning Code Meaning 0.6/1 kV Rated voltage: U₀ = 0.6 kV (phase-to-earth), U = 1 kV (phase-to-phase) WD Low-smoke, zero-halogen (LSZH) ZB Flame retardant Category B (IEC 60332-3-23, Class B) ...

Product Details

Highlight:

xlpe 5 core cable

,

xlpe copper conductor cable

,

black 5 core cable

Conductor (×3, phase):
Copper, Class 2 Stranded, Nominal 19×∅1.78 Mm (50 Mm²), Conductor Ø ≈ 8.8–9.8 Mm
Conductor (×2, N/PE):
Copper, Class 2 Stranded, Nominal 7×∅2.14 Mm (25 Mm²), Conductor Ø ≈ 6.4–7.2 Mm
Fire barrier:
Mica Tape, 0.15–0.20 Mm × 2 Layers
Insulation:
XLPE (cross-linked Polyethylene), Nominal Thickness 1.0 Mm (for 0.6/1 KV Class), Colours: Red/black (phase), Blue (neutral), Yellow/green (earth)
Filler & bedding:
LSZH​ Filler, Round Profile, Inner LSZH Bedding Thickness ≈ 1.0 Mm
Outer sheath:
LSZH (low-smoke Zero-halogen)​ Compound, Nominal Thickness 2.0 Mm (typical), Colour: Orange​ Or Red​ (fire Identification)
Conductor nominal area:
50 Mm² (phase, ×3), 25 Mm² (N/PE, ×2)
Number of cores:
5
Conductor material:
Conductor Material
Conductor class:
Class 2 Stranded
Conductor construction (phase):
19×∅1.78 Mm (50 Mm²)
Conductor construction (N/PE):
Conductor Construction (N/PE)
Insulation thickness:
1.0 Mm
Bedding thickness:
1.0 Mm
Outer sheath thickness:
2.0 Mm
Overall cable diameter:
28 – 36 Mm
Design outer diameter:
≈ 32 Mm
Approx. weight:
2.2 – 2.8 Kg/m (2200–2800 Kg/km)
Design weight:
≈ 2500 Kg/km

Product Description

WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE Cable 0.6/1kV

Cable Designation & Meaning

Code

Meaning

0.6/1 kV

Rated voltage: U₀ = 0.6 kV (phase-to-earth), U = 1 kV (phase-to-phase)

WD

Low-smoke, zero-halogen (LSZH)

ZB

Flame retardant Category B (IEC 60332-3-23, Class B)

N

Fire-resistant (circuit integrity under fire, mica tape)

YJ

XLPE (cross-linked polyethylene) insulation

Y

LSZH outer sheath

3×50 mm²

Three phase cores, each 50 mm² copper

+2×25 mm²

Two additional cores, each 25 mm² copper (typically 1×N + 1×PE)


Construction: Copper conductors with mica tape fire barrier, XLPE insulation, LSZH sheath, 5-core unarmoured power cable with combined low-smoke zero-halogen + flame retardant B + fire-resistant properties.


WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE Cable 0.6/1kV


WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE Cable 0.6/1kV


WDZBN-YJY 3×50+2×25 mm² — LV LSZH Fire-Resistant Power Cable — Specification & Engineering Data 

1. Overview & Ratings. WDZBN-YJY 3×50+2×25 is a 5-core (3P+N+PE) low-voltage LSZH fire-resistant power cable rated 0.6/1 kV (Um = 1.2 kV), 90 °C continuous. Built per GB/T 12701 / IEC 60502-1, ZB flame retardant per GB/T 19666, N fire-resistant per GB/T 19216. No steel armor — designed for tray and conduit in life-safety circuits. Finished OD ≈ 35 mm, ≈ 2600 kg/km, 200 m drums.


2. Construction Stack (Conductor → Outer).

Layer Build Wall Diameter
Phase conductors (×3) Compacted stranded Cu, Class 2, 3×50 mm² — ≈ 8.6 mm each
N/PE conductors (×2) Compacted stranded Cu, Class 2, 2×25 mm² — ≈ 6.6 mm each
Fire-resistant mica tape Mica tape wrapped per core ≈ 0.14 mm —
XLPE insulation Cross-linked polyethylene 1.3 (phase) / 1.2 (N) 11.2 / 8.8 mm
Filler + binder PP filler + non-woven tape — ≈ 31 mm
LSZH outer sheath Low smoke zero halogen, off-white ≈ 1.8 mm ≈ 35 mm


3. Electrical Characteristics. Phase DC resistance ≤ 0.387 Ω/km; N/PE resistance ≤ 0.741 Ω/km at 20 °C. Routine test 3.5 kV AC / 5 min; insulation resistance ≥ 36.7 MΩ·km. Nominal ampacity ≈ 165 A (air, 25 °C). Circuit integrity maintained ≥ 90 min at 750 °C under fire conditions.

Insulation Data

Property

Value

Material

XLPE (cross-linked polyethylene)

Nominal thickness

1.0 mm (0.6/1 kV class)

Long-term service temp.

90 °C

Short-circuit temp. (≤5 s)

250 °C​ (Cu conductor limit)

Emergency overload temp.

130 °C

Routine test voltage (AC, 5 min)

3.5 kV (for 0.6/1 kV)

Type-test voltage (AC)

4.0 kV (for 0.6/1 kV)

Partial discharge test

≤ 10 pC at 1.73 U₀ (1.04 kV)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

GB/T 12706.1 / IEC 60502-1

Max. system voltage Uₘ

1.2 kV

—

Test voltage AC (5 min)

3.5 kV

Routine test

DC resistance @20 °C (50 mm²)

≤ 0.387 Ω/km

GB/T 3956 Class 2 Cu max

DC resistance @20 °C (25 mm²)

≤ 0.727 Ω/km

GB/T 3956 Class 2 Cu max

AC resistance @90 °C (est., 50 mm²)

≈ 0.493 Ω/km

per phase core

AC resistance @90 °C (est., 25 mm²)

≈ 0.926 Ω/km

N/PE core

Capacitance (approx.)

≈ 0.25 µF/km

core to sheath

Inductive reactance (approx.)

≈ 0.08 Ω/km

at 50 Hz, 5-core unarmoured

Current rating in air (30 °C)

165 A​

3-phase loaded, 3×50 mm² (derated for 5-core)

Current rating buried (20 °C)

145 A​

direct buried

Current rating in conduit (30 °C)

140 A​

3-phase, 5-core

Short-circuit current (1 s, Cu, 250 °C, 50 mm²)

≈ 5.0 kA (5000 A)

per phase core

Short-circuit current (1 s, Cu, 250 °C, 25 mm²)

≈ 2.5 kA (2500 A)

per N/PE core

Frequency

50/60 Hz AC

—

Reference values: 50 mm² Cu at 165 A, 3-phase 400 V → max balanced load ≈ 114 kVA. Voltage drop at 165 A ≈ 81.3 V/km per phase core (≈3.3% per 100 m at 400 V).


4. Thermal & Fire. 90 °C continuous; 250 °C short-circuit (≤ 5 s). ZB flame retardant (Class B) per GB/T 19666. N fire-resistant per GB/T 19216 — circuit integrity ≥ 90 min at 750 °C. LSZH sheath produces low, transparent smoke and zero halogen acid gas in fire.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C (Cu conductor)

Emergency overload temp.

130 °C

Min. installation ambient temp.

−20 °C​ (LSZH sheath, flexible at low temp)

Service ambient range

−20 °C to +90 °C (with LSZH sheath)

Fire survival

GB/T 19216 / IEC 60331​ — circuit integrity ≥ 90 min at 750–800 °C (Category N, fire-resistant)

Fire Performance (WDZBN-YJY — Combined LSZH + Flame Retardant B + Fire Resistant)

Property

Value / Requirement

Flame retardant

IEC 60332-3-23 Category B​ (bunched cable test, flame propagation ≤ 1.5 m)

Halogen content

Zero​ (IEC 60754, LSZH)

Smoke density

Low smoke​ (IEC 61034, light transmittance ≥ 60%)

Corrosivity

Non-corrosive​ (IEC 60754, pH ≥ 4.3)

Toxicity

Low toxicity​ (IEC 60754, HCN emission ≤ 5 mg/g)

Fire survival (circuit integrity)

GB/T 19216 / IEC 60331​ — ≥ 90 min at 750–800 °C (mica tape fire barrier)

Heat release

Low (LSZH material)


Combined Classification Summary:


Feature

Code

Standard

Result

Low-smoke

WD

IEC 61034

✅ Pass (transmittance ≥ 60%)

Zero-halogen

WD

IEC 60754

✅ Pass (halogen-free)

Flame retardant B

ZB

IEC 60332-3-23

✅ Pass (propagation ≤ 1.5 m)

Fire resistant

N

IEC 60331 / GB/T 19216

✅ Pass (≥ 90 min at 750–800 °C)


5. Installation Practice & Handling. Bend ≥ 12 × OD ≈ 420 mm. Tray, conduit, indoor — not for direct burial (no armor). Site DC test 2.4 kV / 15 min before energizing. LSZH sheath is less crush-resistant than PVC. At 2600 kg/km, moderate weight. Store away from UV exposure.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 12 × OD → ≈ 384 mm at Ø32 mm

unarmoured, flexible

Max. pulling tension

5000 N (phase), 2500 N (N/PE)

Cu conductor

Direct burial

Good​ (LSZH sheath, use sand bedding)

not watertight; use water-blocking for submerged

Conduit ID

≥ 1.5 × OD → ≥ 48 mm; use 50 mm or 63 mm

—

Fixing

cable ties, clamps, tray

—

Impact resistance

Moderate​ (unarmoured, LSZH sheath)

protect with conduit in exposed areas

Water resistance

Moisture-resistant (LSZH)

not waterproof

UV resistance

Good (LSZH, outdoor rated)

—

Termination note

Cu conductors + mica tape — strip mica tape at termination point; use standard compression lugs

mica tape must be removed for electrical contact


6. Typical Service Applications. Fire alarm systems, emergency lighting, smoke extraction fans, public building risers, tunnels, high-rises, hospitals — where low smoke, halogen-free, and circuit integrity during fire are critical for human evacuation.


WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE Cable 0.6/1kV


7. Testing & QA Regime. Routine: conductor DC resistance, 3.5 kV AC withstand, insulation resistance, dimensional check. Type: fire resistance test (750 °C, 90 min), flame retardancy Class B, smoke density (IEC 61034), halogen acid gas (IEC 60754), XLPE heating test.


Cable Parameters


WDZBN-YJY 3×50+2×25 mm² — LV LSZH Fire-Resistant Power Cable — Full Parameter Sheet 
5-core (3+2) non-armored · Cu / XLPE + fire-resistant mica / LSZH sheath · 0.6/1 kV · B-class flame retardant · low smoke zero halogen · ≈ 35 mm
Section Parameter Value Unit Remarks / Standard
01 · Identification

Cable type WDZBN-YJY — LSZH fire-resistant XLPE power cable — Non-armored

Rated voltage (U0/U) 0.6/1 kV LV distribution

Number of cores 3 × 50 + 2 × 25 — 3P + N + PE

Conductor material Annealed copper, compacted stranded — Class 2

Insulation material XLPE + fire-resistant mica tape — N = fire resistant

Sheath material LSZH (low smoke zero halogen) — Halogen-free

Flame retardant ZB (Class B) — GB/T 19666

Fire resistance N (fire-resistant) — Circuit integrity

Standard GB/T 12701 / IEC 60502-1 — LV power
02 · Conductor (Cu)

Conductor type Compacted stranded annealed copper — Class 2

Phase conductor area 3 × 50 mm² L1/L2/L3

Neutral/earth area 2 × 25 mm² N + PE

Phase stranding ≈ 19 × 1.78 mm — 50 mm²

N/PE stranding ≈ 7 × 2.21 mm — 25 mm²

DC resistance (phase) @ 20 °C ≤ 0.387 Ω/km Cu 50 mm²

DC resistance (N/PE) @ 20 °C ≤ 0.741 Ω/km Cu 25 mm²

Conductor weight per km ≈ 1050 kg/km 5-core Cu
03 · Insulation

Fire-resistant layer Mica tape wrapped ≈ 0.14 mm

Insulation type XLPE (cross-linked polyethylene) — Thermoset

Phase insulation thickness ≈ 1.3 mm 50 mm²

N/PE insulation thickness ≈ 1.2 mm 25 mm²

Phase core OD ≈ 11.2 mm Insulated

N/PE core OD ≈ 8.8 mm Insulated
04 · Sheath

Sheath type LSZH (low smoke zero halogen) — Halogen-free

Sheath thickness ≈ 1.8 mm LV

Finished outer diameter ≈ 35 mm Overall

Sheath color Off-white / orange — LSZH standard

Halogen content Zero (halogen-free) — WD = low smoke
05 · Electrical

Rated voltage (U0/U) 0.6/1 kV LV

Max voltage 1.2 kV Um

DC resistance (phase) @ 20 °C ≤ 0.387 Ω/km Cu 50

Test voltage (AC) 3.5 kV / 5 min — Routine

Insulation resistance ≥ 36.7 MΩ·km XLPE

Nominal current (ampacity) ≈ 165 A Air, 25 °C

Circuit integrity (fire) ≥ 90 min @ 750 °C — N-rated
06 · Thermal & Fire

Max conductor temp. 90 °C XLPE continuous

Short-circuit temp. 250 °C Max 5 s

Fire resistance ≥ 90 min @ 750 °C — GB/T 19216

Flame retardancy ZB (Class B) — GB/T 19666

Smoke density Low (LSZH) — Transparent smoke

Halogen acid gas Zero — Halogen-free
07 · Mechanical

Min bending radius (fixed) ≥ 12 × OD ≈ 420 mm Non-armored

Crush resistance Moderate — Non-armored

Weight per km ≈ 2600 kg/km 5-core LSZH
08 · Installation

Laying methods Tray, conduit, indoor, cable basket — Non-armored

Bending radius ≥ 12 × OD ≈ 420 mm — Non-armored

Site test 4U0 = 2.4 kV DC / 15 min — Before energizing

Connectors Cu lugs for 50 / 25 mm² — Compression
09 · Packing

Standard supply length 200 m / drum m Non-armored

Reel / packing type Wooden drum — Export standard

Surface marking WDZBN-YJY, 3×50+2×25, 0.6/1kV, GB/T 12701 — Continuous printing

Storage conditions Dry, indoor — Protect from UV
10 · Applications

Typical use Fire systems, emergency lighting, public buildings, high-rise risers — Life safety

Application level Low voltage — 0.6/1 kV

Installation type Indoor / tray / conduit — Non-armored


Cable Test Parameters


Test Parameters — WDZBN-YJY 3×50+2×25 mm² LSZH Fire-Resistant Cable
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance GB/T 3956, 20 °C ≤ 0.387 Ω/km (50); ≤ 0.741 Ω/km (25) Routine
2 Voltage test (AC) 3.5 kV AC, 5 min No breakdown Routine
3 Insulation resistance 5000 V DC ≥ 36.7 MΩ·km Routine
4 Fire resistance test GB/T 19216, 750 °C, 90 min Circuit integrity maintained Type
5 Flame retardancy GB/T 19666 Class B ZB certified Type
6 Smoke density test IEC 61034 Low smoke, transparent Type
7 Halogen acid gas IEC 60754 Zero halogen content Type
8 Dimensional check Caliper OD ≈ 35 mm Routine
9 XLPE heating test 90 °C conductor, 4 h No damage Type
10 Bending test 12× OD, cycles No damage Type
11 Mica tape check Visual / thickness Fire layer intact Routine
12 Printing legibility Visual Marking readable Routine


Cable Cross Section Structure


WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE Cable 0.6/1kV


WDZBN-YJY 3×50+2×25 mm² — Cross-Section Construction Diagram (Schematic)
5-core (3+2) non-armored: Cu → fire-resistant mica → XLPE insulation → filler → LSZH sheath · 0.6/1 kV · ≈ 35 mm
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Phase conductors (×3) Compacted stranded Cu, Class 2, 3×50 mm² — ≈ 8.6 each R ≤ 0.387 Ω/km
2 N/PE conductors (×2) Compacted stranded Cu, Class 2, 2×25 mm² — ≈ 6.6 each R ≤ 0.741 Ω/km
3 Fire-resistant mica tape Mica tape wrapped over each core ≈ 0.14 — N = fire resistant
4 XLPE insulation Cross-linked polyethylene 1.3 (phase) / 1.2 (N) 11.2 / 8.8 90 °C rated
5 Filler + binder tape PP filler + non-woven tape — ≈ 31 Round out the core
6 LSZH outer sheath Low smoke zero halogen, off-white ≈ 1.8 ≈ 35 Halogen-free
Key Dimensions & Properties (expanded)
Finished cable diameter ≈ 35 mm Overall

Approx. cable mass ≈ 2600 kg/km 5-core LSZH

Nominal voltage rating 0.6/1 kV LV distribution

Max conductor temp. 90 °C XLPE continuous

Short-circuit temp. 250 °C Max 5 s

Min bending radius (fixed) ≥ 12 × OD ≈ 420 mm Non-armored

DC resistance (phase) @ 20 °C ≤ 0.387 Ω/km Cu 50 mm²

DC resistance (N/PE) @ 20 °C ≤ 0.741 Ω/km Cu 25 mm²

Test voltage (AC) 3.5 kV / 5 min — Routine

Nominal current (ampacity) ≈ 165 A Air, 25 °C

Fire resistance ≥ 90 min @ 750 °C — N-rated

Flame retardancy ZB (Class B) — GB/T 19666

Halogen content Zero — LSZH

Standard GB/T 12701 / IEC 60502-1 — LV power

Schematic — not to exact scale. Finished OD ≈ 35 mm and weight ≈ 2600 kg/km from cross-referenced industry samples. WDZBN-YJY is a 5-core (3P+N+PE) LSZH fire-resistant non-armored LV power cable for life-safety circuits. Values marked (est.) require confirmation against the factory test certificate.


Construction Description


Construction Description — WDZBN-YJY 3×50+2×25 mm² LSZH fire-resistant cable
Layer-by-layer LSZH fire-resistant: Cu / mica fire layer / XLPE insulation / filler / LSZH sheath · 0.6/1 kV · 90 °C · ≈ 35 mm
1. Product Identity & Ratings
WDZBN-YJY 3×50+2×25 is a 5-core (3P+N+PE) low-voltage LSZH fire-resistant power cable rated 0.6/1 kV, 90 °C. Built per GB/T 12701, ZB flame retardant and N fire-resistant per GB/T 19666/19216. Designed for life-safety circuits where low smoke and halogen-free performance is critical. Finished OD ≈ 35 mm, mass ≈ 2600 kg/km, 200 m drums.
2. Five Copper Conductors (3+2)
Three 50 mm² phase conductors (compact stranded Cu, ~19×1.78 mm) plus two 25 mm² conductors for N and PE (~7×2.21 mm). Phase resistance ≤ 0.387 Ω/km; N/PE resistance ≤ 0.741 Ω/km at 20 °C.
3. Fire-Resistant Mica + XLPE Insulation
Each core is first wrapped with mica tape (~0.14 mm) for circuit integrity during fire, then extruded with XLPE (1.3 mm phase / 1.2 mm N). The mica layer maintains circuit integrity for ≥ 90 min at 750 °C.
4. LSZH Outer Sheath
The outer sheath is made of low-smoke zero-halogen (LSZH) compound, ~1.8 mm thick. Unlike PVC, LSZH emits no halogen acid gas and produces low, transparent smoke in a fire — critical for human evacuation in tunnels, high-rises, and public buildings.
5. Site Handling & Operational Notes
• Bend radius 12×OD (≈ 420 mm).  • Tray, conduit, indoor.  • Site DC test 2.4 kV / 15 min.  • LSZH sheath is less crush-resistant than PVC — avoid direct burial.  • At 2600 kg/km, moderate.  • Store away from UV.


8. Standards & Conformity. GB/T 12701 (LV power cables); IEC 60502-1; GB/T 3956 (conductors); GB/T 19666 (ZB flame retardant); GB/T 19216 (fire-resistant circuit integrity); IEC 61034 (smoke density); IEC 60754 (halogen gas).


9. Packaging, Storage & Logistics. 200 m per wooden drum. Continuous marking: WDZBN-YJY, 3×50+2×25, 0.6/1kV, GB/T 12701. Store indoors, dry, away from direct sunlight.


WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE Cable 0.6/1kV


10. Procurement Specification. State "WDZBN-YJY 0.6/1 kV 3×50+2×25" + drum length. Confirm fire-resistance and LSZH certificates against factory test records.


11. Cable Industry FAQ.

  • Q1: What does "WDZBN" mean? W = low smoke (低烟); D = halogen-free (无卤); Z = flame retardant (阻燃); B = Class B (B 级); N = fire resistant (耐火). It combines LSZH, B-class flame retardancy, and fire-resistant circuit integrity.
  • Q2: What is the difference between WDZBN-YJY and ZC-YJV22? ZC-YJV22 has a PVC sheath and steel tape armor for direct burial. WDZBN-YJY has an LSZH sheath and no armor for tray/conduit in life-safety areas. WDZBN-YJY emits no toxic halogen gas in fire; ZC-YJV22's PVC does.
  • Q3: Why is there no armor? WDZBN-YJY is designed for indoor tray and conduit installation where mechanical protection is provided by the cable tray itself. Armor adds weight and cost and is unnecessary in these protected environments.
  • Q4: What is the mica tape layer for? The mica tape wrapped under the XLPE insulation maintains circuit integrity during fire. Even if the XLPE burns away, the mica layer keeps the circuit live for ≥ 90 minutes at 750 °C — critical for emergency lighting and fire pumps.
  • Q5: What is LSZH? Low Smoke Zero Halogen. In a fire, LSZH emits much less smoke than PVC, and the smoke is transparent (improving visibility for evacuation). It contains no halogen, so no toxic acid gas is released.
  • Q6: Can this be directly buried? No — without steel armor, the LSZH sheath is vulnerable to crush and rodent damage. Use ZC-YJV22 (armored) for direct burial.
  • Q7: What is the ampacity? Approximately 165 A in free air at 25 °C. The smaller 50 mm² conductors give lower ampacity than the 185 mm² ZC-YJV22 (370 A).
  • Q8: What is the bending radius? 12×OD ≈ 420 mm — more flexible than armored cable but still requires generous bends.
  • Q9: Where must this cable be used? Building codes often require LSZH fire-resistant cables in: tunnels, underground stations, high-rise evacuation routes, hospitals, schools, and public assembly buildings.
  • Q10: How long does it maintain circuit integrity in a fire? ≥ 90 minutes at 750 °C per GB/T 19216. This allows enough time for evacuation and emergency services.
  • Q11: Can WDZBN-YJY replace regular YJV? Yes, but it costs more. Use it in life-safety circuits and enclosed spaces where smoke toxicity is a concern. For ordinary power distribution, standard YJV is sufficient.