0.6/1kV ZC-YJV 5x16mm² Copper XLPE PVC Flame-Retardant Power Cable for Residential Main Distribution
Basic Properties
Trading Properties
Product Summary
Product Details
xlpe 5 core cable
,xlpe copper conductor cable
,black 5 core cable
Product Description
0.6/1kV ZC-YJV 5x16mm² Copper XLPE PVC Flame-Retardant Power Cable for Residential Main Distribution
Technical Datasheet — ZC-YJV 0.6/1 kV 5×16 mm²
1. Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant, Class C (bundled combustion test per GB/T 18380.3 / GB/T 19666) |
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
V |
PVC (polyvinyl chloride) outer sheath (flame-retardant ZC grade) |
|
0.6/1 kV |
Rated voltage U₀/U = 600/1000 V; max. system voltage Uₘ = 1.2 kV |
|
5×16 mm² |
Five cores, nominal copper conductor area 16 mm² per core |
|
Construction |
Unarmoured, non-screened, round multi-core |
2. Applicable Standards
- GB/T 12706.1-2020 (equiv. IEC 60502-1) — Extruded insulation power cables ≤ 1 kV
- GB/T 3956 / IEC 60228 — Conductors (Class 2)
- GB/T 19666-2019 — Flame retardant & fire resistant cables (ZC = Class C)
- GB/T 18380.3 — Bunched flame propagation test, Class C (char ≤ 2.5 m above burner)
- GB/T 16895.15 / IEC 60364-5-52 — Current-carrying capacity reference for installation
3. Product Components / Construction (inside → outside)
- Conductor (×5) — Bare annealed copper, Class 2 stranded circular, 7×∅1.70 mm (typical); conductor diameter ≈ 5.0–5.1 mm
- Conductor screen — Not required for 0.6/1 kV; omitted
- Insulation (×5) — XLPE compound, extruded (colours: brown/black/grey/blue + green-yellow for 3L+N+PE)
- Insulation thickness (nominal) — 0.7 mm (GB/T 12706.1, 10/16 mm² class)
- Filler — Flame-retardant non-hygroscopic PP/PE filler (ZC grade) to form round assembly
- Binder — Flame-retardant glass-fibre / FR tape (ZC grade) over laid-up cores
- Outer sheath — Flame-retardant PVC compound (ZC grade)
- Sheath thickness (nominal) — 1.8 mm (multi-core rule, ≥1.8 mm)
- Sheath colour — Black (standard); other colours available
- Armour — None
- Metallic screen — None

4. Dimensional Data
|
Item |
Typical value |
Remarks |
|---|---|---|
|
Conductor nominal area (per core) |
16 mm² |
— |
|
Number of cores |
5 |
3L + N + PE typical |
|
Conductor construction |
Class 2, 7×∅1.70 mm |
min. 7 wires per GB/T 3956 |
|
Conductor diameter (approx.) |
5.0 – 5.1 mm |
|
|
Insulation nominal thickness |
0.7 mm |
|
|
Diameter over one insulated core (approx.) |
6.4 mm |
5.0 + 2×0.7 |
|
Sheath nominal thickness |
1.8 mm |
|
|
Overall cable diameter |
21.3 – 22.4 mm |
21.3, 21.7 (Made-in-China/YJV std.), 21.8 (gbt12706), 22.4 , 22.6 ; use 22.0 mm for design |
|
Approx. weight |
965 – 1053 kg/km |
965 (Made-in-China), 1000 (gbt12706 YJV), 1004 1011 , 1053 ; use ≈ 1010 kg/km |
|
Cable shape |
Round |
— |


5. Insulation Data
- Material: XLPE (cross-linked polyethylene)
- Nominal thickness: 0.7 mm (GB/T 12706.1, 16 mm² at 0.6/1 kV)
- Long-term service temperature: 90 °C
- Short-circuit temperature (≤5 s): 250 °C
- Emergency overload: 105–130 °C (limited duration, general XLPE practice)
- Routine test: 3.5 kV AC / 5 min; type test 4.0 kV
- Volume resistivity @90 °C: ≥ 10¹² Ω·cm (typical XLPE)
- Insulation resistance: ≥ 100 MΩ·km @20 °C (500 V megger); constant R₀·L ≈ 3.67 MΩ·km @90 °C
6. Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
Uₘ = 1.2 kV |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
Type-test voltage |
4.0 kV |
IEC 60502 practice |
|
DC resistance @20 °C (Class 2 Cu, per core) |
≤ 1.15 Ω/km |
GB/T 3956 / IEC 60228 max |
|
AC resistance @90 °C (est.) |
≈ 1.50 Ω/km |
copper temp. coefficient |
|
Recommended current rating — in air (30 °C, single circuit, 5-core) |
≈ 84–86 A |
84, 86 , 95 ; design ≈ 85 A |
|
In air — bundled / tray (per ) |
107 A |
higher, not conservative |
|
Direct buried / in soil (20 °C, soil thermal res. 1.0 K·m/W, depth 0.7 m) |
≈ 94–100 A |
94 , 100, 110 ; design ≈ 95 A |
|
Short-circuit current capacity (1 s adiabatic, Cu, 250 °C, per core) |
≈ 1.84 kA |
reference |
|
Frequency |
50/60 Hz AC (DC usable) |
— |


7. Temperature Characteristics
- Max. conductor operating temp. (continuous): 90 °C
- Max. short-circuit temp. (≤5 s): 250 °C
- Emergency overload temp.: 105 °C (limited duration)
- Min. ambient temp. during installation: 0 °C (pre-heat below 0 °C)
- Service ambient temperature range: −20 °C to +90 °C (sheath/environment)
- Flame retardant class: Category C per GB/T 19666 (bundled, self-extinguishing, char ≤ 2.5 m)

8. Mechanical & Installation Parameters
- Minimum bending radius (unarmoured multi-core): ≥ 15 × overall diameter → ≈ 330 mm at Ø22 mm
- Maximum pulling tension (copper conductor only): 50 N/mm² × 16 mm² × 5 = 4000 N total (distributed to all 5 cores)
- PVC sheath pulling limit: significantly lower — avoid direct sheath grip; use conductor pulling sock
- Direct burial: Allowed in non-aggressive soil; sand bed + warning tape, depth ≥ 0.7 m, conduit under roads
- Conduit fill: Conduit ID ≥ 1.5 × cable OD → ≥ 33 mm (use 40 mm conduit or larger)
- Cable tray / duct: 5-core is stiff; observe 15D bend radius to avoid core deformation
- Elevation difference: No limitation for XLPE insulated cable
9. Material Specification Summary
- Conductor: Cu ≥ 99.9 % annealed, Class 2, 7×1.70 mm, IEC 60228 / GB/T 3956
- Insulation: XLPE, 0.7 mm nom., rated 90 °C (coloured per core function)
- Filler: Flame-retardant PP/PE (ZC grade)
- Binder: Flame-retardant glass fibre / FR tape
- Outer sheath: Flame-retardant PVC (ZC), 1.8 mm nom.
- No armour, no metallic screen



10. Scope of Application / Usage Range
ZC-YJV 0.6/1 kV 5×16 mm² is intended for fixed installation in low-voltage power distribution & transmission systems up to 1.2 kV where flame-retardant Class C is required. As a five-core cable (3L+N+PE), it is the standard choice for three-phase LV supplies with separate neutral and protective earth.
Typical applicable locations:
- Three-phase distribution feeders (L1/L2/L3 + N + PE) for equipment, motors, distribution boards, and final sub-circuits in TN-S / TN-C-S systems
- Indoor/outdoor distribution rooms, floor distribution cabinets, and risers in high-rise buildings, hotels, shopping malls, hospitals, schools, stations and metros (where ZC flame-retardant grade is mandated by fire code)
- Cable trays, cable ducts, cable trenches & shafts in commercial / residential / public buildings
- Industrial plants, warehouses, small-to-medium machinery and HVAC feeders, elevator power supplies
- Direct buried routes in non-aggressive soil with low mechanical impact
- Renewable / PV inverter AC output and EV charger three-phase branch circuits (polarity/earthing design required)