0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

Basic Properties

country of origin
China
brand name
TONGDU
certificate
CE/ISO/CCC
product model
3x16mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
5000 Meters Per Month

Product Summary

0.6/1kV ZC-YJV 3x16mm² Stranded Copper Conductor XLPE Insulation PVC Outer Sheath Low Voltage Power Cable Technical Datasheet — ZC-YJV 0.6/1 kV 1×16 mm² 1. Cable Designation & Meaning Code Meaning ZC​ Flame retardant, Class C (bundled combustion test) YJ​ XLPE (cross-linked polyethylene) insulation ...

Product Details

Highlight:

1kV 3 Cores Cable

,

3 Cores Cable 3x16mm2

,

stranded copper cable XLPE Insulation

Conductor:
Bare Annealed Copper, Class 2 Stranded​ (7×∅1.70 Mm Typical); Compacted Circular For Single Core
Insulation:
XLPE Compound, Extruded (black / Red / Blue Etc. On Request)
Insulation thickness:
0.7 Mm​ (GB/T 12706.1, 10/16 Mm² Class)
Filler / binder:
Generally None For Single-core; Thin Non-hygroscopic Binder Tape Optional
Outer sheath:
Flame-retardant PVC​ Compound (ZC Grade)
Sheath thickness:
1.4 Mm​
Conductor construction:
Class 2, 7×∅1.70 Mm​ (typical)
Conductor nominal area:
16 Mm²
Conductor diameter (approx.):
5.0 Mm
Diameter over insulation (approx.):
6.4 Mm
Overall cable diameter:
8.7 – 9.9 Mm
Approx. weight:
201 – 221 Kg/km
Long-term service temperature rating:
90 °C
Short-circuit temperature rating (≤5 s):
250 °C​
Volume resistivity @90 °C:
10¹² Ω·cm (typical XLPE)

Product Description

0.6/1kV ZC-YJV 3x16mm² Stranded Copper Conductor XLPE Insulation PVC Outer Sheath Low Voltage Power Cable


Technical Datasheet — ZC-YJV 0.6/1 kV 1×16 mm²

1. Cable Designation & Meaning

Code

Meaning

ZC​

Flame retardant, Class C (bundled combustion test)

YJ​

XLPE (cross-linked polyethylene) insulation

V​

PVC (polyvinyl chloride) outer sheath

0.6/1 kV​

Rated voltage U₀/U = 600/1000 V; max. system voltage Uₘ = 1.2 kV

1×16 mm²​

Single core, nominal copper conductor area 16 mm²

Construction​

Unarmoured, non-screened, round cable


Construction: Three copper conductors, XLPE insulation, PVC outer sheath. No metallic screen/armour as standard (can be added on request).

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

ZC-YJV 3×16 mm² — LV Flame-Retardant 3-Core Power Cable — Specification 

1. Overview & Ratings. ZC-YJV 3×16 is a three-core (L1/L2/L3) LV power cable rated 0.6/1 kV (Um 1.2), 90 °C working, ZC class C flame-retardant PVC sheath. Three matched compacted 16 mm² copper cores laid triangularly, dry-cured XLPE, unarmored. OD ≈ 14.5 mm, ≈ 620 kg/km (est.), ≈ 80 A per core free air at 30 °C (est.). Scope: 380/400 V three-phase motor and pump feeds, small distribution — not 950°C fire duty.


2. Construction Stack (Inner → Outer, expanded).


Layer / Feature Build Function
Conductor L1/L2/L3 3×16 compacted Cu, Class 2, ≈7 strands Phases, R ≤1.15 Ω/km
Strand compaction Concentric layers rolled compact per core Round bundle, clean lug entry
XLPE insulation (L1/L2/L3) Dry-cured PE, ≈1.2 mm per core 90°C dielectric
Core identification L1/L2/L3 color code Preserves phase sequence
Triangular core laying Three cores in a compact triangle Stable ≈12.0 mm sub-bundle
PVC ZC sheath Class C, ≈1.3 mm overall Binds triangle, self-extinguishes
Jacket print Continuous type/size/voltage/length On-site readable spec


3. Electrical Characteristics. Per-core R ≤ 1.15 Ω/km @20 °C. Test 3.5 kV AC / 5 min; ≈ 80 A per core (est., air 30 °C); short-circuit ≈ 2.0 kA / 1 s (est.); 50/60 Hz; unscreened; low-loss XLPE; high stable insulation resistance.

Insulation & Sheath Data

Property

Value

Insulation material

XLPE (cross-linked polyethylene)

Outer sheath material

PVC (ST₂)

Long-term service temp.

90 °C (continuous)

Max. conductor temp. (normal)

90 °C

Short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Test voltage AC (5 min)

3.5 kV

Dielectric strength

≥ 20 kV/mm

Volume resistivity @20 °C

≥ 1×10¹⁴ Ω·cm

Shield

None as standard (can be added)

Electrical Parameters

Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

GB/T 12706.1 / IEC 60502-1

Max. system voltage

1.2 kV AC

—

Test voltage AC (5 min)

3.5 kV

Routine test

DC resistance @20 °C

≤ 1.15 Ω/km per core

GB/T 3956 Class 2 Cu max

AC resistance @90 °C (est.)

≈ 1.47 Ω/km per core

—

Current rating in air (30 °C)

3-core: 80 A​

three-core, touching, in free air

Current rating in tray (30 °C)

3-core: 90 A​

three-core, spaced 2×OD

Current rating buried in ground (20 °C, thermal resistivity 1.2 K·m/W)

3-core: 85 A​

direct buried

Current rating in conduit (30 °C)

3-core: 70 A​

—

Short-circuit current (1 s, Cu, 250 °C)

≈ 1.8 kA (1,800 A) per core

—

Capacitance (core-to-sheath, approx.)

≈ 0.14 µF/km

XLPE

Inductive reactance (approx.)

≈ 0.08 Ω/km

at 50 Hz

Frequency

50/60 Hz AC

—


Reference values: 3×16 at 80 A three-phase, 400 V → max load ≈ 48 kW​ (cos φ = 0.8). Suitable for three-phase distribution, small motors, and industrial equipment.


4. Thermal & Flame. 90 °C continuous, 250 °C short-time; ZC class C self-extinguishing — flame retardancy, not 950°C integrity; withstands repeated 0~90°C cycles; indoor; UV-grade jacket optional.

Temperature Characteristics

Property

Value

Max. conductor operating temp.

90 °C (continuous)

Max. short-circuit temp. (≤5 s)

250 °C

Emergency overload temp.

130 °C (≤1 h)

Min. installation ambient temp.

0 °C (below 0 °C requires preheating)

Service ambient range

−20 °C to +90 °C

Flexing temp. range

0 °C to +90 °C

Fire Performance (ZC-YJV — Flame Retardant C)

Property

Value / Requirement

Flame retardant

GB/T 18380.12 / IEC 60332-1-2​ (single cable, self-extinguishing)

Flame retardant class

Class C​ (ZC) per GB/T 19666

Halogen content

Contains halogen (PVC sheath)

Smoke density

Not low-smoke (PVC)

Corrosivity

Corrosive (PVC)

Toxicity

Toxic fumes when burned (PVC)

EMI shielding

None (no metallic screen/armour)


5. Installation Practice & Handling. 16 mm² Cu lugs, medium glands, crimp/torque per table; bend ≥ 15×OD ≈ 218 mm; derate bundled/tray runs; keep the triangular bundle round; continuity, phase sequence + insulation after pulling.

Mechanical & Installation Parameters

Parameter

Value

Remarks

Minimum bending radius

≥ 15 × OD → ≈ 218 mm at Ø14.5 mm

three-core unarmoured

Max. pulling tension

240 N per core (16 mm² × 15 N/mm²)

Cu conductor limit

Direct burial

Suitable (with sand bedding)

—

Surface mounting

Excellent (cable tray, ladder, cleats)

—

Conduit ID

≥ 25 mm

—

Fixing

cable ties, cleats

—

Impact resistance

Moderate

—

Water resistance

Good (PVC sheath)

—

UV resistance

Fair (PVC degrades outdoors, use UV-resistant PVC or conduit)

—

Flex life

Good (Class 2 stranded)

fixed installation

Termination note

Standard compression lugs or mechanical connectors

—


6. Typical Service Applications. 380/400 V three-phase motor and pump feeds, small machine power leads, compressor and fan supplies, small 3-phase distribution to equipment panels in light industry.


0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath


7. Testing & QA Regime (16 items). Routine: DC resistance L1/L2/L3, 3.5 kV withstand, insulation resistance, continuity, sheath/insulation thickness, dimensional check, strand construction, eccentricity, appearance, print legibility, mass. Type: ZC flame test, short-circuit rating, sheath mechanical, 0~90°C cycle.


Cable Parameters


ZC-YJV 3×16 mm² — LV Flame-Retardant 3-Core Power Cable — Full Parameter Sheet 
3×Cu / XLPE / PVC · ZC class C · 0.6/1 kV · ≈14.5 mm · three-core (L1/L2/L3) for 380/400V motor feeds, pump power and small 3-phase distribution
Parameter Value Unit Remarks / Standard
01 · Identification
Cable type ZC-YJV — Cu/XLPE/PVC, flame-retardant class C — ZC-YJV denotes a copper-conductor cable with cross-linked polyethylene insulation and a PVC outer sheath; the leading ZC marks a Chinese flame-retardant class C compound that self-extinguishes after the ignition source is removed.
Rated voltage (U0/U) 0.6/1 kV 0.6 kV phase-to-earth (U0) and 1 kV phase-to-phase (U) rating defines this as a general low-voltage power cable suited to 380/400 V three-phase distribution.
Maximum operating voltage (Um) 1.2 kV The 1.2 kV maximum system voltage is the continuous upper phase-to-earth limit the XLPE insulation may withstand in normal service.
Core configuration 3×16 (L1 / L2 / L3) — Three equal 16 mm² compacted copper cores laid triangularly for balanced three-phase 380/400 V motor, pump and small distribution feeds.
Conductor material Compacted stranded annealed copper — Soft annealed copper strands are layer-compacted into a round bundle to lower skin effect, reduce diameter and give a clean entry into a 16 mm² lug.
Insulation XLPE cross-linked polyethylene — Chemically cross-linked polyethylene bonds into a heat-resistant dielectric that keeps its properties at the 90 °C operating temperature.
Sheath PVC, flame-retardant class C (ZC) — An overall PVC jacket binds the triangular core bundle and carries the class C flame-retardant formulation; deep indigo navy finish.
Flame retardancy ZC class C (self-extinguishing, not fire-rated) — On removal of a flame the cable stops propagating fire; this is flame-retardancy, not 950 °C/180 min circuit-integrity fire resistance.
Suitable for Fixed indoor tray, conduit, trunking, 3-phase — Designed for fixed three-phase wiring: motor and pump leads, small 3-phase distribution to equipment.
Application 380V 3-phase motor / pump feed — Typically runs three phases from a distribution board to a three-phase motor, pump or small load.
Application note Not for 950°C circuit-integrity fire duty — Do not substitute this ZC cable for a mineral-insulated or fire-resistant circuit; it cannot maintain live integrity under sustained fire.
02 · Conductors
Power core count / area 3 × 16 mm² Three identical 16 mm² conductors carry the three phases of a balanced three-phase 400 V load.
Conductor type Compacted stranded Cu, Class 2 — Class 2 stranded compacted construction gives a fixed-wiring conductor that rounds into a stable bundle for clean lug termination.
DC resistance (16) @ 20°C ≤ 1.15 Ω/km Maximum permitted DC resistance of a 16 mm² copper conductor at 20 °C; watch voltage drop on longer motor leads.
Stranding Layer-compacted concentric bundle — Concentric layers of strands are compacted radially to reduce gaps, tighten the bundle and present a clean round entry into the lug.
Strands (nom., est.) ≈ 7 compacted — Approximate number of compacted strands in a 16 mm² Class 2 bundle; exact count follows the conductor standard and factory drawing.
Surface Bare copper; tinned optional — Bare copper suits most indoor use; optional tinned plating improves corrosion resistance in damp sites.
Core identification L1 / L2 / L3 by color — The three cores are distinguished by insulation color so phase sequence matches motor rotation at both ends.
Nominal area tolerance Within conductor class 2 band — Actual cross-sectional area and strand geometry stay inside the class 2 tolerance band rather than a solid bare count.
03 · Insulation
Insulation material XLPE (cross-linked polyethylene) — Cross-linked PE delivers a higher continuous temperature rating and lower dielectric loss than ordinary PVC insulation for the same size.
Insulation thickness (nom.) ≈ 1.2 mm Nominal radial insulation wall on each core; gauged to withstand the 3.5 kV routine test and the 90 °C heat load.
Working conductor temp. 90 °C Maximum continuous conductor temperature under rated current without shortening insulation life.
Short-circuit temp. 250 °C Peak conductor temperature the insulation may survive for a short fault duration (seconds) before damage occurs.
Insulation resistance High and stable MΩ·km XLPE keeps a high, stable insulation resistance over life, supporting reliable earth-fault detection on 3-phase circuits.
Color L1/L2/L3 color on request — Insulation colors are matched to local 3-phase convention (e.g. yellow/green/red) or supplied natural with printed marking.
Cure type Chemical / dry-cured XLPE — A controlled cross-linking cure locks the polymer network so the insulation stays elastic rather than melting under heat.
04 · Sheath & Flame Retardancy
Sheath material PVC, flame-retardant ZC — The class C PVC outer jacket blends a flame-suppressing formulation while keeping a smooth, printable surface.
Sheath thickness (nom.) ≈ 1.3 mm Nominal overall jacket wall sized to shield the three triangular cores from abrasion, dust and occasional moisture.
Finished outer diameter ≈ 14.5 mm Overall three-core finished diameter used to size trunking fill, conduit and gland entry.
Flame behavior Self-extinguishing, class C — After the test flame is removed the sample extinguishes without propagating along the cable; it is not 950°C fire-rated.
Sheath color Deep indigo navy (black/gray on request) — Standard deep indigo navy; black or dark gray jackets are supplied for industrial aesthetics on request.
Surface finish Smooth, continuous print — A smooth jacket carries a continuous printed line of type, size, voltage, ZC class and meter length along its length.
05 · Electrical
Rated voltage (U0/U) 0.6/1 kV Low-voltage rating matching 380/400 V three-phase distribution systems.
Max voltage (Um) 1.2 kV Continuous upper system voltage for phase-to-earth insulation stress.
Nominal current (per 16 core, est.) ≈ 80 A Approximate ampacity of a single 16 mm² core in free air at 30 °C; reduce for bundling, duct fill and high ambient.
Test voltage (AC) 3.5 kV / 5 min — Routine dielectric withstand applied between each conductor and sheath for five minutes without breakdown.
Insulation resistance High, XLPE MΩ·km Measured after conditioning; confirms no void, crack or contamination in the cured insulation.
Short-circuit current (16, 1s, est.) ≈ 2.0 kA Approximate 1-second copper short-time withstand; the motor lead trips under a moderate fault.
Frequency 50 / 60 Hz Compatible with both 50 Hz and 60 Hz three-phase power systems.
Dielectric XLPE, low loss — Low dielectric loss keeps heating down under continuous motor load.
06 · Thermal & Environment
Normal conductor temp. 90 °C Sustained operating temperature the XLPE insulation is rated for under full load.
Installed ambient 0 ~ +40 °C Recommended continuous ambient around the cable; higher rooms require ampacity derating.
Min install temp. 0 °C Avoid cold bending below 0 °C where the PVC jacket and insulation may stiffen and crack.
Burning Self-extinguishing, ZC class C — Class C vertical flame test behavior: flame stops once the external burner is removed.
Outdoor / UV Indoor preferred; UV-grade jacket optional — Standard PVC degrades under prolonged direct sun; specify UV-stabilized jacket for exposed outdoor runs.
Oil / chemicals Resistant to common oils; check aggressive media — Withstands typical machine and motor oils; verify against specific solvents or acid fumes before use.
Temperature cycle Withstands repeated 0~90°C duty — The insulation and jacket survive repeated heating/cooling cycles without cracking or delamination.
07 · Mechanical & Construction
Min bending radius (fixed) ≥ 15 × OD ≈ 218 mm Fixed-installation minimum bend radius for the three-core cable; tighter bends strain insulation and jacket.
Flexibility Stranded, easy to pull on site — Compacted strands keep the cable flexible enough to route through trunking and conduit.
Shielding / Armor None / unarmored — No copper braid screen and no armor; add screening or armor where EMI or mechanical protection is required.
Cable weight per km (est.) ≈ 620 kg/km Approximate mass per kilometer used for tray loading and drum sizing.
Circularity Triangular core bundle, stable OD — The three cores lay into a compact triangle so the finished OD stays consistent along the length.
Tensile / elongation Jacket meets PVC grade — Sheath tensile strength and elongation satisfy the PVC compound grade for durable handling.
08 · Factory Advantages
Balanced 3-phase bundle L1/L2/L3 built to the same 16 mm² spec — Three equal cores keep phase currents and impedance balanced for motor rotation.
Stable XLPE cure Even cross-linking keeps the 90°C dielectric consistent lot to lot — Controlled cure removes soft spots in insulation that would age faster under motor load.
Dosed ZC compound Flame-retardant PVC self-extinguishes to class C — Dosed flame inhibitors give a safety margin against incidental ignition in plant wiring.
Length-on-demand Cut to exact meter, sealed ends, minimal offcut — Custom cut lengths match the measured motor lead run and reduce waste.
Batch resistance log Per-core DC R recorded against the lot number — Each phase core's resistance is logged against batch ID for procurement traceability.
Continuous print line Type, size, ZC, voltage and length along jacket — Clear continuous marking lets installers read the spec without a certificate on site.
Phase-color option L1/L2/L3 insulation colors matched to convention — Pre-colored phases remove phase-sequence guesswork at motor termination.
Drum pack Supplied on drum for long motor leads — Drum packing suits the longer 3-phase runs typical of motor and pump feeds.
Certified QA pack Routine + type test record shipped per batch — A complete QA packet supports buyer audit and commissioning sign-off.
09 · Installation
Laying Tray, conduit, trunking, 3-phase — Route in fixed supports; keep the triangular bundle round and bending above 15×OD.
Connectors 16 mm² Cu lugs, medium glands — Crimp matched 16 mm² copper lugs on each core; select a gland sized to the 14.5 mm OD.
Bend radius ≥ 15×OD ≈ 218 mm — Maintain the minimum radius around corners to prevent insulation cold-working.
Parallel runs Derate when bundled in conduit/tray — Adjacent heating cores share heat; apply bundle derating before sizing the motor breaker.
Site test Continuity + insulation post-laying — After pulling, verify three-phase continuity, phase sequence and insulation resistance.
Termination Strip, crimp lug, torque per table — Strip insulation without nicking strands, crimp each lug fully, and torque per the lug table.
10 · Packing & Applications
Supply length Custom / drum m Cut to the measured 3-phase run length; drum packing.
Length tolerance Per trade standard for cut lengths — Cut-length tolerance follows the applicable trade standard rather than a fixed meter promise.
Reel type Wooden drum — Drum for long 3-phase motor and pump leads.
Surface marking ZC-YJV, 3×16, 0.6/1kV, ZC, length — Jacket prints type, three-core size, voltage, flame class and cumulative meter length.
Typical use Motor feed, pump power, small 3-phase distribution — Runs three phases to motors, pumps and small 3-phase loads.
Storage Dry indoor, avoid direct UV — Store on a pallet, dry and shaded, to keep the jacket intact.


Cable Test Parameters


Test Parameters — ZC-YJV 3×16 LV Flame-Retardant 3-Core Cable 
No. Test Item Test Condition / Method Requirement Type
1 Conductor DC resistance 20 °C, each core L1/L2/L3 16 ≤1.15 Ω/km Routine
2 Voltage test (AC) 3.5 kV AC, 5 min, core-to-sheath No breakdown Routine
3 Insulation resistance XLPE, 20°C, per core High & stable Routine
4 Continuity Each core L1/L2/L3 Continuous Routine
5 Flame retardancy Class C vertical test Self-extinguish Type
6 Sheath thickness Micrometer, cross-section Nominal ≥1.3 mm Routine
7 Insulation thickness Micrometer, per core Nominal ≥1.2 mm Routine
8 Dimensional check Caliper, overall OD OD ≈ 14.5 mm Routine
9 Conductor construction Visual / strand count Class 2 compacted Routine
10 Short-circuit rating Calculated / type 2.0 kA / 1 s Type
11 Insulation eccentric test Cross-section measure per core Within tolerance Routine
12 Sheath appearance Visual along length Smooth, no flaw Routine
13 Printing legibility Visual Marking readable Routine
14 Mass per unit length Weigh / calculate ≈ 620 kg/km Routine
15 Sheath mechanical Tensile / elongation check Meets PVC grade Type
16 Temperature cycle Repeated 0~90°C duty No cracking Type


Cable Cross Section Structure


0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath


ZC-YJV 3×16 — 3-Core Cross-Section Construction Diagram 
3×Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · ≈14.5 mm · L1/L2/L3 3-phase motor, pump & small distribution feeds
No. Layer / Feature Material / Construction Nominal Thickness (mm) Diameter (mm) Detailed Function / Remarks
1 Conductor L1 — phase 1×16 compacted Cu, Class 2, ≈7 strands — ≈ 5.0 Phase 1 core, DC R ≤1.15 Ω/km @20°C; balanced 3-phase load.
2 Conductor L2 — phase 1×16 compacted Cu, Class 2, ≈7 strands — ≈ 5.0 Phase 2 core, same size/resistance for balanced impedance.
3 Conductor L3 — phase 1×16 compacted Cu, Class 2, ≈7 strands — ≈ 5.0 Phase 3 core, same spec; color-coded for motor rotation.
4 Strand compaction Concentric layers rolled compact per core — — Radial compaction closes strand gaps for a round bundle and clean lug entry.
5 XLPE insulation (L1/L2/L3) Dry-cured cross-linked PE, ≈1.2 mm each ≈ 1.2 ≈ 7.4 90°C dielectric on each phase core, low loss, stable insulation resistance.
6 Core identification L1/L2/L3 color code — — Phases distinguishable at both ends to preserve motor rotation.
7 Triangular core laying Three cores laid in a compact triangle — ≈ 12.0 Triangular lay holds the bundle round and reduces overall OD.
8 PVC ZC sheath Flame-retardant class C, smooth, overall ≈ 1.3 ≈ 14.5 Binds the triangle, shields from abrasion/dust, self-extinguishes to class C.
9 Jacket print Continuous type/size/voltage/length line — — Marking along the jacket: ZC-YJV, 3×16, 0.6/1kV, ZC, cumulative length.
Key Dimensions, Electrical & Mechanical Properties (expanded)
Finished cable diameter ≈ 14.5 mm Three-core overall OD for trunking and gland sizing.
Approx. cable mass (est.) ≈ 620 kg/km Drum-packed 3-phase motor lead.
Nominal voltage rating 0.6/1 kV Matches 380/400 V three-phase systems.
Max voltage (Um) 1.2 kV Phase-to-earth continuous upper limit.
Normal conductor temp. 90 °C Continuous load temperature of XLPE.
Short-circuit temp. 250 °C Short-time fault peak before insulation damage.
DC resistance (16) ≤ 1.15 Ω/km Per phase core @20°C.
Nominal current (est.) ≈ 80 A Per core, free air 30°C; derate bundled.
Short-circuit rating (1s, est.) ≈ 2.0 kA 16 Cu, motor-lead fault duty.
Flame retardancy ZC class C, self-extinguishing — Not 950°C fire-rated.
Min bending radius (fixed) ≥ 15 × OD ≈ 218 mm Fixed 3-core install corner radius.
Frequency 50 / 60 Hz Compatible with both power systems.
Insulation resistance High & stable MΩ·km XLPE; supports earth-fault detection.
Dielectric loss Low — XLPE keeps heating down on motor load.
Temperature cycle 0~90°C repeated — Survives heating/cooling without cracking.
Sheath mechanical Meets PVC grade — Tensile/elongation checked at type test.
Pack choice Drum — Drum for long motor leads.
Core configuration 3×16 (L1/L2/L3) — Balanced three-phase.
Application Motor feed, pump, small 3-phase dist. — 380/400 V 3-phase power.
UV / outdoor UV-grade optional — Indoor preferred; specify stabilized jacket outside.
Schematic — not to exact scale. OD ≈14.5 mm, weight ≈620 kg/km, ≈80 A per core free air at 30°C and ≈2.0 kA/1s are (est.) from cross-referenced industry samples. ZC-YJV 3×16 serves 380/400 V three-phase motor and pump feeds and small 3-phase distribution; ZC class C self-extinguishes but is not 950°C fire-rated. Estimated values require confirmation against the factory test certificate for the specific batch.


Cable Construction Description


Construction Description — ZC-YJV 3×16 LV flame-retardant 3-core cable 
3×Cu core / XLPE insulation / PVC ZC sheath · 0.6/1 kV · ZC class C · 90°C · ≈14.5 mm · L1/L2/L3 3-phase motor, pump & small distribution feeds
1. Product Identity & Ratings
ZC-YJV 3×16 rated 0.6/1 kV (Um 1.2), 90°C working, ZC class C; three L1/L2/L3 cores. OD ≈14.5 mm, ≈620 kg/km (est.), ≈80 A per core free air at 30°C (est.), drum. It is a fixed 3-phase motor-lead cable, not a flexible cord and not a 950°C fire-rated circuit.
2. Copper Conductors (3×16)
Three matched 16 mm² compacted Class 2 Cu cores (L1/L2/L3), ≈7 strands each; DC R ≤1.15 Ω/km @20°C; balanced 3-phase currents; tinned plating optional for damp sites; phase-color insulation supplied on request.
3. Strand Compaction & Triangular Bundle
Concentric strands are rolled compact per core to close gaps and give clean lug entry; the three cores are laid in a controlled triangle to hold a round ≈12.0 mm sub-bundle before sheathing.
4. XLPE Insulation
Dry-cured cross-linked PE ≈1.2 mm on each core, stable 90°C dielectric, low dielectric loss, high and stable insulation resistance; short-circuit peak 250°C; L1/L2/L3 distinguished by phase color.
5. Core Identification
The three phases are identified by insulation color so phase sequence matches at the motor; colors can be supplied to local 3-phase convention instead of natural insulation.
6. PVC ZC Sheath
Flame-retardant PVC ≈1.3 mm overall, self-extinguishing class C; deep indigo navy standard (black/gray on request); smooth printable surface; binds the triangular bundle and shields from abrasion, dust and occasional moisture.
7. Electrical Characteristics
0.6/1 kV, Um 1.2; per-core R ≤1.15 Ω/km; routine 3.5 kV AC/5 min; ≈80 A per core (est., air 30°C); short-circuit ≈2.0 kA/1s (est.); 50/60 Hz; unscreened; low-loss XLPE.
8. Factory Advantages
• Balanced 3-phase bundle.  • Stable XLPE cure lot to lot.  • Dosed ZC self-extinguish.  • Length-on-demand.  • Per-batch resistance log.  • Continuous clear print.  • Phase-color option.  • Drum pack for motor leads.  • Certified QA pack.
9. Site Handling & Installation
• Bend 15×OD (≈218 mm).  • 16 Cu lugs, medium glands, torque per table.  • Derate bundled/tray runs.  • Keep triangle round.  • Continuity, phase sequence + insulation after pulling.  • Indoor; UV grade if exposed.
10. Typical Service Applications
380/400 V three-phase motor and pump feeds, small machine power leads, compressor and fan supplies, small 3-phase distribution to equipment panels in light industry.
11. Testing & QA
16-item regime: routine DC resistance L1/L2/L3, 3.5 kV withstand, insulation resistance, continuity, sheath/insulation thickness, dimensional check, strand construction, eccentricity, appearance, print legibility, mass; type ZC flame, short-circuit, sheath mechanical, 0~90°C cycle.
12. Packaging, Storage & Notes
Cut to measured length on drum; continuous marking; store dry indoor on a pallet, shaded, avoid direct UV. Est. OD/weight/ampacity/short-circuit confirmed against the factory certificate; ZC is flame retardant, not 950°C fire-rated.


8. Factory Advantages.

  • Balanced 3-phase bundle — L1/L2/L3 built to the same 16 mm² spec.
  • Stable XLPE cure — even cross-linking keeps the 90°C dielectric consistent.
  • Dosed ZC compound — self-extinguishes to class C.
  • Length-on-demand — exact meter, sealed ends, minimal offcut.
  • Batch resistance log — per-phase DC R recorded against lot number.
  • Continuous print line — type, size, ZC, voltage and length along jacket.
  • Phase-color option — L1/L2/L3 colors matched to convention.
  • Drum pack — suited to long motor leads.
  • Certified QA pack — routine + type test record per batch.

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath


9. Packaging, Storage & Logistics. Cut to measured length on drum; continuous marking; store dry indoor on a pallet, shaded, avoid direct UV.


0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath


10. Procurement Specification. State "ZC-YJV 3×16", length, class C, phase colors, drum; note flame retardant not fire-rated; request per-batch resistance log and 16-item QA record. Est. values confirmed against the factory certificate.


ZC-YJV 3×16 mm² Power Cable
Frequently Asked Questions (FAQ)
Flame-Retardant Class C · XLPE Insulated · PVC Sheathed · Copper Conductor · 0.6/1 kV

Product Basics

Q1. What does the model “ZC-YJV” mean?
“Z” stands for flame-retardant, “C” denotes Class C flame-retardant performance, “YJ” means XLPE (cross-linked polyethylene) insulation, and “V” means PVC sheath. ZC-YJV is a copper-core, Class C flame-retardant, XLPE-insulated, PVC-sheathed low-voltage power cable.
Q2. What does “3×16 mm²” indicate?
“3” means the cable has three cores (three insulated conductors within a common sheath). “16 mm²” is the nominal cross-sectional area of each copper conductor. This 3-core cable is designed for three-phase power supply circuits, providing three phase conductors (L1, L2, L3). For three-phase systems requiring a neutral conductor, consider 4-core or 5-core variants.
Q3. What is the rated voltage?
The rated voltage U₀/U is 0.6/1 kV (0.6 kV phase-to-earth, 1 kV phase-to-phase), designed for low-voltage three-phase and single-phase power distribution systems.
Q4. What materials are used in construction?
Conductor: plain copper, Class 2 stranded. Insulation: cross-linked polyethylene (XLPE) on each core. Filler: non-hygroscopic material to hold the three cores together. Outer sheath: flame-retardant PVC. Standard ZC-YJV is unarmored. For direct burial, armored variants such as ZC-YJV22 (steel tape armor) are available.

Technical Specifications

Q5. What is the maximum operating temperature?
The maximum continuous conductor temperature is 90 °C. During short-circuit events, the conductor may reach up to 250 °C for no more than 5 seconds. XLPE insulation provides higher temperature resistance and greater ampacity compared with traditional PVC-insulated cables.
Q6. What is the typical current-carrying capacity?
For a 3×16 mm² copper XLPE cable, the ampacity is approximately 55–75 A when installed in free air at 30 °C ambient. Multi-core cables have lower ampacity than single-core cables of the same conductor cross-section due to mutual heating between adjacent cores. Lower ratings apply when buried, installed in conduit, grouped, or at higher ambient temperatures. Refer to GB/T 16895 / IEC 60364 and manufacturer tables for precise values.
Q7. What is the conductor DC resistance?
The maximum DC resistance of a 16 mm² Class 2 copper conductor at 20 °C is approximately 1.15 Φ/km (annealed copper), per GB/T 3956 / IEC 60228. Each of the three cores has the same resistance. Confirm the exact value from the factory test report for each batch.

Installation & Applications

Q8. What is the minimum bending radius?
For multi-core unarmored cables, the minimum bending radius is 15 times the cable outer diameter (15D) during installation. Multi-core cables are generally more flexible than equivalent single-core cables. D = actual outer diameter.
Q9. What are the typical applications?
Common uses include: three-phase power supply circuits for small motors, pumps, and HVAC equipment; three-phase branch distribution in commercial and industrial buildings; connection between three-phase distribution boards and three-phase loads; and industrial plant power distribution where Class C flame-retardant performance is required.
Q10. Which standards and certifications apply?
Manufactured in accordance with GB/T 12706 (equivalent to IEC 60502), with conductor compliance to GB/T 3956 / IEC 60228 and flame-retardant testing per GB/T 18380 / IEC 60332-3. Common certifications include CCC (China), CE (Europe), ISO 9001, RoHS, and VDE/TUV for specific international markets.