0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

Basic Properties

country of origin
China
brand name
TD
certificate
CE/ISO/CCC
product model
3x16mm²

Trading Properties

moq
1 Meter
payment method
L/C,T/T
supply capacity
5000 Meters Per Month

Product Summary

0.6/1kV ZC-YJV 3x16mm² Stranded Copper Conductor XLPE Insulation PVC Outer Sheath Low Voltage Power Cable Technical Datasheet — ZC-YJV 0.6/1 kV 1×16 mm² 1. Cable Designation & Meaning Code Meaning ZC​ Flame retardant, Class C (bundled combustion test) YJ​ XLPE (cross-linked polyethylene) insulation ...

Product Details

Highlight:

1kV 3 Cores Cable

,

3 Cores Cable 3x16mm2

,

stranded copper cable XLPE Insulation

Conductor:
Bare Annealed Copper, Class 2 Stranded​ (7×∅1.70 Mm Typical); Compacted Circular For Single Core
Insulation:
XLPE Compound, Extruded (black / Red / Blue Etc. On Request)
Insulation thickness:
0.7 Mm​ (GB/T 12706.1, 10/16 Mm² Class)
Filler / binder:
Generally None For Single-core; Thin Non-hygroscopic Binder Tape Optional
Outer sheath:
Flame-retardant PVC​ Compound (ZC Grade)
Sheath thickness:
1.4 Mm​
Conductor construction:
Class 2, 7×∅1.70 Mm​ (typical)
Conductor nominal area:
16 Mm²
Conductor diameter (approx.):
5.0 Mm
Diameter over insulation (approx.):
6.4 Mm
Overall cable diameter:
8.7 – 9.9 Mm
Approx. weight:
201 – 221 Kg/km
Long-term service temperature rating:
90 °C
Short-circuit temperature rating (≤5 s):
250 °C​
Volume resistivity @90 °C:
10¹² Ω·cm (typical XLPE)

Product Description

0.6/1kV ZC-YJV 3x16mm² Stranded Copper Conductor XLPE Insulation PVC Outer Sheath Low Voltage Power Cable

 

Technical Datasheet — ZC-YJV 0.6/1 kV 1×16 mm²

1. Cable Designation & Meaning

 

Code

Meaning

ZC​

Flame retardant, Class C (bundled combustion test)

YJ​

XLPE (cross-linked polyethylene) insulation

V​

PVC (polyvinyl chloride) outer sheath

0.6/1 kV​

Rated voltage U₀/U = 600/1000 V; max. system voltage Uₘ = 1.2 kV

1×16 mm²​

Single core, nominal copper conductor area 16 mm²

Construction​

Unarmoured, non-screened, round cable

2. Applicable Standards

  • GB/T 12706.1-2020​ (equivalent to IEC 60502-1) — Extruded insulation power cables ≤ 1 kV
  • GB/T 3956 / IEC 60228​ — Conductors (Class 2)
  • GB/T 19666-2019​ — Flame retardant & fire resistant cables
  • GB/T 18380.3​ — Bundled flame propagation test (Class C)

关键参数已核实,16mm² 有几个重要差异点必须先说明(与前面 120/185 大截面不同):

  • 绝缘标称厚度 = 0.7 mm(GB/T 12706.1,10/16 mm² 档)——这是正确值.注:部分招标文件把 PVC/XLPE 分开规定,XLPE 16mm² 为 0.7 mm
  • 护套标称厚度 = 1.4 mm(单芯 16mm²,1.5–35 mm² 档均取 1.4)
  • 导体 = Class 2 绞合铜,7×∅1.70 mm(16mm² ≤35mm² 可实心/绞合,GB/T 3956 最少 7 根)
  • 导体直流电阻 ≤1.15 Ω/km(20℃,GB/T 3956 Class 2)
  • 外径 ≈ 9.3 mm,重量 ≈ 201–221 kg/km(多家样本一致,ZC-YJV 约 214)
  • 载流量:空气中 ≈ 100–115 A(30℃单根单芯),直埋 ≈ 125 A(20℃)——注意:单芯 16mm² 直埋反而高于空气中(典型样本表值 125/99 铜)

下面交付完整英文数据表.


Technical Datasheet — ZC-YJV 0.6/1 kV 1×16 mm²

1. Cable Designation & Meaning

 

Code

Meaning

ZC​

Flame retardant, Class C (bundled combustion test)

YJ​

XLPE (cross-linked polyethylene) insulation

V​

PVC (polyvinyl chloride) outer sheath

0.6/1 kV​

Rated voltage U₀/U = 600/1000 V; max. system voltage Uₘ = 1.2 kV

1×16 mm²​

Single core, nominal copper conductor area 16 mm²

Construction​

Unarmoured, non-screened, round cable

2. Applicable Standards

  • GB/T 12706.1-2020​ (equivalent to IEC 60502-1) — Extruded insulation power cables ≤ 1 kV
  • GB/T 3956 / IEC 60228​ — Conductors (Class 2)
  • GB/T 19666-2019​ — Flame retardant & fire resistant cables
  • GB/T 18380.3​ — Bundled flame propagation test (Class C)

3. Product Components / Construction (inside → outside)

  1. Conductor​ — Bare annealed copper, Class 2 stranded​ (7×∅1.70 mm typical); compacted circular for single core
  2. Conductor screen​ — Not required for 0.6/1 kV Class 2; normally omitted
  3. Insulation​ — XLPE compound, extruded (black / red / blue etc. on request)
  4. Insulation thickness (nominal)​ — 0.7 mm​ (GB/T 12706.1, 10/16 mm² class)
  5. Filler / binder​ — Generally none for single-core; thin non-hygroscopic binder tape optional
  6. Outer sheath​ — Flame-retardant PVC​ compound (ZC grade)
  7. Sheath thickness (nominal)​ — 1.4 mm​
  8. Sheath colour​ — Black (standard); other colours available
  9. Armour​ — None
  10. Metallic screen​ — None

4. Dimensional Data

 

Item

Typical value

Remarks

Conductor nominal area

16 mm²

—

Conductor construction

Class 2, 7×∅1.70 mm​ (typical)

min. 7 wires per GB/T 3956

Conductor diameter (approx.)

5.0 mm​

 

Insulation nominal thickness

0.7 mm​

 

Diameter over insulation (approx.)

6.4 mm

5.0 + 2×0.7

Sheath nominal thickness

1.4 mm​

 

Overall cable diameter

8.7 – 9.9 mm​

Typical 9.3 mm; range 8.7–9.9 across makers

Approx. weight

201 – 221 kg/km​

201 (EVER), 202 (gbt12706), 204 (Walsin), 210 (ZC-YJV structure table), 214 (ZC-YJV), 221.6 (JCCC)

Cable shape

Round

—

 

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

5. Insulation Data

  • Material:​ XLPE (cross-linked polyethylene)
  • Nominal thickness:​ 0.7 mm (GB/T 12706.1, 16 mm² at 0.6/1 kV)
  • Long-term service temperature rating:​ 90 °C​
  • Short-circuit temperature rating (≤5 s):​ 250 °C​
  • Emergency overload temperature:​ 105–130 °C (limited duration, general XLPE practice)
  • Dielectric strength:​ Pass 3.5 kV AC / 5 min routine test; 4.0 kV type test
  • Volume resistivity @90 °C:​ ≥ 10¹² Ω·cm (typical XLPE)
  • Insulation resistance:​ ≥ 100 MΩ·km @20 °C (500 V megger); constant R₀·L ≈ 3.67 MΩ·km @90 °C

6. Electrical Parameters

 

Parameter

Value

Source / Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV​

Routine test (some makers 4.0 kV)

Type-test voltage

4.0 kV

IEC 60502 practice

DC resistance @20 °C (Class 2 Cu)​

≤ 1.15 Ω/km​

GB/T 3956 / IEC 60228 max

AC resistance @90 °C (est.)

≈ 1.50 Ω/km

Copper temp. coefficient

Recommended current rating — in air (30 °C, single circuit, single-core, 25 ℃ ref.)

≈ 100–115 A​

100 (河南太平洋), 115 (金环宇单芯); typical design ≈ 105–115 A

In air — per common sample table (25 ℃)

125 A

copper

In air (40 ℃)

≈ 105 A

 

Direct buried / in soil (20 ℃)

≈ 125 A​

125 (JCCC/河南太平洋); 99 (玖开 Al/Cu mixed note)

Trefoil (air / ground)

84 / 98 A

reference, NYY type

Flat (air / ground)

87 / 101 A

reference

Short-circuit current capacity (1 s adiabatic, Cu, 250 °C)

≈ 1.84 kA​

reference

Inductance

Trefoil ≈ 0.327 mH/km; Flat ≈ 0.374 mH/km

reference

Frequency

50/60 Hz AC (DC usable)

—

 

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

 

7. Temperature Characteristics

  • Max. conductor operating temperature (continuous):​ 90 °C​
  • Max. conductor temperature during short circuit (≤5 s):​ 250 °C​
  • Emergency overload temperature:​ 105 °C (limited duration)
  • Min. ambient temperature during installation:​ 0 °C​ (below 0 °C requires pre-heating)
  • Service ambient temperature range:​ −20 °C to +90 °C (sheath/environment)
  • Flame retardant class:​ Category C, bundled flame test, self-extinguishing, limited flame spread per GB/T 19666

8. Mechanical & Installation Parameters

  • Minimum bending radius (single-core unarmoured):​ ≥ 15 × overall diameter​ (single-core; some sources state 20D for GB/T 12706) → ≈ 140–150 mm at Ø9.3 mm
  • Maximum pulling tension (copper conductor only):​ 50 N/mm² × 16 mm² = 800 N​
  • PVC sheath pulling limit:​ significantly lower — avoid direct sheath grip; use conductor pulling eye
  • Direct burial:​ Allowed in non-aggressive soil; recommended sand bed + warning tape, depth ≥ 0.7 m, conduit under roads
  • Magnetic conduit warning (AC single-core):​ Avoid magnetic steel pipe/conduit in AC circuits; use non-magnetic conduit or trefoil arrangement to prevent eddy-current heating
  • Conduit fill:​ Conduit ID ≥ 1.5 × cable OD
  • Elevation difference:​ No limitation for XLPE insulated cable

9. Material Specification Summary

  • Conductor:​ Cu ≥ 99.9 % annealed, Class 2, 7×∅1.70 mm (typical), IEC 60228 / GB/T 3956
  • Insulation:​ XLPE, 0.7 mm nom., rated 90 °C
  • Sheath:​ PVC (black, flame-retardant ZC type), 1.4 mm nom.
  • No armour, no metallic screen, no separate earth core

10. Scope of Application / Usage Range

The ZC-YJV 0.6/1 kV 1×16 mm²​ cable is intended for fixed installation​ in low-voltage power distribution & transmission systems up to 1.2 kV system voltage, where basic flame-retardant (Class C)​ performance is required but fire-survival (fire-resistant)​ function is not mandated.

Typical applicable locations:

  • Indoor power distribution rooms, switchboards, distribution boxes, and final sub-circuits
  • Cable trays, cable ducts, cable trenches & shafts in residential, commercial and public buildings
  • Lighting branch circuits and small-to-medium power equipment feeders​ (16 mm² is a standard size for lighting/utility circuits)
  • Fixed wiring in industrial plants, warehouses, and machinery feeders
  • Direct buried routes in non-aggressive soil with low mechanical impact
  • Street lighting, small PV/combiner and EV charger branch circuits (DC side requires polarity check)
  • High-rise buildings, metro/station auxiliary power, general civil projects requiring ZC flame-retardant grade​

Not suitable for:

  • Heavy tensile / armour-protected routes → use YJV22 / ZC-YJV22
  • Fire-survival emergency circuits → use NH-ZC-YJV
  • Highly corrosive / hydrocarbon-rich environments without extra barrier
  • Magnetic conduit AC single-core runs​ (eddy-current risk)
  • Long high-current feeders where voltage drop / 105 A limit governs (upsize to 25 mm²+)

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

11. Packing

  • Drum:​ Steel-wooden drum; common length 100–1000 m per drum (16 mm² flexible, long continuous lengths typical)
  • HS code (China):​ 8544 4921 (LV power cable, PVC sheath)

0.6/1kV 3 Cores Cable 3x16mm2 Stranded Copper Conductor XLPE Insulation PVC Outer Sheath

Key engineering notes for 16 mm²

  1. Insulation is only 0.7 mm​ — the same as 1.5 mm². This is correct per GB/T 12706.1 (the 10/16 mm² class). Do not apply the 1.2/1.6 mm values from 120/185 mm².
  2. Sheath is 1.4 mm​ (not 1.5/1.7 mm) — single-core 1.5–35 mm² share this value .
  3. Conductor is 7×1.70 mm​ for stranded (Class 2); solid Class 1 is also permitted for 16 mm² ≤ 35 mm² .
  4. Design current: ≈ 100 A (air) / ≈ 115–125 A (buried)​ — always apply correction for grouping, ambient temperature, and conduit fill; for a 30 kW motor (≈54 A) at 200 m, 16 mm² gives voltage drop ≈ 2.4 V (well within 19 V limit) .
  5. ZC ≠ NH:​ ZC is flame-retardant only, not fire-survival. For emergency/life-safety circuits, use NH-ZC-YJV.