2X1.5mm2 Flat Sheathed Wires PVC ST4 Copper Electrical Wire
Basic Properties
Trading Properties
Product Summary
Product Details
2X1.5mm2 Flat Sheathed Wires
,PVC ST4 Copper Electrical Wire
,Flat Sheathed Wires Copper
Product Description
300/500V White BVVB-2*1.5mm² Twin Solid Copper Core Electrical Wire PVC Insulation Household Wire
BVVB 2×1.5 mm² Copper Core PVC Insulated PVC Sheathed Flat Cable
Model decode (GB/T 5023 / JB/T 8734 / IEC 60227):
B = Building wire (fixed wiring) · V = PVC insulation · V = PVC sheath · B = Flat (parallel-core) construction.
Equivalent IEC name: 60227 IEC 10 (BVV) in flat form, or BS 6004 twin flat in UK context. Rated 300/500 V.
1. Identification & Standards
|
Item |
Specification |
|---|---|
|
Model |
BVVB 300/500V 2×1.5 mm² (also ZC-BVVB for flame-retardant Class C) |
|
Product Name |
Copper Conductor PVC Insulated PVC Sheathed Flat Sheathed Wire |
|
Rated Voltage U₀/U |
300/500 V AC (max. system voltage 550 V) |
|
Standards |
GB/T 5023.3 / GB/T 5023.7 · JB/T 8734.2-2016 · IEC 60227-3 / IEC 60227-7 · BS 6004 (UK equivalent) |
|
Conductor Class |
Class 1 solid (1/1.38 mm) or Class 2 stranded (7/0.52 mm or 30/0.25 mm) per order |
|
Certification |
CCC (China) · CE / RoHS on export versions |
|
Origin |
Anhui / China general mfr base |
2. Cable Construction (inside → outside)
|
Layer |
Material & Dimension (2×1.5 mm²) |
|---|---|
|
Conductor |
Annealed copper, Class 1 solid = 1/1.38 mm (Ø 1.38 mm); Class 2 option = 7/0.52 mm or 30/0.25 mm; cross-section 1.5 mm² |
|
Insulation |
PVC/D compound, nominal thickness 0.7 mm (min. 0.54 mm), tightly extruded on each core |
|
Core Layout |
Two insulated cores laid parallel (not twisted), flat formation |
|
Outer Sheath |
PVC/ST4 (or PVC/ST5) compound, nominal thickness 0.9 mm (min. 0.69 mm), overall flat jacket enclosing both cores |
|
Overall Dimensions |
4.4×7.0 mm (min) ~ 5.3×8.5 mm (max); typical reference 4.6×7.3 mm |
|
Approx. Weight |
61–71 kg/km (solid version ≈ 63–70.7 kg/km; stranded slightly higher) |
|
Core Colors |
Brown + Blue (standard IEC L/N); alt. Red + Black; custom on request |
|
Sheath Color |
White (most common for indoor), Black, Grey, Orange available |


3. Electrical & Thermal Parameters
|
Parameter |
Value |
|---|---|
|
Conductor DC resistance @ 20 °C |
≤ 12.1 Ω/km (Class 1 & Class 2, per GB/T 3956) |
|
Dielectric withstand test |
2000 V AC, 5 min, no breakdown |
|
Min. insulation resistance @ 70 °C |
≥ 0.011 MΩ·km |
|
Rated continuous conductor temp. |
70 °C (PVC/D) — some makers offer 90 °C BVVB-90 variant |
|
Short-circuit temp. (≤ 5 s) |
160 °C |
|
Min. installation / laying temp. |
0 °C (warm cable if colder; some compounds allow −15 °C service) |
|
Ambient service range |
−15 °C to +40 °C ambient (conductor ≤70 °C) |
Ampacity reference (2×1.5 mm², 300/500 V)
|
Condition |
Reference Ampacity* |
|---|---|
|
Single cable in free air, 30 °C ambient |
~18 A (per GB/T 5023 maker table) |
|
Single cable in free air, 40 °C ambient |
~14–15 A (×0.82 correction) |
|
Clipped to wall surface (30 °C) |
~16–17 A |
|
In conduit / trunking (30 °C, 2-core grouped) |
~13–14 A |

4. Mechanical & Safety Performance
|
Item |
Specification |
|---|---|
|
Min. bending radius |
4 × overall thickness (flat short axis) for D<25 mm → ≈ 4×4.6 = 18.4 mm; maker rule: ≥4D of major axis (~28 mm) conservative |
|
Flame retardant |
Passes GB/T 18380.1 / IEC 60332-1 (single vertical, self-extinguishing); ZC version = Class C bunch retardant per GB/T 19666 |
|
IP level |
IP40 (bare) — sheath protects against minor abrasion, dust, humidity; not waterproof |
|
Crush / abrasion |
PVC/ST4 sheath resists minor foot traffic compression, skirting-board clamping, painter scraping |
|
Smoke / halogen |
Standard PVC emits smoke + HCl when burned; not LSZH — for low-smoke use WDZ-BVVB |
|
Service life |
≥ 30 years indoor at ≤70 °C conductor |
|
Flexibility |
Class 1 solid = stiff, for fixed wiring only; Class 2 stranded = slightly easier to dress, still not flexible like RVV |


5. Product Performance Summary
BVVB 2×1.5 is the classic Chinese flat sheathed wire for surface-mounted fixed wiring. Its value proposition versus BV (single-core naked) and BVV (round sheathed):
-
Double protection in one piece — each core has PVC insulation + the whole assembly has a PVC sheath → resists moisture, dust, and minor mechanical knocks better than BV, without the bulky round profile of BVV.
-
Flat shape hugs walls — 4.6×7.3 mm cross-section sits flush under skirting boards, along tile edges, behind trunking lids; far neater than round BVV or conduit-run BV for retro-fit / visible runs.
-
1.5 mm² is the lighting-and-small-socket sweet spot — 18 A free-air rating covers 220 V lighting circuits, switch drops, 1 A–10 A socket branches, appliance cords back to a fused spur.
-
Solid core = stable termination — Class 1 1/1.38 mm conductor clamps cleanly under screw terminals in switches, choc-boxes, and distribution boards; no strand splay if ferrule omitted (though ferrule still recommended).
-
Cost-effective — cheaper than armoured or LSZH cables; the default choice for non-emergency indoor exposed wiring.
Trade-off: not for direct burial (PVC sheath not rodent/soil rated), not for moving equipment (solid core fatigues), not fire-survival (standard PVC), not UV-stable for permanent outdoor sun exposure without conduit.
6. Application Scope
Primary uses
-
Residential surface wiring: living-room/bedroom lighting switches, ceiling rose feeds, skirting-board socket spurs
-
Retrofit / renovation where chasing walls is unwanted — run flat along cornices, door frames, under carpets (protected)
-
Small commercial fit-out lighting circuits, signage feeds, shop display lighting
-
Household appliances fixed connection: extractor hood, water heater switch drop, wall-mounted AC indoor unit power (low-current branch, not the 16 A socket itself)
-
Instrumentation, thermostats, doorbell transformers, CCTV camera 220 V feeds (low current)
-
Temporary site offices, exhibition booths, market stalls (indoor/under-canopy)
Typical projects: apartments & villas · office partitions · retail shops · school classrooms · hotel guest-room wiring · old-building rewire where conduit is impractical.
Not suitable for: direct burial · outdoor sun-exposed runs > few months · emergency/fire-alarm circuits (use NH-BV or WDZ-BYJ) · flexible appliance cords (use RVV) · 16 A+ socket radial circuits on long runs (use 2.5 mm² BV/BVVB) · 450/750 V industrial feeds (BV 450/750 is fine, but BVVB 2×1.5 is 300/500 V only).

7. Installation Notes (2×1.5 flat)
|
Item |
Practice |
|---|---|
|
Mounting |
Clip to wall every 300–400 mm (plastic saddle/clip matching flat profile); not zip-tie on round surfaces |
|
Bending |
4× short-axis min (~18 mm); avoid creasing the flat edge — use gentle sweeps |
|
Termination |
Strip insulation 8–10 mm; solid core into screw terminal directly, or bootlace ferrule (DIN 46228 1.5 mm²) for panel use |
|
Junction |
Use choc-box or PVC junction box; never twist-and-tape in open air |
|
Conduit? |
Discouraged — flat shape scrapes sheath in round conduit; if conduit mandatory, use round BVV or single BV in conduit instead |
|
Pre-energizing |
500 V DC megger L-L, L-outer-sheath ≥ 1 MΩ; visual check sheath not nicked at clips |
|
Low temp |
Below 0 °C, warm cable before bending to avoid sheath cracking |
8. Selection Cross-Reference
|
Need |
Better choice |
|---|---|
|
Concealed in wall / conduit |
BV 1.5 mm² (single-core, 450/750 V) |
|
Round sheathed, same 2×1.5 |
BVV 2×1.5 (round, bulkier) |
|
Flexible / appliance cord |
RVV 2×1.5 (Class 5 stranded) |
|
Flame-retardant Class C |
ZC-BVVB 2×1.5 |
|
Low-smoke halogen-free |
WDZ-BVVB 2×1.5 (LSZH sheath) |
|
16 A socket circuits |
BVVB 2×2.5 or BV 2.5 in conduit |
|
3-core (L+N+PE) |
BVVB 3×1.5 |
Quick spec snapshot
-
Model: BVVB 300/500V 2×1.5 mm² (Class 1: 1/1.38 mm, or Class 2: 7/0.52 mm)
-
Build: Cu + PVC ins 0.7 mm + flat parallel + PVC sheath 0.9 mm
-
OD: 4.4×7.0 ~ 5.3×8.5 mm (typ. 4.6×7.3 mm)
-
Weight: ~63 kg/km · R₂₀: ≤12.1 Ω/km
-
Ampacity: ~18 A free air / ~14 A conduit (30 °C)
-
Temp: 70 °C cont. / 160 °C sc (5 s) / lay ≥0 °C
-
Bend: ≥4× thickness · Standards: GB/T 5023.3+7, JB/T 8734.2, IEC 60227-3/7