DC (PV) Solar Cable H1Z2Z2-K 4.0 mm² Single Core Tinned Copper XLPE/XLPO Insulated
H1Z2Z2-K 1×4.0 mm² Photovoltaic (PV) DC Solar Cable.
H = Harmonised EU designation · 1Z2Z2 = halogen-free (HFFR) insulation + halogen-free (HFFR) sheath, both cross-linked · K = flexible Class 5 conductor · 1×4.0 mm² = single-core, 4 mm².
This is the current-generation replacement of legacy PV1-F (2 PfG 1169), built for 1500 V DC photovoltaic systems.
1.Cable Construction (inside → outside)
|
Layer |
Material & Dimension (1×4 mm²) |
|---|---|
|
Conductor |
Class 5 flexible tinned copper, 56/0.285 mm (some makers 56/0.30 mm or 56/0.31 mm) → conductor Ø ≈ 2.4–2.6 mm |
|
Insulation |
Electron-beam cross-linked polyolefin (XLPO / XL-HFFR), halogen-free, nominal thickness 0.7 mm (min. ~0.53 mm) |
|
Outer Sheath |
Electron-beam cross-linked polyolefin (XLPO / XL-HFFR), halogen-free, flame-retardant, nominal thickness 0.8 mm (min. ~0.58 mm) |
|
Overall diameter |
5.6 mm nominal (range 5.2–6.0 mm by maker) |
|
Weight |
55–62 kg/km (typ. 57 kg/km) |
|
Colors |
Black (standard), Red (positive string), optional White/Blue stripe |
|
Printing |
|
Both insulation and sheath are double-layer cross-linked HFFR — no PVC anywhere.


2.Electrical Parameters
|
Parameter |
Value |
|---|---|
|
Rated voltage (DC) |
1.5/1.5 kV (U₀/U), max. operating 1.8 kV DC |
|
Rated voltage (AC) |
1.0/1.0 kV (U₀/U), Um 1.2 kV |
|
High-voltage test |
6.5 kV AC, 5 min (routine), no breakdown |
|
Spark test |
10 kV AC on insulation line |
|
Conductor DC resistance @ 20 °C |
≤ 5.09 Ω/km (Class 5, IEC 60228) |
|
Conductor DC resistance @ 90 °C |
≈ 6.6 Ω/km |
|
Min. insulation resistance @ 90 °C |
≥ 0.58 MΩ·km |
|
Short-circuit temp. (5 s) |
250 °C max |
|
Capacitance (L-E, approx.) |
~0.12 µF/km |


3.Thermal & Current-Carrying Capacity
|
Condition |
Ampacity* |
|---|---|
|
Single cable in free air, ambient 30 °C, conductor 90 °C |
≈ 60 A |
|
Single cable in free air, ambient 60 °C, conductor 120 °C |
55 A |
|
On surface (single cable, 60 °C amb.) |
52 A |
|
Two adjacent cables on surface (60 °C amb.) |
44 A |
|
In conduit / pipe / duct (60 °C amb.) |
33 A |
* Per EN 50618 maker tables (Nexans, Kuka, Midsummer, etc.).
Temperature correction (free-air base at 60 °C amb. = 55 A): ×1.00 @60 °C · ×0.91 @70 °C · ×0.82 @80 °C · ×0.71 @90 °C · ×0.58 @100 °C.
-
Continuous conductor temp.: 90 °C (normal service)
-
Peak conductor temp.: 120 °C for up to 20,000 h cumulative (Arrhenius life model) → design life 30–40 years outdoor.
-
Ambient range (installation & service): −40 °C to +90 °C; lay-in min. −25 °C to 0 °C depending on compound.
-
Min. bending radius: 4× OD fixed (~22 mm), 5× OD flexing (~28 mm).



4.Mechanical, Chemical & Environmental Performance
-
Halogen-free: IEC 60754-1 (halogen acid gas ≈ 0; pH > 4.3, conductivity < 10 µS/mm)
-
Low smoke: IEC 61034-2, light transmittance > 60%
-
Flame retardant: IEC 60332-1-2 (single cable, self-extinguishing)
-
UV resistance: EN 50289-4-17 Method A, 720 h+ UV, plus maker 4000 h prestige tests — suitable for permanent outdoor exposure without conduit.
-
Ozone resistance: EN 50396 (cable intact after ozone chamber)
-
Water resistance: AD8 per EN 50525-2-21 Annex E — permanent immersion / direct burial acceptable without extra jacket.
-
Hydrolysis / salt mist / ammonia: pass EN 60068-2-78 damp heat, HD 60364-5-52 condition AH3
-
Tensile / bending fatigue: 100,000 reverse-bend cycles (Nexans class test), flexible Class 5 survives panel tracking movement and installer pulls
-
MC4 compatibility: 4 mm² mates with standard MC4 (4–6 mm² crimp) connectors.
-
Anticipated service life: ≥ 25 years (TÜV), 30–40 years typical per Arrhenius extrapolation.


5.Product Performance Summary
H1Z2Z2-K 1×4 mm² is the default DC string cable for modern 1500 V photovoltaic systems. Its three decisive advantages over legacy PV1-F or general-purpose H07 cables:
-
1500 V DC rating with 1800 V margin — thicker XLPO wall suppresses partial discharge in 1500 V strings; PV1-F (1000 V DC) is not allowed in 1500 V systems.
-
Double cross-linked HFFR (insulation + sheath) — electron-beam cured, does not melt or flow at 120 °C, zero halogen, low smoke, AD8 submersible. Survives roof-top thermal cycling, desert UV, coastal salt fog, and floating-PV humidity in one product.
-
Class 5 tinned copper — tin coating prevents copper oxidation/corrosion at MC4 contacts over 25+ years; fine stranding tolerates panel micro-movement and tight tray dressing.
Trade-off: stiffer than rubber cord, not intended for continuous flexing like a drag-chain cable; 4 mm² is best for short-to-medium string runs (≤ ~30 m one-way at 15 A) — for longer runs or higher Isc, move to 6 mm².
6. Application Scope
-
PV module → combiner box / string inverter DC interconnect (the primary use)
-
Rooftop residential, commercial, and industrial PV (≤ 1500 V DC string voltage)
-
Utility-scale ground-mounted solar farms, single-axis tracker wiring
-
Floating photovoltaic (FPV) — AD8 water resistance is critical here
-
Battery energy storage (BESS) DC side, charge controller to battery bank (low-voltage 12–48 V too, with correct fusing)
-
Solar pump, solar street-light, off-grid cabin DC wiring
-
MC4-terminated panel harnesses and extension leads
Not suitable for: AC mains distribution (>1 kV AC), conduit-only building wiring inside dwellings (use H07Z-K etc.), continuous flexing machinery, direct connection to grid without inverter.


7.Installation Notes (1×4 mm²)
|
Item |
Practice |
|---|---|
|
Bending |
4×OD fixed (~22 mm), 5×OD flexing (~28 mm) |
|
Supports |
Clip to rail or tray every ≤ 400 mm horizontal; avoid sharp edge contact (use edge guards) |
|
Termination |
Strip ~8–10 mm, use MC4 crimp contact 4–6 mm², never tin-and-screw on PV DC |
|
Earthing |
PV DC is ungrounded/floating; equipotential bonding done at inverter/combiner, not on cable sheath |
|
Pulling |
By conductor or factory MC4; do not pull by sheath alone on long runs |
|
Temperature |
Lay ≥ 0 °C (or use cold-flex compound); service −40 to +90 °C ambient |
|
Direct burial |
Allowed (AD8); for rodent zones add sand bed or warning tape, no armour needed |
|
Pre-commissioning |
1000 V DC megger L-(shield/nil) ≥ 100 MΩ; visual check of MC4 seal |
8. Selection Cross-Reference
|
Need |
Better choice |
|---|---|
|
Legacy 1000 V DC system, cost-driven |
PV1-F 1×4 (but 2 PfG 1169 withdrawn, not for new EU projects) |
|
Longer string / higher Isc (>15 A) |
H1Z2Z2-K 1×6 mm² (70 A ref.) |
|
10–20 A commercial string, lower drop |
H1Z2Z2-K 1×10 mm² |
|
Twin-core panel harness |
H1Z2Z2-K 2×4 mm² (parallel ± run) |
|
Aluminium conductor (cost) |
H1Z2Z2-K Al 1×4 — rare, avoid on MC4 (galvanic) |
|
AC inverter output side |
Switch to N2XH / H07Z-K per LV regs, not H1Z2Z2-K |
Quick spec snapshot
-
Model: H1Z2Z2-K 1×4 mm² (EN 50618 / IEC 62930)
-
Rating: 1.5/1.5 kV DC (max 1.8 kV), 1.0/1.0 kV AC
-
Build: 56/0.285 mm tinned Cu Class 5 + 0.7 mm XLPO ins + 0.8 mm XLPO HFFR sheath
-
OD: 5.6 mm · Weight: ~57 kg/km
-
R₁₀: ≤ 5.09 Ω/km · Ampacity: 55 A @60 °C air / 44 A two-on-surface
-
Temp: −40…+90 °C (120 °C peak 20 kh) · Bend: 4D fixed
-
Fire/Env: LSZH Dca-s1,d2,a1, AD8, UV 720h+, ozone OK, 30-yr life