RVVP 3x6.0mm² Shielded Control Cable for High Power Equipment & Industrial Control
RVVP 3x6.0mm² Shielded Control Cable for High Power Equipment & Industrial Control
Riepilogo Prodotto
RVVP 3x6.0mm² Shielded Control Cable for High Power Equipment & Industrial Control Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 3×6.0 mm² Three cores of 6.0 mm² copper conductor Construction : Three 6.0 mm² fine-stranded copper ...
Dettagli del prodotto
Conductor (×3):
Copper, flexible (Class 5), nominal 84×∅0.30 mm (6.0 mm²), conductor Ø ≈ 4.0 mm per core
Insulation:
PVC (Type TI2), nominal thickness 0.8 mm, min. thickness 0.62 mm
Lay-up:
Three insulated cores twisted together
Shield:
Pure copper braid, coverage ≥ 80%, nominal 16×8/0.10 mm
Outer sheath:
PVC (Type TM2), nominal thickness 1.2 mm, min. thickness 0.92 mm
Conductor nominal area:
6.0 mm² (Cu) × 3
Number of cores:
3
Conductor material:
Copper (Cu)
Conductor class:
Class 5 flexible
Conductor construction:
84×∅0.30 mm per core
Conductor diameter:
≈ 4.0 mm per core
Insulation thickness (nom.):
0.8 mm
Insulation thickness (min.):
0.62 mm
Shield coverage:
≥ 80%
Outer sheath thickness (nom.):
1.2 mm
Outer sheath thickness (min.):
0.92 mm
Overall cable diameter:
12.5 – 14.5 mm
Design outer diameter:
≈ 13.6 mm
Approx. weight:
330 – 410 kg/km
Design weight:
≈ 372 kg/km
Cable shape:
Round
Descrizione del prodotto
RVVP 3x6.0mm² Shielded Control Cable for High Power Equipment & Industrial Control Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 3×6.0 mm² Three cores of 6.0 mm² copper conductor Construction : Three 6.0 mm² fine-stranded copper conductors, PVC insulation on each core, laid up together, tinned copper braid shield (≥80% coverage) over the laid-up cores, PVC outer sheath. Applicable Standards GB/T 5023.5-2008 / IEC