RVVP 4x4.0mm² Shielded Control Cable for High Power Motor and Equipment Control
RVVP 4x4.0mm² Shielded Control Cable for High Power Motor and Equipment Control
Ürün Özetleri
RVVP 4x4.0mm² Shielded Control Cable for High Power Motor and Equipment Control Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 4×4.0 mm² Four cores of 4.0 mm² copper conductor Construction : Four 4.0 mm² fine-stranded copper conductors, ...
Ürün Detayları
Vurgulamak:
RVVP 4x4.0mm² shielded control cable
,4 core flexible motor control cable
,high power equipment control cable
Conductor (×4):
Bakır, esnek (Sınıf 5), nominal 56×∅0,30 mm (4,0 mm²), iletken Ø ≈ damar başına 3,2 mm
Insulation:
PVC (Tip TI2), nominal kalınlık 0,8 mm, min. kalınlık 0,62 mm
Lay-up:
Birlikte bükülmüş dört yalıtımlı çekirdek
Shield:
Saf bakır örgü, kapsama alanı ≥ %80, nominal 16×8/0,10 mm
Outer sheath:
PVC (Tip TM2), nominal kalınlık 1,2 mm, min. kalınlık 0,92 mm
Conductor nominal area:
4,0 mm² (Cu) × 4
Number of cores:
4
Conductor material:
Bakır (Cu)
Conductor class:
Sınıf 5 Esnek
Conductor construction:
Çekirdek başına 56×∅0,30 mm
Conductor diameter:
≈ çekirdek başına 3,2 mm
Insulation thickness (nom.):
0,8 mm
Insulation thickness (min.):
0,62 mm
Shield coverage:
≥ %80
Outer sheath thickness (nom.):
1.2 mm
Outer sheath thickness (min.):
0,92 mm
Overall cable diameter:
13,2 – 15,5 mm
Design outer diameter:
≈ 14,5 mm
Approx. weight:
310 – 390 kg/km
Design weight:
≈ 350 kg/km
Cable shape:
Yuvarlak
Ürün Açıklaması
RVVP 4x4.0mm² Shielded Control Cable for High Power Motor and Equipment Control Cable Designation & Meaning Code Meaning R Flexible cord V PVC insulation V PVC sheath P Copper braid shield 4×4.0 mm² Four cores of 4.0 mm² copper conductor Construction : Four 4.0 mm² fine-stranded copper conductors, PVC insulation on each core, laid up together, tinned copper braid shield (≥80% coverage) over the laid-up cores, PVC outer sheath. Applicable Standards GB/T 5023.5-2008 / IEC 60227